Mounting Data; Transport And Storage Conditions; Electromagnetic Compatibility; Connection And Startup - ebm-papst W3G630-GG97-01 Operating Instructions Manual

Table of Contents

Advertisement

W3G630-GG97-01
Motor protection
Thermal overload protector (TOP)
internally connected
Protection class
I (with customer connection of protective
earth)
Conformity with
EN 61800-5-1; CE; UKCA
standards
Approval
CSA C22.2 No. 77 + CAN/CSA-
E60730-1; UL 1004-7 + 60730-1; EAC;
CCC
Comment
Conformity with EN 60335-1 in preparation
; Use the device in accordance with its degree of protection.
Information on surface quality
The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. The product is to be protected against UV radiation to
prevent the formation of patches and fading. Changes in color are not a
reason for complaint and are not covered by the warranty. UV radiation
in the frequency range and the intensity of natural solar radiation has no
effect on the technical properties of the products.

3.5 Mounting data

Further mounting data can be taken from the product drawing or Chapter
4.1 Mechanical connection as required.
Strength class of
8.8
screws
; Secure the screws against unintentional loosening (e.g. use self-
locking screws).

3.6 Transport and storage conditions

Max. permitted
+ 80 °C
ambient temp. for
motor (transport/
storage)
Min. permitted
- 40 °C
ambient temp. for
motor (transport/
storage)

3.7 Electromagnetic compatibility

EMC immunity to
According to EN 61000-6-2 (industrial
interference
environment)
EMC interference
According to EN 61000-6-3 (household
emission
environment), except EN 61000-3-2 for
professionally used equipment with a
total rated power greater than 1 kW
If several devices are connected in parallel on the supply side
so that the line current of the arrangement is in the range 16 - 75
A, this arrangement conforms to IEC 61000-3-12, provided that
the short-circuit power S
customer system to the public power grid is greater than or
equal to 250 times the rated output of the arrangement. It is the
responsibility of the installation engineer or operator/owner of the
device to ensure, if necessary after consultation with the
network operator, that this device is only connected to a
connection point with an S
times the rated output of the arrangement.
Item no. 53813-5-9970 · ENU · Change 260823 · Approved 2022-06-28 · Page 6 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
sc at the connection point of the
sc value greater than or equal to 250

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Cutting and crushing hazard when removing device
from packaging
Blades can bend
→ Carefully remove the device from its packaging, by the fan
housing. Strictly avoid shocks.
→ Wear safety shoes and cut-resistant safety gloves.
CAUTION
Device weighs over 25 kg! Heavy load when unpacking
device.
Risk of physical injury, such as back injuries.
→ Use suitable hoisting equipment to remove the device from
its packaging.
CAUTION
The blades of the impeller could be damaged.
→ Carefully set down the fan on a soft surface. Make sure the
blades are not subjected to load.
→ Following installation, make sure the impeller moves
easily and that the blades of the impeller are not deformed or
bent and do not catch at any point.
NOTE
Damage to the device from vibration
Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration
from sections of the installation.
→ If the fan is connected to air ducts, the connection should
be isolated from vibration, e.g. using compensators or similar
elements.
→ Ensure stress-free attachment of the fan to the
substructure.
; Check the device for transport damage. Damaged devices are not to
be installed.
; Install the undamaged device in accordance with your application.
CAUTION
Possible damage to the device
If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of
installation until all fastening screws have been tightened.
The fan must not be strained on fastening.

4.2 Electrical connection

DANGER
Voltage on the device
Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

Advertisement

Table of Contents
loading

Table of Contents