Concrete Slab
At the appropriate location, construct a concrete slab:
• 28 day compression strength of 3000 psi (200 MPa)
• Minimum 5" (13 cm) thick
• Minimum 6" (15 cm) wider than enclosure on all sides
(shown as D in figure)
• Strengthen slab with No. 6 reinforcing bars
(on 12" (30.5 cm) centers) or 8 ga. steel wire fabric
(6" (15 cm) centers).
Attach unit to slab at four corner locations (A) with minimum
5/16"(8 mm) diameter masonry anchor bolts long enough to
secure the unit.
B
The fuel inlet location (B), the wire entry location (C), the
concrete slab (D), and the exhaust outlet (E) are shown for
D
reference.

Electrical and Fuel Inlet Locations

Electrical and Fuel Inlet Locations
The 3/4 inch N.P.T. fuel inlet connector (B) and 2 inch
electrical inlet location (C) is shown.
C
A
C
E
B
Concrete Slab (Ref)
6" (15.24 cm)
Min. Overhang
All Sides
7.4"
(18.80 cm)
18.9"
(48.00 cm)
70"
(177.80 cm)
Base
68"
(172.72 cm)
Anchor Hole
D
29.8"
(75.69 cm)
7.4"
2.0"
(18.80 cm)
(5.08 cm)
42" (106.68 cm)
30" (76.20 cm)
Base
27.73" (70.43 cm)
Anchor Hole
C
A
(180.34 cm)
B
Overhang
2X 73.43"
(186.51 cm)
E
32.3" (82.04 cm)
Roof Overhang
C
B
18.9"
(48.00 cm)
71"
Roof
82"
(208.28 cm)
Concrete
Slab (Ref)
15