AGIL - MODULAR UPS
Including Smart ByPass (SBP)
User Manual V7.6
RE-INVENTING THE MODULAR UPS
THE NEW GENERATION OF POWER CONVERTERS
SELECTIVITY
Adapted response to short circuit and overload
VERSATILE CHARGING
Short or long backup recovery time at no extra cost
BATTERY SUSTAINABILITY
Qualitative charging for longer battery life expectancy
HARSHEST AC INPUT CONDITIONS
Without compromising the quality of the AC output
Copyright © 2013. Construction electroniques & telecommunications S.A.
All rights reserved. The contents in document are subject to change without notice.
The products presented are protected by several international patents and trademarks.
Address: CE+T S.a, Rue du Charbonnage 12, B 4020 Wandre, Belgium
www.cet-power.com - info@cet-power.com
www.cet-power.com

Advertisement

Table of Contents
loading

Summary of Contents for CE+T Power AGIL 60

  • Page 1 AGIL - MODULAR UPS Including Smart ByPass (SBP) User Manual V7.6 RE-INVENTING THE MODULAR UPS THE NEW GENERATION OF POWER CONVERTERS SELECTIVITY Adapted response to short circuit and overload VERSATILE CHARGING Short or long backup recovery time at no extra cost BATTERY SUSTAINABILITY Qualitative charging for longer battery life expectancy HARSHEST AC INPUT CONDITIONS...
  • Page 2: Table Of Contents

    Table of Contents 1. CE+T Power at a glance ......................... 2. Abbreviations ............................3. Introduction ............................Scope of the manual ........................User Interface presentation......................3.2.1 AGIL UPS module User Interface ..................3.2.2 T4S supervisor ....................... 3.2.3 CATENA GUI Interface .....................
  • Page 3 10. SNMP V1 & SNMP V3 Configuration ......................10.1 SNMPv1 configuration ......................... 10.2 SNMPv1 MIB (RFC1628) ......................10.3 SNMPv3 configuration ......................... 11. ModBus RTU ............................11.1 Physical Connection ........................11.2 Configuration ..........................11.3 Tables ............................ANNEXE 1. Battery Management with AGIL Technology and T4S ..............1.1.
  • Page 4 Release Note: Release date Modified Version Modifications (DD/MM/YYYY) page number 06/01/2014 First release of the Manual. 7 and 9 Modified picture Added Note 28/05/2014 Password details updated 27 to 30 Text updated Table updated 05/06/2015 SBP Information 23/12/2015 Amendment and correction. 05/01/2018 Updated the pictures and information 29/01/2018...
  • Page 5: Ce+T Power At A Glance

    CE+T Power at a glance 1. CE+T Power at a glance CE+T Power designs, manufactures and markets a range of products for industrial operators with mission critical applications, who are not satisfied with existing AC backup systems performances, and related maintenance costs.
  • Page 6: Abbreviations

    Abbreviations 2. Abbreviations Twin Sine Innovation Enhanced Power Conversion Regular Digital Signal Processor Alternating current Direct current Electro Static Discharge Main Earth Terminal Manual By-pass TCP/IP Transmission Control Protocol/Internet Protocol Universal Serial Bus Protective Earth (also called Main Protective Conductor) Neutral Printed Circuit Board True Redundant Structure...
  • Page 7: Introduction

    Introduction 3. Introduction 3.1 Scope of the manual This document describes the software features, on-site setup and operation of the AGIL Modular Power system. Please refer to AGIL Installation manual for hardware installation and wiring information. 3.2 User Interface presentation 3.2.1 AGIL UPS module User Interface Output power bar graph 0-100% (25% increment) Phase 1, phase 2, phase 3...
  • Page 8 Introduction 3.2.1.1 Output Power LED interface : Each segment represent 25% load. 0-25 / 25,1-50 / 50,1-75 / 75,1-100 Load can differ between the 3 phases in one module Load can differ in one phase in several modules Overload (blinking) 100% - 110% segment 0-25 blinking 110,1% - 135% segment 0-50 blinking –...
  • Page 9 Introduction 3.2.1.2 Module status LEDs interface AC input LEDs interface Starting up (all LEDs) AC Input OK (within limits) GREEN AC Input not OK (out of limits) ORANGE (Auto restart) Flash ORANGE (Manual restart) Flash RED (Non recoverable) RED AC failure OFF + external alarm AC output LEDs interface Starting up...
  • Page 10 Introduction Starting up DC OK (within limits) GREEN DC not OK (out of limits) YELLOW (auto restart) YELLOW Blink (man restart) RED Blink (non recover) No battery connected Communication LEDs interface COM OK GREEN COM ERROR (Bus A or B) GREEN Blink still one bus present COM ERROR (Bus A &...
  • Page 11: T4S Supervisor

    Introduction 3.2.2 T4S supervisor T4S supervisor monitors the AGIL module as well as system environment. It is connected to : • The AGIL module through the CE+T bus [1]. • The Catena through the “Catena bus” [2]. • To Catena on left ETH port - see page 12 [3]. T4S has: •...
  • Page 12: Catena Gui Interface

    Introduction 3.2.3 CATENA GUI Interface CATENA GUI interface allows the user to easily access the system monitoring via a powerful web based graphic display. In addition to the touch-screen display the user can also access to the same GUI using an Ethernet port present on the T4S or CATENA.
  • Page 13 Introduction Catena - Door Mounting Version To access the user interface, user has to connect through Ethernet port in Catena. Installing the Door mount catena in the AGIL Cabinet door Step 1. In the Cabinet Door, make 8 x M3 holes as per the catena support sheet dimensions. Step 2.
  • Page 14: Installation

    Installation 4. Installation T4S is a DIN rail mountable controller which is connected to the AGIL module / system as indicated in the schematic in next page Remark: Catena acts as a switch on the network. Both T4S & Catena need IP address as they are both connected to the network.
  • Page 15: Schematic Diagram - Common Input Source For Agil With Sbp + Mbp

    Installation 4.1 Schematic Diagram - Common Input Source for AGIL with SBP + MBP – Agil Modular UPS – User manual – v7.6...
  • Page 16: Schematic Diagram - Dual Input Source For Agil With Sbp + Mbp

    Installation 4.2 Schematic Diagram - Dual Input Source for AGIL with SBP + MBP • Page 1 – Agil Modular UPS – User manual – v7.6...
  • Page 17 Installation • Page 2 – Agil Modular UPS – User manual – v7.6...
  • Page 18: T4S/Catena Start-Up

    If you have installed the T4S and CATENA by yourself, make sure to respect the connections as indicated in the schematic. If you have ordered the complete solution with cabinet and module from CE+T Power, both controllers are installed, wired, tested and preconfigured according to the system.
  • Page 19: Standard Features

    Standard Features 6. Standard Features The main screen presents an overview of the system where any “click” on the magnifying glass icon will result to access the selected sub-menu: 1  AC Input sub-menu. 2  DC Battery sub-menu. 3  AGIL Modules sub-menu. 4 ...
  • Page 20: Ac Input Sub-Menu

    Standard Features 6.1 AC Input Sub-menu Provides AC input information (up to 3 phases). y AC input voltage. y AC input current. y AC input Frequency. y AC input Power (kW). 6.2 DC Battery Sub-menu Battery x (x = 1 or 2) provide info on batteries status.
  • Page 21: Agil Modules Sub-Menu

    Standard Features 6.3 AGIL Modules Sub-menu Provides AGIL module info y Number of module installed y Redundancy level y Installed power. y Available power. y Temperature of the warmest module. 6.3.1 AGIL Modules Sub-menu. Clicking on the “Select Module” icon will open a module selection table. Each number represents the address of a module in the system.
  • Page 22 Standard Features Selected Module information y Click “identify icon” to see corresponding module in the bay (all LEDs blinking). y Module status indicated through the LED color on : ƒ -AC input. ƒ -DC input. ƒ -AC output. Green: Organe: Recoverable error. Red: Non recoverable error.
  • Page 23: Ac Output Load Sub-Menu

    Standard Features 6.4 AC Output Load Sub-menu AC output control board y Level of power bar graph. y Measures: individual phase details of L1, L2, and L3 ƒ Voltage ƒ Current ƒ Frequency ƒ Active Power ƒ Apparent Power ƒ Power Factor 6.5 SBP Modules Sub-menu NB: This sub-menu is accessible only when there is at least one SBP installed in the system.
  • Page 24: Sbp Modules Sub-Menu

    Standard Features 6.5.1 SBP Modules Sub-menu. Clicking on the “Select Module” icon will open a module selection table. Clicking on any line will give the view of the selected module. While SBP engaged y AC IN measures voltage and current y AC Out measures apparent power and output ratio in percent.
  • Page 25: Toolbar

