Table of Contents

Advertisement

Quick Links

MONITORING - T2S ETH WITH INVIEW X
User Manual V3.0
THE NEW GENERATION OF MONITORING
EXTENDED LOG CAPABILITIES
WEB-BASED USER INTERFACE
Copyright © 2023. Construction electroniques + telecommunications S.A.
All rights reserved. The contents in document are subject to change without notice.
The products presented are protected by several international patents and trademarks.
Address: CE+T S.a, Rue du Charbonnage 12, B 4020 Wandre, Belgium
www.cet-power.com - info@cet-power.com
Contact us:  www.cet-power.com
|
Follow us on social media:

Advertisement

Table of Contents
loading

Summary of Contents for CE+T Power T2S ETH WITH INVIEW X

  • Page 1 MONITORING - T2S ETH WITH INVIEW X User Manual V3.0 THE NEW GENERATION OF MONITORING • EXTENDED LOG CAPABILITIES • WEB-BASED USER INTERFACE Copyright © 2023. Construction electroniques + telecommunications S.A. All rights reserved. The contents in document are subject to change without notice.
  • Page 2: Table Of Contents

    7.3.2 Main Area ........................7.3.3 Toolbar ........................... Pages and Feature........................7.4.1 AC IN ..........................7.4.2 DC IN ..........................7.4.3 AC Out ..........................7.4.4 System ........................... 7.4.5 Module ........................... 7.4.6 Events ..........................- Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 3 15. Annex 2: Module alarms - T2S ETH ....................... 16. Annex 3: Configuration parameters - T2S ETH ..................16.1 Montioring ........................... 16.2 Inputs/Relays ..........................16.3 SNMP ............................16.4 Modbus ............................16.5 Power............................- Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 4 17.3.4 Validity and Unit description (A2):..................17.4 Modbus over RTU ........................17.4.1 Introduction ........................17.4.2 Modbus RTU - Testing ....................17.5 ModBus Table ..........................17.5.1 Data table ........................17.5.2 Alarm Table ........................- Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 5 Added SNMP details 25/05/2020 Additional information included 18/06/2020 Additional information included 19/05/2022 33 & 70 Added Digital input information and updated an action 04/10/2023 Replaced Catena with Inview X - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 6: Introduction To Ce+T

    Introduction to CE+T 1. Introduction to CE+T CE+T Power designs, manufactures, and markets a range of products for industrial operators with mission critical applications, who are not satisfied with existing AC backup system performances and related maintenance costs. Our product is an innovative AC backup solution that unlike most UPS’s available.
  • Page 7: Abbreviations

    Protective Earth (also called Main Protective Conductor) Power Regular SNMP Simple Network Management Protocol TCP/IP Transmission Control Protocol/Internet Protocol True Redundant Structure Twin Sine Innovation Urgent Alarm Universal Serial Bus - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 8: Warranty And Safety Conditions

    • When handling the system/units pay attention to sharp edges. * These instructions are valid for most CE+T Products/Systems. Some points might however not be valid for the product described in this manual. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 9: Installation

    Earthing must be carried out prior to energizing the system. Earthing shall be made according to local regulations. 3.3.3 Other • Isolation test (Hi-Pot) must not be performed without instructions from the manufacturer. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 10: Pre-Cautions Before Maintenance

    To download the latest: • Documents - www.cet-power.com • Softwares - my.cet-power.com - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 11: Product Code And Identification

    The part number, serial number, and burn in date are essential information when you contact CE+T to get help in commissioning or in troubleshooting or when the item is sent back for repair. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 12: Introduction

    T2S also supports Modbus Serial communication (RTU) and SNMP v1 Communication. This new monitoring device provides a graphical user interface, embeds an SNMPv2c/SNMP v3 agent, and Modbus TCP support with Inview X. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 13: Hardware

    The RJ45 is a standard ETH connector that could be connected to any IPv4 network. T2S ETH software can be upgraded using the Micro SD card. The latest device softwares are available in my.cet-power.com - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 14: Leds Code During Operations

    No micro SD card or file *.bcf not valid or not present File *.acf found Installation *.saf please wait System error or no micro SD card Configuration.ini found waiting network - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 15: Signaling Information

    If the T2S ETH is included in a complete system, the alarm terminals will be located somewhere in the system. For exact location, refer to the system user manual. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 16 (i.e., when the external Volt-free contact is closed). 6.1.2.3 Communication An RJ45 connector is present at rear of the shelf and can be used for Candis display and Modbus (RTU) communication. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 17 Currently, no protocol is available for customer use on CAN bus connection and it is dedicated for Candis accessory. The unregulated +12 V power supply is designed for powering CE+T accessories and should not be used for any other purpose. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 18: Monitoring - Inview

