2. Installation location
2.5. Constraints on indoor unit installation
You should note that indoor units that can be connected to this outdoor unit are the following constraints.
• Indoor units with model numbers 04-96 can be connected.
• When using Branch box, Indoor units with model numbers 06-36 can be connected.
• Refer to the table 1 below for possible room, indoor unit combinations.
Verification
The rated capacity should be determined by observing the table below. The unit's quantities are limited as shown in the following table 2. For the next step, make sure that
the total rated capacity selected will stay in a range of 50% – 130% of the outdoor unit capacity.
• MXZ-SM72
36 – 93 kBtu/h
• MXZ-SM96
48 – 124 kBtu/h
• MXZ-SM120 60 – 156 kBtu/h
Table 1-1: City Multi indoor units (P·FY series)
Indoor unit type
P04
Rated capacity
4
(Cooling) (kBtu/h)
Table 1-2: M series, P series, S series
Model No.
06
Rated capacity
6
(Cooling) (kBtu/h)
Combinations in which the total capacity of indoor units exceeds the capacity of the outdoor unit will reduce the cooling capacity of each indoor unit below their rated cooling
capacity. Thus, combine indoor units with an outdoor unit within the outdoor unit's capacity, if possible.
Table 2: Connectable indoor units quantities
• City Multi indoor units
SM72
1-23
SM96
1-30
SM120
1-30
• Branch Box system (M, S, P series indoor units via Branch box)
SM72
2*
– 12 (6) units *
1
SM96
2 – 12 (8) units *
SM120
2 – 12 (10) units *
Table 3: Connectable Branch box quantities (In case of Branch Box system)
Model
MXZ-SM72/96/120
*1 Only one unit connection is possible with SVZ-series unit.
*2 The number enclosed in parentheses is the maximum number of units that can be connected when 1 or more PLA-A·EA units is connected.
*3 When connecting PEAD-A24/30/36AA or SVZ series unit, the maximum total capacity of the units that can be connected each branch box is 60 kBtu/h.
*4 When connecting a SVZ-series unit(s), set additional constraints as follows.
For connections other than those specified below, consult your dealer.
Number of connecting SVZ-series unit
2
1
For connections other than those specified in 1 and 2, including connections with SVZ-series units, consult a dealer.
en
5
P05
P06
P08
P12
P15
P18
5
6
8
12
15
18
09
12
15
18
24
30
9
12
15
18
24
30
*
*
2
3
4
*
*
2
3
4
*
*
2
3
4
Branch box
1-3
Any indoor units other than SVZ-series units are not connectable.
Only 1 PEAD can be included in the connection.
P24
P30
P36
P48
P54
P72
24
30
36
48
54
72
36
36
Constraints (For each connected branch box)