    Toolbar 7. Toolbar 7.1 Events and Log Please note “text alarm page” is refreshed every minute for easy reading while LED’s are active immediately. Display the active event/alarm present on the system. y Red: Major alarm. y Orange: Minor alarm. y White: No alarm.
  • Page 26: Input, Output Mapping

    Toolbar Do not forget to click apply to activated the selected filter. Clear Filter will remove all selected filter and view all log file. 7.2 Input, output mapping Present the output relay mapping with possibility to test each relay with the “toogle” button. Click and check relay chaging status with an ohmeter.
  • Page 27: Files

    Toolbar 7.3 Files Transfer screen allow to export the log file and export or import configuration file Transfer: Event History y Both Event log and configuration file can be exported. y Event file name cet.log is a text format *.txt file. y Log size limited to about 500 –...
  • Page 28: Parameters

    Toolbar Battery Log: To export or clear the battery log files. 7.4 Parameters WARNING ! All values present are default values ! User shall consult and change default value with caution. Wrong parameters can affect the system operation, reliability, battery life duration and system autonomy.
  • Page 29 Toolbar Regional settings y Choose language. y Site name. y Site Location. y Auto logout delay (will disconnect user after defined seconds). y Keyboard layout. Password Choose password. Read the information carefully at section 5.1, page 18. Temperature sensors Allow to configure the temperature probe for battery compensation or ambient temperature.
  • Page 30: Communication

    Toolbar Alarms Allow to enable and disable the alarms. 7.4.2 Communication Network: Allow to configure the LAN Network parameters (Note: Default IP address is 192.168.0.2) – Agil Modular UPS – User manual – v7.6...
  • Page 31: Digital Input And Output Relay Mapping

    Toolbar SNMP: You can configure all SNMP and Trap related settings. For more details refer section 10, page 44. Remark: Catena Network configuration is mandatory for having the screen working. It should be on the same network as T4S. Modbus: You can view Modbus settings.
  • Page 32 Toolbar Input labels y Allow to define a label that will be used for any digital input activated. y Example y Label 1 : Door open will report the event “Door open” every time the digital input 1 is active. By default Digital Input 1 is assigned to “Manual By Pass”...
  • Page 33: Power Parameter Setting

    Toolbar Relay Mapping Allow to perform the mapping of any alarm to any relay association. One alarm can be allocated to more then one relays 7.4.4 Power parameter setting The menu “Power” allow to perform the setting of the system, AC input, DC battery, AC output and Others. General To configure: y Redundancy...
  • Page 34 Toolbar AC out To configure AC output parameter AC out Phase sequence and AC out phase shift. Nominal AC out frequency. If set different then AC input the BOOST will not be available Frequency limit 30 to 70Hz. Note: The parameter “Out voltage consign”...
  • Page 35 Toolbar DC group To define min, max battery voltage for .Default value are related to 408VDC nominal battery (204 cells). To configure DC input 1 Parameter. Low and High define voltage to configure boundaries min and max from where AGIL will STOP to preserve battery from deep discharge.
  • Page 36 Toolbar Other • Customer repartition: 0 to 100% to define the ratio from AC in and battery. 0% - AC input as primary source. 100% - Battery as primary source. • Commutation time: define the duration to return from DC to AC. •...
  • Page 37: Battery 1 And Battery 2

    Toolbar 7.4.5 Battery 1 and Battery 2 Warning: !!! Battery configuration is extremely important. There must be correct value entered for battery. Those parameter will define: - The floating charging voltage; - The boost charging voltage (if enabled); - The current limitation to protect battery from overcharging current; - The prediction of the battery capacity when battery test are performed.
  • Page 38 Toolbar Test y To set up the battery test parameter Power, time duration and voltage stop y Auto test to define the periodicity of the test Boost To set up Boost, first enable it then set up the parameter y Voltage per cell (from manufacturer) y Boost can be activated on voltage value : Voltage start.
  • Page 39: Info

    Toolbar 7.4.6 Info Info Provide information about T4S y Serial number y Software version y Interface version y Bootloader version y MAC Address – Agil Modular UPS – User manual – v7.6...
  • Page 40: Agil / Sbp Module And Fan Replacement

    AGIL / SBP module and Fan replacement 8. AGIL / SBP module and Fan replacement 8.1 AGIL / SBP module replacement Caution: Before sliding the module into the cabinet, make sure nothing is blocking the module such as objects, Catena wires and other wires. Step 1.
  • Page 41: Fan Replacement

