AGIL - MODULAR UPS Installation Manual V7.2 RE-INVENTING THE MODULAR UPS THE NEW GENERATION OF POWER CONVERTERS SELECTIVITY Adapted response to short circuit and overload VERSATILE CHARGING Short or long backup recovery time at no extra cost BATTERY SUSTAINABILITY Qualitative charging for longer battery life expectancy...
System Description Agil 160 ..................6.1.3 System Description AGIL 200 to 640kVA ..............Manual by-pass........................... 6.2.1 Internal MBP for AGIL 60 and AGIL 160 with internal MBP ........... 6.2.2 External MBP ......................MBP Procedure ........................... 6.3.1 From Normal to By-Pass ....................
Page 3
Cabling Termination AGIL 60 KVA System ..............7.9.2 Cabling Termination AGIL 160 KVA System ..............7.9.3 Cabling termination AGIL 200 to 640 KVA System ............7.10 Cable Selection ........................... 7.10.1 AC Input ........................7.10.2 DC Input ........................7.10.3 Ground .........................
1. CE+T Power at a glance CE+T Power designs, manufactures and markets a range of products for industrial operators with mission critical applications, who are not satisfied with existing AC backup systems performances, and related maintenance costs. Our product is an innovative AC backup solution that unlike most used UPS’s •...
• When handling the system/units pay attention to sharp edges. 1 These instructions are valid for most CE+T Products/Systems. Some points might however not be valid for the product described in this manual – Agil Modular UPS – Installation manual – v7.2...
Earthing must be carried out prior energizing the system. Earthing shall be made according to local regulations. 3.3.3 Other • Isolation test (Hi-Pot) must not be performed without instructions from the manufacturer. – Agil Modular UPS – Installation manual – v7.2...
• There is a risk of explosion if battery is replaced by an incorrect battery type dispose of used batteries according to the instructions. To download the latest documentation and software, please visit our website at www.cet-power.com – Agil Modular UPS – Installation manual – v7.2...
1 | Information and data given in this chapter intend to for an overview on the technology. Detailed features and parameters for each individual module type of the range may differ and should be referred in the dedicated data sheet. – Agil Modular UPS – Installation manual – v7.2...
. A specific example of Mix-mode is the Walk-in mode where the transfer from DC source to AC source is ramped up within a fix and adjustable period of time. – Agil Modular UPS – Installation manual – v7.2...
• Single stand alone cabinet with or without integrated battery backup and internal manual by-pass(up to 60 kVA) • System of up to four cabinets with external by-pass AGIL 60 AGIL 160 – Agil Modular UPS – Installation manual – v7.2...
Page 12
AGIL 640 200 kVA 200 kVA EXTERNAL 420 kVA 420 kVA 640 kVA 640 kVA – Agil Modular UPS – Installation manual – v7.2...
5.2 AGIL UPS Module 20 kVA The AGIL module is a modular UPS of 20kVA/20kW. The design of the module allows dynamic load transfer, high efficiency, unsurpassed flexibility and scalability. The module is hot pluggable and hot swappable 5.3 T4S Monitoring Controller The T4S supervisor act as a link between the system and the user, the control of the system and the modules are distributed on each module.
Manual Bypass included Maximum output power 60 kVA or 40 kVA N+1 Agil 160 Cabinet prepared to receive maximum 8 Agil module (20 kVA each) Maximum output power 160 kVA or 140 kVA N+1 Agil 200 Primary cabinet 200 kVA...
The manual by-pass works in Make before Break. NORMAL the AGIL modular UPS is operational providing secure backup of the load. BY PASS the AGIL modular UPS is bypassed. UPS modules are powered off and AC input/output is isolated. However battery input is not isolated.
6.2.2 External MBP External MBP for AGIL 200 kVA to 640 kVA is installed in separate cabinet with AC input/AC output terminal as well as all interconnection cable to AGIL cabinet. – Agil Modular UPS – Installation manual – v7.2...
