Solution: Use the disconnection detection function to locate the disconnection point. The
procedure is as follows:
Step 1 Log in to the FusionSolar app and tap the plant name on the Home screen to access the
plant screen.
Step 2 Choose Layout, tap Disconnection detection to check optimizer disconnection, and rectify
the fault based on the result.
----End

3.5 Faults in the Multiple-Inverter Scenario

3.5.1 Impedance Is Normal

Symptom: Multiple inverters are used onsite. The positive and negative cables of
optimizers are not routed close to each other. The measured impedance of each PV string
connected to each inverter matches the number of connected optimizers, and either of the
following conditions is met:
1.
2.
Cause: Crosstalk occurs. The customer does not connect cables in accordance with the user
manual, which requires that the positive and negative cables of the optimizers be routed
close to each other to reduce the impact of EMC.
Issue 01 (2024-1-2)
The number of optimizers found by certain inverters is greater than the number of
connected optimizers, and the number of optimizers found by other inverters is less
than the number of connected optimizers.
An inverter does not find all optimizers connected to it. The optimizers that are not
found were connected to another inverter before.