    ○ It is dedicated to T2S ETH and does not connect to the network • Power: The unregulated separate +48 V power supply is required for powering Inview X and this power should not be shared with other devices. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 19: Wiring

    DIG IN RS485 ISO CAN 48Vdc 0 ,5 PROG EXTERNAL (AC OUTPUT OPTION REMOTE HELP CONTACT) (OPTIONAL) TO REMOVE WHEN EXTERNAL REMOTE USED EARTH FROM FROM AC/DC CONV(A3) - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 20: User Interface

    Provides information about the corresponding screen. In some screens, left and right navigation buttons appear, indicating more screens are present. Navigation arrows for the next and previous pages. Up and down arrows appear on some screens, indicating more information is present. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 21: Menu Structure

    AC OUT details • Voltage • Current • Voltage • Current • Voltage • Current • Frequency • Power • Frequency • Active • Active power power • Apparent Power - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 22: Inview X Web Ui

    • System setting and configuration (password protected). • System status and information display. • System alarms and events log file. In addition to these, there is minimal information available via “touch screen display”. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 23: T2S Web Ui

    “Passwords”, page 34. In case of lost password, please refer to FAQ at page 63 7.3 Interface Areas 1  Banner 2  Main Area 3  Tool bar - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 24: Banner

    Given the system can be configured with up to 2 DC groups, power is the total power consumption. Flowing (moving white ball) from this item to the system means power is taken from the DC source. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 25: Toolbar

    This leads to the file management page. Files such as configuration, update and log download. • Parameters The parameters page allows user to change every parameter related to the system. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 26: Pages And Feature

    This page displays the measurements made by the modules on the DC input. Available values are: Measure Unit Voltage (V) Volts (V) Current (I) Ampere (A) Input Power(P) Kilo Watts (kW) - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 27: Ac Out

    Each module’s information can be accessed by clicking the corresponding button. A legend is always present to recall the color scheme: • White: no module in slot • Grey: module manually off - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 28: Module

    Clicking on this button, the corresponding module LED’s blink for few seconds. It helps to identify the module in the system and also the assigned phase of the module.. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 29: Events

    Events appear with a color corresponding to their alarm level (Grey – event, orange – minor, red – major). A filter, as shown below is available to display only a subset of these events. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 30: Log

    “0” on the alarm condition. Therefore, a TRUE state indicates the input is not active. A FALSE state indicates the input is active - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 31: Files

    “*.saf” file. Once uploaded, the system will restart, installing the new application after verifications. The dedicated procedure will be provided at the same location if needed. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 32: Parameters

    Note: If the system has no power, the Real-Time Clock in T2S ETH can run up to 24 hours. After that, the clock will reset the date to 01/10/2013 and time to 8.00. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 33 NTP server. NTP configuration parameters. ƒ IP Address of NTP server ƒ Port Number ƒ Time zone offset ƒ Auto-refresh ƒ Synchronization interval (days) ƒ Force Synchronization. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 34 8.3, page 46. ƒ IP address ƒ Subnet mask ƒ Default gateway ƒ Primary DNS ƒ Secondary DNS DNS has to be configured where server has host name. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 35 “MBP ENGAGED” or “Surge Arrester”, it will display the given name in the web interface, but in the log file, it shows only as “Digital Input 1” and “Digital Input 2”. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 36 Note: While selecting an alarm type for a relay, choose either Major or Minor. If both selected, only the major alarm will be enabled during that relay energized. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 37 Modbus RTU. NOTE! Modbus TCP/IP can be accessed and configured through Inview X only. For configuration refer to the sections “Modbus”, page 79 and “Modbus over RTU”, page - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 38 AC input side. User shall modify it ONLY if he has followed a proper training by CE+T. Note: To know more about each field, refer to “AC In”, page 81. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 39 AC output power exceed 80% of the total installed power. Delta mode: operation mode delta for 3 phase configuration only. Note: To know more about each field, refer to “AC Out”, page 82. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 40 ƒ Interface version ƒ Bootloader version ƒ MAC Address: In case of required support, it’s mandatory to provide information listed in this page or a screenshot of it. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 41: Network Architecture

    • If the T2S ETH IP address is changed by the user, then the same has to be entered in CF340 and CF220 values acordingly. • Ensure that the Dashboard and data are on the GUI screen. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 42: Snmp

