CHAP.07 POSITIONING AND CONNECTIONS FOR THE INSTALLER

07.1

HYDRAULIC CONNECTION AND EXTERNAL AIR INTAKE SETTINGS

The device must only be installed indoors and on surfaces that can support the load. If the existing construction does not meet this
requirement, it will be necessary to take appropriate measures (e.g. installing a load distribution plate). The appliance must be installed
in an area where the appliance itself, gas exhaust pipes and flue can be easily accessed for maintenance.
max 1250
1
4
200
NOTE
The external air intakes must be made so that they cannot get accidentally covered and if they have an insect protection
mesh they must be cleaned periodically to prevent clogging with dust and dirt, especially in periods with intense pollen
concentrations.
NOTE
The hydraulic kit does not include cut-off valves. Therefore, we recommend these valves are installed on each stove
hydraulic connection during installation.
Use outlet type valves leaving the pulley towards the stove (see CHAP.07.6 - HYDRAULIC KIT).
FOR THE SYSTEM FEED THE COLD WATER MUST BE CONNECTED TO THE APPLIANCE.
WARNING
At the end of installation, accurately clean the heating system to eliminate all work residue. Dirt deposits can
cause hydraulic components installed on the device such as the water circulator, anti-condensation valve, automatic air
breather valve and safety valve to malfunction.
Maintenance for problems due to these faults is not covered by the Jolly Mec warranty.
The device must be installed near walls made of non-flammable
Front view
material. The installation of the device near flammable walls
is allowed if observing the clearances specified below, or if a
proper protection is installed (surfaces such as floor, ceiling and
walls of the house near the device should be protected against
overheating).
The hydraulic connections between the wall and the appliance
must be made using flexible pipes.
Fig. 1 illustrates minimum distances that must be observed, all
measures must be in mm.
The lateral distance from the adjacent wall, according to
installation, is to be maintained on both sides.
1.
2
3
2.
3.
4.
View from
above
NOTE
NOTE
800
Minimum air distance from inflammable side wale: 200 mm
Minimum air distance from inflammable rear wall: 100 mm
Frontal air distance from inflammable material: 800 mm
as indicated in CHAP.06.1 - HOMOLOGATION
Electrical socket
External air inlet (see chap. 07.4)
Rear panel
Side panel
As indicated in the national reference standard
UNI 10683:2012, the product can not be installed
in rooms with a volume of under 15 m3.
Bear in mind that the minimum distances from
inflammable materials are: