Honeywell Farenhyt IFP-75HV Manual page 81

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt IFP-75HV:
Table of Contents

Advertisement

Zone
Detector
Type of Smoke Detector
Protocol
IDP/SK
IDP-PHOTO,
IDP-ACCLIMATE,
IDP-PHOTO-T,
SK-PHOTO,
SK-ACCLIMATE,
SK-PHOTO-T
DNR with IDP-PHOTO or
IDP-PHOTO-R
SK-PHOTO-CO-W and
IDP-PHOTO-CO-W
SK-CO-W and IDP-CO-W
SD
SD505-PHOTO
SD505-DUCT with SD505-
DUCTR
SD505-DUCT with SD505-
DUCTR
1. Detectors are suitable for Open Area Protection within the listed air velocity range. Typically, this range is 0 - 4,000 ft/min for photoelectric
detectors and 0 - 1,200 ft/min for ionization detectors. Be sure to confirm this range before installing the detector by referring to the
Manufacturer's Installation Instructions.
2. Detectors will default to Open Area Protection (High Sensitivity). Where applicable, detectors will only be compliant with UL 268 7th Edition if
they remain programmed to open area.
3. The alarm and threshold limits determined by the control unit interconnected to detectors that employ a special application
mode/configuration are designed and shipped from the factory with the Detector Sensitivity Setting set to an acceptable Open Area Protection
sensitivity being the default mode of operation.
The special application mode/configuration shall not be activated at the control unit without a deliberate action by the user to initiate the
special application mode through an alternate detector sensitivity selection setting. Additionally, the extended label should be modified at this
address to include the phrase 'SPECIAL APPLICATIONS' or 'SPECIAL APPS' for compliance with UL 864 requirements. Please refer to the
FACP Programming/Installation Instructions for further instructions on altering the extended labels.
NOTE: Automatic drift compensation is always in effect for all detectors. See Section 9.3.11 for information on the procedure to check if a
detector is in compliance.
3.
Use the up or down arrow key to scroll through the range or use the number keys on the annunciator, then press ENTER.
NOTE: If the SLC protocol is changed from IDP/SK to SD and a zone's sensitivity is higher than the SD limit, the zone sensitivity will be set to
the max value, 150, for the SD family.
Zone Accessory Options
1.
Login to the panel.
2.
Select 7 to access the Program Menu.
3.
Press 2 to enter the Zone Menu.
4.
Press 1 to edit a zone.
5.
Enter the Zone Number, then press ENTER.
6.
Press 3 to edit the Zone's Accessory options.
Single or Multi-Station cadence pattern (choose from Patterns 00 to 02, 23 if using IDP or SK. Choose from 00-16, 23 if using SD devices).
See Appendix C, "Cadence Patterns", on page 127.
CO Single and Multi-station Cadence (choose from Cadence Patterns 00 to 02, 23 for IDP or SK devices).
NOTE: The B200S Intelligent Sounder base provides the recommended CO cadence pattern
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Choices
Low
(3.5% obscurity)
Medium (2.5% obscurity)
High
(1.5% obscurity) (Default)
Low
(2.5% obscurity)
Medium (2.0% obscurity)
High
(1.5% obscurity) (Default)
Low
(4% obscurity)
Medium (3% obscurity)
High
(2% obscurity) (Default)
Fixed
Low
Medium
High (Default)
Fixed
Fixed
Table 8.3 IDP/SK and SD Detector Sensitivity Choices
If the day/night sensitivity option is selected, you can have different sensitivity
settings during the day and at night. You can program the days of the week
that Day/Night Sensitivity will automatically adjust. You can also designate
specific days as holidays. Holiday and weekend days use night sensitivity for
the entire day.
Low, Medium, and High settings have no effect for CO detectors. Day and
night settings also have no effect on these detectors.
If the day/night sensitivity option is selected, you can have different sensitivity
settings during the day and at night. You can program the days of the week
that Day/night sensitivity will automatically adjust. You can also designate
specific days as holidays. Holiday and weekend days use night sensitivity for
the entire day.
Low, Medium and High settings have no effect for photoelectric duct
detectors. Photoelectric duct detector sensitivity is always 1.1% per foot. Day
and night settings also have no effect on these detectors.
Low, Medium, or High settings have no effect for ionization duct detectors.
Ionization duct detector sensitivity is always 75 MIC (0.8%) regardless of Low,
Medium or High setting. Day and night settings also have no effect on these
detectors.
Programming
Comments
81

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt ifp-75

Table of Contents