    This document describes the Management Information Base (MIB) schema design for standalone T2S ETH for SNMPv1 configuration and T2S ETH with Inview X for SNMP V2C and V3 configuration. A MIB schema describes the structure of information served by a Simple Network Management Protocol Subsystem (SNMP) agent.
  • Page 43: Snmp V1 Configuration

    5. If you are on a network with DHCP, you can enable the DHCP inside the Network submenu of the “Monitoring” menu. 6. Turn DHCP to “Enable”. 7. Click “Save”. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 44 SNMP V1. Ignore SNMP V2C and SNMP V3 from the drop down list and these configurations will not communicate with T2S ETH card. 5. SNMP Port is configurable through Expert login - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 45: Snmp Configuration Via Inview

    • In the ID CF61, select “True” to enable the SNMP function and enter the port address in the ID CF62. • In the ID CF63, select the SNMP version V1, V2c and V3. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 46: Mib

    LAN. The program shows all network devices, gives you access to shared folders, and provides remote control of computers. Download the application from https://www.advanced-ip-scanner.com Run the .exe file when the application opens, click on RUN scan. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 47 SNMP - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 48: Snmp V1 Testing

    2. Once it is done, you can browse the MIB content under MIB Tree > iso.org.dod.internet > private > enterprises > cetMIB > cetTSIMIB 3. Fill the address field with your unit IP address. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 49 SNMP 4. Click “ advanced ” if you changed settings like Read Community. 5. Select the operation, for example “WALK” and click “Go”. 6. The result looks like - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 50: Snmp V1 Traps

    2. Open CET-TSI-MIB and paste it in the editor. 3. Press Ctrl + S to save the file with the same file name. 4. Open CET-TSI-SIM and paste it in the editor. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 51 8. Select the above files and Press right arrow to move the files to Loaded MIB Module. 9. By doing this CET MIB files are loaded to SNMPB MIB tree. 10. Navigate to tree tab and check for CET MIB under iso-org-dod-internet-private-enterprises-cetMIB. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 52: Steps To Load Inview Mib

    2. Click on ‘MMI References’ and click on ‘Export’ button under ‘Generate SNMP MIB’ option. 3. Save the file in your computer. 4. Open the snmpb application and navigate to editor. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 53 6. Press Ctrl + S to save the file with the same file name. 7. Navigate to Modules Tab. 8. Check if ‘CetCompas.mib’ is listed under available MIB Modules. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 54 9. Select the file and Press right arrow to move the it to Loaded MIB Modules window. 10. By doing this CET MIB files are loaded to SNMPB MIB tree. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 55: Steps To Discover Device

    3. SNMP Agent profile to be selected based on the type of SNMP communication. 4. Click on discover device. 5. T2S device will be discovered. 6. Right click on the device and add device to agent profile list. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 56: Steps To Get / Walk Oid

    10. Select Security level NoAuth/NoPriv or Auth/NoPriv or AuthPriv as the once configured in T2S ETH web page. 11. Enter SNMP content text same as in T2S ETH web page. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 57 SNMP - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 58: Reading Alarms In Snmp

    (0) in SNMP. Alarm type can be either: • noAlarm (0) • minor (1) • major(2) Example: tsiAlarmType.1 minor(1) as Source V Too Low Stop is configured as Minor Alarm - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 59 2020-3-18, noAlarm(0) module01(1) Manual or Remote Off 6:41:29 2020-3-16, noAlarm(0) system(33) Output Fault 23:44:39 2020-3-16, minor(1) system(33) Too Many Starts 23:44:39 2020-3- major(2) system(33) Output Failure 16,23:44:33 - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 60 18,6:43 2020-3- noAlarm(0) module01(1) Manual or Remote Off 18,6:41:29 2020-3- noAlarm(0) system(33) Output Fault 16,23:44:39 2020-3- minor(1) system(33) Too Many Starts 16,23:44:39 2020-3- major(2) system(33) Output Failure 16,23:44:33 - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 61: Modbus Tcp/Ip Via Inview

    • Input Registers, data reading (Read Only), using modbus command 03 If you want to use Modbus to monitor other types of systems, please contact us. We will study the business case and make a proposal. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 62 To download the Modbus data, log in to the Inview web interface, go to Administration > Files > MMI References and click the Modbus Map “Export” button. For Modbus Data and Alarm details, refer to”17.5 ModBus Table”, page 103 . - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 63: Faq