3. Turn Rotary Switch to NORMAL. External MBP 1. Switch on the DC feed to the Agil Cabinet (DC battery fuse ON) 2. Turn switch S2 to ON(Position 1) 3. Wait for all LED on AGIL module to be permanent green 4.
Make sure the wooden crate is in right position with TOP and BOTTOM stickers in the right direction. The top cover fixing bolts must NOT be replaced with lifting eye bolts. Raise the cabinet on location. – Agil Modular UPS – Installation manual – v7.2...
7.2.4 Module Packaging: AGIL modules are not included in the cabinet. They are packed individually in cartons and on pallet. One AGIL module is 24Kg, maximum 3 modules carton boxes may be stacked on each other at all times. Always transport modules in their carton box with suitable protection.
Step 3. Pull on one side of the foam to free the one side of the AGIL hand grip from the foam. Step 4. Pull on the other side of the foam to free the other side of AGIL hand grip from the foam.
The cabinet is fixed through the base of the cabinet. Remove lowest front cover to gain access to the fixing holes. Max screw diameter is 0.8” (22mm). See Hole pattern, foot print for measurements – Agil Modular UPS – Installation manual – v7.2...
Cables need to be terminated in the following order to facilitate the installation 1. Signal cables 2. AC output 3. AC input 4. Battery Negative 5. Battery Common 6. Battery Positive – Agil Modular UPS – Installation manual – v7.2...
VR1 to VR3 Surge Arrester F1 and F2 DC+ and DC- AC Input Terminal 5 Wires (L1, L2, L3, N, PE) AC Output Terminal 5 Wires (L1, L2, L3, N, PE) – Agil Modular UPS – Installation manual – v7.2...
DC Input Terminal (L1, L-) N(C) Neutral and BAT 0V Terminal EARTH PE Grounding F7 to F10 Auxiliary power supply A9 and A10 Protections VR1 to VR3 Surge Arrester Remote ON/OFF Terminal T4S Monitoring Unit – Agil Modular UPS – Installation manual – v7.2...
7.9.3 Cabling termination AGIL 200 to 640 KVA System AGIL 200 to 640 consist of several interconnected cabinets as below – Agil Modular UPS – Installation manual – v7.2...
Ground cable connected to cabinet ground terminal. The ground cable is terminated using single hole cable lug. The ground cable shall be at least ¾ that of the AC input cable dimension. – Agil Modular UPS – Installation manual – v7.2...
D4 : Digital input available for user D5 : Digital input available for user D6: Digital input available for user D7: Digital input available for user D8: Digital input available for user – Agil Modular UPS – Installation manual – v7.2...
7.11.2 Protective device External supply circuit breakers/fuses are required in the mains input supply of the system. AGIL 60kVA recommended protection 3 pole 125 A MCB. AGIL 160kVA recommended protection 3 pole 300 A MCB. AGIL 200kVA recommended protection 3 pole 400 A MCB...
AGIL battery consist of 204 cells with nominal voltage of 2 V or 34 block of 12 VDC. The AGIL battery has a middle connection which means we have +204 VDC / 0 VDC / -204 VDC. There is a risk of explosion if battery is replaced by an incorrect battery type dispose of used batteries according to the instructions –...
Installation and commissioning must be conducted by trained and “AGIL installation duly authorized” personnel only. CE+T Power cannot be held responsible for any liabilities that would occur due to a non respect of the instructions stated in this manual or due to unproper installation.
Switch OFF AC input (commercial power failure) and check the alarm according to the configuration Switch OFF DC input (DC power failure) and check that the alarm according to the configuration Check the different digital input according to the configuration (when used) – Agil Modular UPS – Installation manual – v7.2...
All OK but I have alarm: Check configuration file and correct No of modules Download/clear log file No output alarm: Mind the default time delay (UA: 60s, NUA: 30s) Check configuration file – Agil Modular UPS – Installation manual – v7.2...