    AGIL / SBP module and Fan replacement 8.2 Fan Replacement The FAN pre-alarm “FAN life elapse” has been set to 5 years. An event will appear on the Catena to remind the “FAN life elapse”. Perform the following steps to replace the AGIL Fan Kit: 1.
  • Page 42: Factory Ranges And Defaults

    Factory Ranges and Defaults 9. Factory Ranges and Defaults Submenu Item Programmable range Default values 408Vdc Float (FL) Voltage 408 – 490 463 Vdc Equalize (BOOST) Voltage 408 – 490 480 Vdc (2,35V/per cell) Test Batterie (BT) Voltage 315 – 490 391 Vdc Battery current limit 0-1000...
  • Page 43: Definition

    Factory Ranges and Defaults 9.1 Definition Alternating current Digital Input ALCO Alarm cutoff Battery current termination Battery discharge test Battery on discharge Test Batterie (mode) Controller Area Network Direct current Depth of discharge Equalize (mode or voltage) Float (mode or voltage) Graphical utilisateur interface Internet Protocol Liquid crystal display...
  • Page 44: Snmp V1 & Snmp V3 Configuration

    SNMP V1 & SNMP V3 Configuration 10. SNMP V1 & SNMP V3 Configuration SNMP is now available on T4S supervisor and on Catena display. SNMPv1 is available on T4S supervisor. The MIB implemented on T4S SNMP agent is the standard USP MIB defined by RFC1628.
  • Page 45 SNMP V1 & SNMP V3 Configuration See Catena network section: Set IP address, subnet mask, and gateway for local network. Set “bridge enable” option. By default, both ETH ports of Catena are in the same LAN. If the bridge is disabled, then each port is on an independent LAN.
  • Page 46: Modbus Rtu

    ModBus RTU 11. ModBus RTU T4S can act as a ModBus RTU slave with various baud rates and configuration options. No action can be done on the system through ModBus port; it’s only for monitoring purposes. 11.1 Physical Connection To get access to the ModBus, the RJ45 labeled “RS485” on T4S monitoring unit should be connected. RJ45 pinout is as follow: Note: The colour of wires is irrelevant and may vary, but make sure the position of wires is exactly crimped.
  • Page 47: Configuration

    ModBus RTU 11.2 Configuration ModBus slave configuration is accessible through user interface by browsing menu Parameters, Monitoring Tab , ModBus submenu. • Modbus RTU slave can be either enabled or disabled . • Slave address ranges from 1 to 247 . Default is 1 . •...
  • Page 48: Annexe 1. Battery Management With Agil Technology And T4S

    Battery Management with AGIL Technology and T4S ANNEXE 1. Battery Management with AGIL Technology and T4S 1.1. Introduction Battery is critical element in a UPS. Many manufacturer offer high performances of their electronic but sometimes forgot about providing an efficient and reliable battery management. Battery are fragile and need to be treated accordingly in discharge and recharge conditions.
  • Page 49 Battery Management with AGIL Technology and T4S MODE 1 algorithm can be trigger based on the following parameter: • Trig Start Voltage : Will activate MODE 1 when battery voltage goes below preset level • Trig Start Current : will activate MODE 1 when battery current goes above the preset value •...
  • Page 50 Battery Management with AGIL Technology and T4S 1.2.3 MODE 3 Discharge Discharge mode is active when energy flow is taken from the battery to the DC/AC converter (inverter) of each module. In this mode the T4S monitoring sent a voltage and current value to the AGIL module. This help in case of one module has AC input failure to take power from DC and is feed through the other module to avoid discharging the battery and assure the continuity of supply for the AC load.
  • Page 51 Battery Management with AGIL Technology and T4S START BAT x TEST + data and time FIN BAT x TEST + data and time For every delta of 1VDC record of: • Date in seconds • Battery voltage • Battery current •...
  • Page 52: Annexe 2. Agil Manual Bypass (Mbp)

    AGIL Manual Bypass (MBP) ANNEXE 2. AGIL Manual Bypass (MBP) The purpose of this document is to provide guidelines for customers to implement, assemble, wire and test external manual by-passes using CE+T AGIL modular UPS’ with T4S monitoring units. The CE+T delivered cabinets equipped with manual by pass are not concerned by this document. 2.1.
  • Page 53: Presentation

    2.3. Presentation The Manual By-pass can be provided with 2 executions: 1. Rotary Switch for AGIL 60 kVA and AGIL 160 kVA 2. Two (2 )power switches external to the AGIL cabinet for power above 160 kVA Please refer to the AGIL installation manual for more specific procedures.
  • Page 54: Mbp Wiring