    4. How can I reset my admin password if I have unfortunately forgotten it? In case of password lost, a new temporary password (valid 24 hrs after creation) can be issued by CE+T Power. To receive a temporary password, send an email with your T2S ETH serial Number and the date at which you expect to go back on site to change the password to customer.support@cet-power.com...
  • Page 64 DC Input Power must be at least 5% of the configured power in the system to be shown; this is to prevent a lack of accuracy of converters measures when the system is almost not loaded. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 65: Trouble Shooting And Defective Situations Fixing

    Repair registering guidelines may be requested by email at repair@cet-power.com. • The RMA number should be mentioned on all shipping documents related to the repair. • Be aware that products shipped back to CE+T Power without being registered first will not be treated with high priority! •...
  • Page 66: Service

    CE+T will redirect your call to your vendor if he has such SLA in place. (**) Valid in USA and Canada only. (***) Messages that are not Major Incident or Emergency will be served at the next scheduled working a day. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 67: Maintenance Task

    * It is not recommended because when you perform a By-pass procedure, generally there is no back up on AC input line, and the load shutdown if mains disappear. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 68: Annex 1: Supervisor Alarms - T2S Eth

    Any output group has 0 seen modules, or no module Output Failure mappable major running (and they are not manually off). System Started event System just started. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 69 Log Full mappable disabled Log file is full (with information loss). Log Cleared event Log file has just been cleared. Config modified event Configuration has just been modified. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 70: Annex 2: Module Alarms - T2S Eth

    Minor TSI has not started must have a T2S - orange LED Parameter Query Minor Inverter is updating his parameters Parameter Mismatch Minor Parameters incompatible with configuration file - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 71 Write an event “REMOTE OFF” in log file when inverter is Remote Off Minor set OFF through REM ON/OFF terminal - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 72 Source Frequ. Too High Minor Check AC IN configuration and live value Phase Not Ready Minor Check AC IN configuration and live value Backfeed Error Minor Inverter in backfeed protection - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 73 Source V Too Low Stop Minor Check VDC parameter and live value Source V Too High Stop Minor Check VDC parameter and live value Error (217) Minor Error (220) Minor - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 74: Annex 3: Configuration Parameters - T2S Eth

    Magnifier button. Display format DD/MM/YYYY Date format YYYY/MM/DD Date format for user interface and user log MM/DD/YYYY Time format Time format for user interface and user log - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 75 T2S ETH is connected. To find the IP address of T2S ETH card IP Enable Scanner tools can be used Default IP address is 192.168.0.2, user can set their own System IP IP address 192.168.0.2 address - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 76: Inputs/Relays

    User label for minor alarm relay and cannot be modified. User can define the label name according to the selected alarm in Relays Relay 3 Name Relay 3 Mapping page. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 77 Module Manual Off Relay 3 Module Output fault Module Brownout Derating Module Temperature Derating Module Over Temperature Dig Input 1 Dig Input 2 Log Nearly Full Log Full - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 78 (number of TRAP receivers can set in SNMP page) Module Brownout Enable Derating Module Temperature Derating Module Over Temperature Dig Input 1 Dig Input 2 Log Nearly Full Log Full Other alarms - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 79: Snmp

    Set slave address for ModBus RTU. 9600 19200 Baud rate Set baud rate for ModBus RTU. 38400 115200 Parity Even Odd No parity Set parity for ModBus RTU. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 80: Power

    If disabled, alarms related to AC source will be inactive and it will not Disable display in the web interface. Enable AC In grid feed If enable, power will re-inject to AC input source. Disable Disable - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 81 Mode On Line If enabled, Load feed by DC source. If DC out of range, Load transfer to AC (Safe) IN with delay transfer of 10 ms. Disable - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 82 Max Power 150% (TSI) Maximum power that module can supply. Derating (%) Max Current Maximum current that module can supply. Derating (%) 125% (ECI) - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 83 ‘0’. If the user want to share a DC group DC sync ID between multiple sub-systems all of these should have the same value for DC 1 to DC 8 this parameter. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 84 Not Applicable for EPC mode operation. Enable No power from It is recommended to set in “Disable” ACin phase 2 Disable Enable No power from ACin phase 3 Disable - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 85: Annex 4: Modbus

    Default From 1 to 247 Slave address 9600, 19200, 38400 or 115200 19200 Baud Rate Even, odd, none Even Parity One, two Stop bits Mode RS485 Electrical interface - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 86: Database Description

