Electronic overload relay

Advertisement

Electrical
Input Voltage
Frequency
Motor Full Load Amp Range
Power Consumption
Output Contact Rating SPDT (Form C)
Expected Life
Mechanical
Electrical
Accuracy at 25° C (77° F)
Voltage
Current
GF Current
Timing
Repeatability
Voltage
Current
Trip Times (Those not shown have user selectable trip times.)
Ground Fault Trip Time
101%-200% of Setpoint
201%-300% of Setpoint
301%-400% of Setpoint
401% or Greater
Current Unbalance Trip Times
% Over Setpoint
1%
2%
3%
4%
5%
6%
10%
15%
Safety Marks
UL
CE
Standards Passed
Electrostatic Discharge (ESD)
Radio Frequency Immunity (RFI),
Conducted
Radio Frequency Immunity (RFI),
Radiated
Fast Transient Burst
Surge
IEC
MODEL 777 SPECIFICATIONS
200-480VAC, 3-phase (Standard)
500-600VAC for Model 777-575
50-60 Hz
2-25A, 3-phase (Looped conductors required)
25-90A, 3-phase (Direct)
80-800A, 3-phase (External CTs)
10W (Maximum)
Pilot duty rating: 480VA @ 240VAC General
purpose: 10A @ 240VAC
1 x 10
1 x 10
±1%
±3%(<100A Direct)
±15%
5% ±1 second
±0.5% of nominal voltage
±1% (<100A direct)
Trip time
8 seconds ±1 second
4 seconds ±1 second
3 seconds ±1 second
2 seconds ±1 second
Trip time
30 seconds
15 seconds
10 seconds
7.5 seconds
6 seconds
5 seconds
3 seconds
2 seconds
UL508, UL1053
IEC 60947-1, IEC 60947-5-1
IEC 1000-4-2, Level 3, 6kV contact, 8kV air
IEC 1000-4-6, Level 3 10V/m
IEC 1000-4-3, Level 3 10V/m
IEC 1000-4-4, Level 3, 3.5 kV input power
1000-4-5 Level 3, 2kV line-to-line; Level 4, 4kV
line-to-ground
- 12 -
6
operations
5
operations at rated load
1/05