    AGIL Manual Bypass (MBP) 2.4. MBP Wiring Both solutions (rotary by-pass or separate switches) need to have auxiliary contacts that need to be wired to the monitoring unit as described below and as shown on the drawing present in annexe Aux 3 (from the by pass switch) : Provides an input to the controller indicating that the MBP is engaged Aux 1 (From AC input switch) and Aux 2 (from the by pass SWITCH): •...
  • Page 55: Annexe 3. Agil Smart By-Pass (Sbp)

    AGIL Smart By-Pass (SBP) ANNEXE 3. AGIL Smart By-Pass (SBP) The purpose of this document is to provide guidelines for customers to accesss the Smart By Pass using CE+T AGIL modular UPS’ with T4S monitoring units. Note: SBP should be installed and operated only in AGIL UPS System. Caution: If AGIL and SBP has two different input source, it is mandatory to disable the Boost function.
  • Page 56: Sbp Leds Indication

    • SBP Ready. • SBP Input Not OK. 3.4. SBP Breaker Selection SBP Upstream and Downstream breakers are depends upon the number of AGIL Modules installed in the system. Model AGIL 60 AGIL 160 AGIL 200 AGIL 380 AGIL 580...
  • Page 57: Annexe 4. T4S Alarms

    T4S Alarms ANNEXE 4. T4S Alarms 4.1. Supervisor alarms: T4S This is the list of alarms issued by supervisor. Other alarms are issued by modules directly (see AGIL alarm table & OCA document). The supervisor is able to generate alarms that are related to the system, to AGILs modules, or to itself. Alarms related to AGILs will be seen as system alarms when module alarm is present on all AGILs.
  • Page 58 T4S Alarms Monitoring Alarms Text Def. Name Level Description/ Possible action The digital input 5 is active (NO or NC depending of the DigIn 5 Mappable configuration) The digital input 6 is active (NO or NC depending of the DigIn 6 Mappable configuration) The digital input 7 is active (NO or NC depending of the...
  • Page 59 T4S Alarms Monitoring Alarms Text Def. Name Level Description/ Possible action Low capacity pre Minor Battery capacity is in pre-alarm condition Low capacity Minor Battery capacity is in alarm condition No more Battery has reach its lower level, DC converter will soon Mappable autonomy stop...
  • Page 60 T4S Alarms Mappable Events (Not alarms !!) Text Name Level Def. Map Description Digital input 3 Event Digital input 4 Event Digital input 5 Event Digital input 6 Event Digital input 7 Event Digital input 8 Event MBP Engaged Major + R5 Battery bad Minor Means that a test has failed...
  • Page 61 T4S Alarms Mappable Events (Not alarms !!) Text Name Level Def. Map Description AC out 1 manual off Event AC out 2 manual off Event Log full Minor MBP procedure Major + R5 Battery safe charging control Major 4.1.1 Module alarms (T4S) Module alarms Text Def.
  • Page 62 T4S Alarms Module alarms Text Def. Name Level Description Bus A not present Minor bus A present signal of backplane not seen by the module Bus B not Minor bus B present signal of backplane not seen by the module present Bus frame Minor...
  • Page 63 T4S Alarms Module DC input alarms Text Def. Name Level Description Not defined 47 Not defined 48 Source+ too low Minor DC+ V is under input transfer to AC threshold - transferred Source- too low - Minor DC- V is under input transfer to AC threshold transferred Source+ too high Minor...
  • Page 64 T4S Alarms Module AC input alarms Text Def. Name Level Description Temperature too Minor ACin converter stopped because of too high temperature high Temperature Minor Communication with temperature probe was lost sensor fail Auto-calib error Minor Error during auto-calibration of current offsets Impedance Too Minor AC input too high impedance detected...
  • Page 65 T4S Alarms Module AC input alarms Text Def. Name Level Description SBP Source frequ Minor SBP source freq is over output stop threshold too high SBP Res not sync Minor SBP source is not in sync (freq + phase shift) with system Not defined 95 Not defined 96 Module AC output alarms...
  • Page 66: Annexe 5. Faq

    From version 3.1, in case of password loss, a new temporary password (valid 24 hrs after creation) can be issued by CE+T Power. To receive a temporary password, send an email with your T4S serial Number and the date at which you expect to go back on site to change the password to customer.support@cet-power.com...