    Data address mapping and signification are described in the following sections. 17.2.3 Supported function: Accordingly to Modbus RTU specification, supported functions by the T2S ETH controller are the following: ƒ Read Input registers (0x04) - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 87 Flag (true or false)that indicates if module cannot cope with more than five bRestrained other module or not bNoEPC Flag (true or false) that indicates if module has an AC input (EPC) or not wPoutNominalW Nominal output power (W) - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 88 Number of modules that are not delivering output due to a failure in the phase Number of modules not seen by T2S ETH in the phase (accordingly to bNbInvNT bNbOndCfg) - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 89 The table described below represents the miscellaneous information that can be retrieved regarding T2S ETH and system. BASE ADDRESS: 1980(0x07BC) Index Name Description Type bOldVersionNumber Deprecated. Always 0x00 ePhaseNumber Number of phase configured in the system - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 90 50. A valid entry represents an alarm present in the system. An invalid entry is an entry where all bits of each field are set. All entries following an invalid entry will be invalid. BASE ADDRESS: 2010(0x07DA) + 2*(Entry number – 1) - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 91: Status And Constants Description

    Standby running. This means that the module is delivering output Standby. This mean that the module is manually OFF Standby with error. This means that the module is not delivering SBWE output due to an unrecoverable error - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 92: Alarm Types

    Device responsible of the alarm is the module number XX where MOD XX 1-32 XX is the value Source of the alarm is the whole system (e.g. if all module are SYSTEM sharing the same alarm). - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 93: Validity And Unit Description (A2)

    In all the following examples, assumption will be made that T2S ETH controller Modbus RTU slave address is 1 (0x01). 17.4.1.1 Reading simple variables: Ex 1: Reading output voltage of module #5 - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 94 4 (0x04) Read input register Address 2014 (0x07DE) 2010 + 2*(3-1) = 2014 (see alarm table, page 90) Number of registers 2 (0x02) Alarm entry is 2 registers wide - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 95 0x0000  PARAM_OK (see 17.3.4, page 93) Parameter ID: 0x0104  260 Units: 0x0101  unit is dV (0.1V) (see 17.3.4, page 93) String description: DC 1 : Vdc_in Low Start - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 96 3. Poll the serial number using “Module information table” using the new address as index until there is a match with the serial number collected at point 1. - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 97: Modbus Rtu - Testing

    • USB to RS485 interface cable (For example USB-RS485-WE cable, FTDI chip), Fig 1 Fig 1: FTDI cable • RJ45-TERM (Gravitech.us) Fig 2 Fig 2: Adapter for RJ45 - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 98 3. Read the COM port number in your computer settings (In the device manager), Fig 3. Fig 3: COM port number 4. Open the downloaded Radzio!, Fig 4 Fig 4: Radzio! Home Screen - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 99 5. Click on the Connection settings icon in the tool bar. Fig 5: Connection settings icon 6. Select Modbus RTU in the Connections settings window Fig 6: Connection settings window - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 100 8. Close the Connection settings window in Radzio!. 9. Click on the Connect icon in the Radzio tool bar in order to establish the connections. (Fig 8) Fig 8: Connect icon - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 101 ○ Set the Device ID (Default value is 1) ○ Set the entity of Device ID as Input Register (Default value is Coil status) Fig 10: Default Radzio settings to Modify - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 102 ƒ Input current (U16) at address 7 = 4 [0.1 A] = 0.4 [A] ƒ Input frequency (U16) at address 8 = 499 [0.1 HZ] = 49.9 [Hz] - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 103: Modbus Table

    Apparent Power Input register 30125 Multiplied by 10 Frequency Input register 30131 Divided By 100 Installed Active Power Input register 30132 Divided By 100 Installed Apparent Power Input register - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 104 Active Power Input register 30344 Divided By 100 Apparent Power Input register 30345 Multiplied by 10 Frequency Input register 30351 Divided By 100 Installed Active Power Input register - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 105: Alarm Table

    10239 DigIn 4 Input status 1=Active, 0=Inactive 10240 DigIn 5 Input status 1=Active, 0=Inactive 10241 DigIn 6 Input status 1=Active, 0=Inactive 10242 DigIn 7 Input status 1=Active, 0=Inactive - Monitoring - T2S ETH with Inview X- User Manual - v3.0...
  • Page 106 Input status 1=Active, 0=Inactive 10255 MBP procedure Input status 1=Active, 0=Inactive 10149 Source- too low - stop Input status 1=Active, 0=Inactive 10152 Source+ no voltage Input status 1=Active, 0=Inactive - Monitoring - T2S ETH with Inview X- User Manual - v3.0...

Table of Contents