RELIANCE SERIES COMPACT LED EMERGENCY LIGHT
INSTALLATION INSTRUCTION
SELF-DIAGNOSTIC/SELF-TESTING OPTION
1. When AC power is supplied to fixture, the unit will automatically
initiate a self-test and self-diagnostic test as follows:
a. Verifies battery disconnection, charger board failure, lamps failure and transformer failure
at ever 5 seconds.
b. One-minute self-testing every month.
c. 30 minutes self-testing on the 6th month of the year after installation.
d. 90 minutes self-testing on the 12th month of the year after installation.
2. Dual color LED lamp indicator shows the following status:
a. Green color: ON/Ready
b. Red color: Service Alert
c. Service Alert LED Code (Red color LED lamp indicator)
O
One blink ON/pause (4 sec)
O O
Two blinks ON/pause (4 sec)
O O O
Three blinks ON/pause (4 sec)
O O O O
Four blinks ON/pause (4 sec)
O O O O O
Five blinks ON/pause (4 sec)
O O O O O O
Six blinks ON/pause (4 sec)
RL2LED
Blinking: Test
SAVE THESE INSTRUCTIONS
31 Waterloo Ave • Berwyn, PA • 19312 U.S.A
Telephone: (610) 647-8200 • Email: support@isolite.com
Battery is not connected
Battery is shorted or voltage drops below acceptable level
Charger board circuit fault
Transformer fault (transformation circuit fault)
Emergency lamp fault
Remote head's emergency lamp fault (if installed)
1
Need help?
Do you have a question about the RELIANCE Series and is the answer not in the manual?
Questions and answers