(Art. # 5231)
Binary input with 4 channels
KNX IO 411 (4Ii)
Application area
The KNX IO 411 (4Ii) is compact binary input with 4 channels to
control lights, shutter etc. with conventional switches or contacts.
Inputs are designed for dry contacts.
Two push buttons and three LEDs allow a local operation and a
visualization of the device state.
In addition to the input channels the device includes 16 inde-
pendent functions for logic or timer control.
1. Installation and Connection
The KNX IO 411 (4Ii) is designed for installation on a DIN rail (35
mm) with a width of 1 unit (18 mm). An installation-friendly de-
sign with pluggable screw terminals helps to reduce the cost of
commissioning. It features the following controls and displays:
KNX bus connector
Programming LED
Button f. programming mode
1/1 LED (multicolor )
WEINZIERL
Ch/M LED (multicolor )
1/1
Ch/M
2/2 LED (multicolor )
2/2
Button A1
A
1
P/Esc
Button B2
B
2
Pluggable screw terminals
411
This device is powered by the KNX bus. An external power
supply is not necessary
The device is not working without bus power.
©2019 WEINZIERL ENGINEERING GmbH
A.
KNX Programming mode
The KNX programming mode is activated/deactivated either by
pressing the flushed KNX programming button
neously pressing the buttons
When the programming mode is active, the programming LED
and LED Ch/M
light red.
2. Manual operation and status display
The LED Ch/M
lights up or flashes if the device is successful-
ly powered by the KNX bus
By pressing button A1
long, the manual operation mode will
be entered for channel pair A (Ch A In1/In2). This is indicated by
cyclic single flashing of LED Ch/M
By pressing button B2
long, the manual operation mode will
be entered for channel pair B (Ch B In1/In2). This is indicated by
cyclic double flashing of LED Ch/M
If manual operation of a channel pair is activated, the bus tele-
grams of In1 and In2 can be triggered by button A1
, if input channel is configured by ETS.
LED 1/1
and LED 2/2
lected channel pair while manual operation. They light green
when the button A1
or B2
Summary of the states of LED Ch/M
LED Status
Meaning
LED lights green
Device is working in standard operation mode.
LED lights red
Programming mode is active.
LED flashes 1x
Programming mode is not active.
orange
Manual operation is active:
Switching first channel pair (Ch A In1/In2)
LED flashes 2x
Programming mode is not active.
orange
Manual operation is active:
Switching first channel pair ( Ch B In1/In2)
Programming mode is not active.
Manual operation is not active.
LED blinks red
The device is not properly loaded
e.g. after an interrupted download .
LED blinks green
The device is currently loaded by the ETS.
3. Reset to factory device settings
It is possible to reset the device to its factory settings:
Disconnect the KNX Bus connector
Press the KNX programming button
pressed down
Reconnect the KNX Bus connector
Keep the KNX programming button
least another 6 seconds
A short flashing of all LEDs (
successful reset of the device to factory default settings.
or by simulta-
and
.
in orange.
in orange.
and B2
are used to indicate state of se-
is pressed.
:
from device
and keep it
of device
pressed for at
❷❹❺❻
) visualizes the
Page 1/11

Advertisement

loading
Need help?

Need help?

Do you have a question about the KNX IO 411 (4Ii) and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Weinzierl KNX IO 411 (4Ii)

  • Page 1 Keep the KNX programming button pressed for at • least another 6 seconds ❷❹❺❻ A short flashing of all LEDs ( ) visualizes the • successful reset of the device to factory default settings. ©2019 WEINZIERL ENGINEERING GmbH Page 1/11...
  • Page 2: Wiring Scheme

    KNX IO 411 (4Ii) This parameter is used to configure the manual operation on the (www.weinzierl.de) or from the ETS online catalogue. The follow- device. The manual operation mode can be disabled or activated ing pages and parameters are visible in the ETS.
  • Page 3 Lock active on 1 Dimming Lock active on 0 Shutter Behavior of (…) on start Send value The telegram can be configured here, which is sent when the lock is activated. Scene Impulse counter ©2019 WEINZIERL ENGINEERING GmbH Page 3/11...
  • Page 4 On selection of function Dimming following objects are visible: Group Object Type KNX Size Direction GO 11 Input A1: Dimming on/off – Switch 1.001 1 Bit To KNX GO 12 Input A1: Dimming relative – 3.007 4 Bit To KNX Brighter/Darker ©2019 WEINZIERL ENGINEERING GmbH Page 4/11...
  • Page 5 On selection of Scene function the following object is visible: Group Object Type KNX Size Direction GO 11 Input A1: Scene - Scene control 18.001 1 Byte To KNX ©2019 WEINZIERL ENGINEERING GmbH Page 5/11...
  • Page 6 An additional parameter is displayed to configure the sending frequency of the counter variable. On change and cyclically Both sending conditions are active. If the counter is locked by the object, also cyclic sending is stopped. ©2019 WEINZIERL ENGINEERING GmbH Page 6/11...
  • Page 7 A floating-point value is to be entered here. It determines the value by which the counter value is increased on every pulse ©2019 WEINZIERL ENGINEERING GmbH Page 7/11...
  • Page 8 - Output in m/s: 1/4 = 0.25 On change and cyclically - Output in km/h: 1/4 * 3.6 = 0.9 Both sending conditions are active. Time base: Pulses per second Measurement time span: 10 s ©2019 WEINZIERL ENGINEERING GmbH Page 8/11...
  • Page 9 This also allows to create complex structures. For this purpose, the output of a function is set to the same group address as the input of the next function. ©2019 WEINZIERL ENGINEERING GmbH Page 9/11...
  • Page 10 Input on (1) is converted into output off (0). Input off (0) is con- verted into output on (1). Group Object Type KNX Size Direction Logic - Gate input - Input 1.002 1 Bit From KNX Logic - Gate output - Output 1.002 1 Bit To KNX ©2019 WEINZIERL ENGINEERING GmbH Page 10/11...
  • Page 11 The power rating is indicated on the side of the product. ETS4/5 Database Weinzierl Engineering GmbH www.weinzierl.de/en/products/411/ets4 D-84508 Burgkirchen / Alz Germany Datasheet www.weinzierl.de www.weinzierl.de/en/products/411/datasheet info@weinzierl.de CE Declaration 2019/07/30 www.weinzierl.de/en/products/411/ce-declaration ©2019 WEINZIERL ENGINEERING GmbH Page 11/11...