Operating Instructions
NET-BOX-PS
5. Protocol Setup
PROFIsafe F-Address assignment using DIP Switch
To adjust the device PROFIsafe 'F-Address' the DIP switches located inside the NET-BOX are used. The
following steps can be performed with the device powered on or off, note the final step if the device is
powered.
•
Remove the lid screws and turn over the NET-BOX Lid to locate the DIP switches (see below).
•
Using a small tool push the required switches to the 'ON' position to set the corresponding bit.
•
The address is given by adding the values of the DIP switches in the ON position.
•
Cycle power to the NET-BOX OR press and hold the reset button until the LEDs turn red then release
to reset the device.
•
The NET-BOX will restart with the configured F-Address.
•
Replace the NET-BOX Lid and Lid screws, ensuring a tight seal of the lid.
INFORMATION
•
The example given in the image above shows only switches 2, 16 and 64 set to the
'ON' position. When adding these numbers up the resulting F-Address is 82.
102637 2303 NET-BOX-PS Operating Instructions