Page 1
For Amazing technical support on Optex IO-LINK contact Ramco today! *FASTUS is a product brand of OPTEX FA. IO-Link Digital I/O Module UR-DS16D Got questions on your application for IO-LINK ?? email us at nsales@ramcoi.com UR-DS16T UR-DS8D8T User’s Manual OPTEX FA CO., LTD.
Page 2
Trademarks and registered trademarks appearing in this manual are the property of their respective owners. The copyright of this user’s manual is owned by OPTEX FA Co., Ltd. All the contents contained herein are protected by copyright law. Unauthorized copying of this manual is strictly prohibited.
Contents Overview ..............................6 Included items ............................6 Dimensions ............................7 Installation .............................. 8 System Configuration..........................9 Connection ............................10 Wiring to the IO-Link Master ....................... 10 Wiring to the I/O Power Supply ......................11 Wiring to the I/O Terminal block......................11 Part Names ............................
1. Overview The UR-DS16D IO-Link Digital I/O Module is a IO-Link digital input unit that transfers 16 points of digital input ON/OFF signals (from a device such as a sensor or switch) to the process input data of an IO-Link master. The UR-DS16T IO-Link Digital I/O Module is a IO-Link digital output unit that outputs process output data transferred from the IO-Link master as 16 points of digital output ON/OFF signals to a device such as an actuator.
4. Installation Follow the steps below to install this product. 1. Hook the upper hook on the back of the product to the DIN rail. 2. Push the lower side from the front. 3. Push the DIN rail mounting hook up to lock the production in place. Install this product at least 10 mm away from an adjacent device and structure.
6. Connection Wiring to the IO-Link Master Connect the IO-Link master to either the e-CON socket on this product or the push-in terminal block (power/IO-Link terminal block). C C onnecting to the IO-Link communication e-CON socket Applicable wires should be between AWG 28 to 20 stranded wires with a rated temperature of 75°C or higher.
Wiring to the I/O Power Supply Supply power to input and output devices to the push-in terminal block. Applicable wires should be between AWG 24 to 12 stranded wires with a rated temperature of 75°C or higher. The length of stripped insulation from the wire for rod type crimp terminal, solid or stranded wires is from 9 to 10 Wiring to the I/O Terminal block.
7. Part Names UR-DS16D N N o. N N ame F F unction POWER LED green Turns on when the unit power is turned on. COM LED green Illuminated: After startup, before IO-Link communication is established 1 second on 0.1 second off: IO-Link communication established 0.55 second on 0.55 second off: Find me 0.1 second on 0.1 second off: IO-Link communication cutoff NPN LED (green)
N N o. N N ame F F unction (10) e-CON socket Unit power (+24 V, 0 V) and C/Q can be wired to the IO-Link master via (four poles) the e-CON socket. (11) DIN rail mounting hook Slides for attaching/removing the product to/from the DIN rail. UR-DS16T N N o.
Page 14
Unit power (+24 V, 0 V) and C/Q are connected internally with the terminals of the e-CON socket, and either the power terminal block or e-CON socket can be connected to the IO-Link master. e-CON socket Unit power (+24 V, 0 V) and C/Q can be wired to the IO-Link master via (four poles) the e-CON socket.
UR-DS8D8T Input power supply is Power supply for o o utput is 24 V, 0 V L+, M N N o. N N ame F F unction POWER LED green Turns on when the unit power is turned on. COM LED green Illuminated: After startup, before IO-Link communication is established 1 second on 0.1 second off: IO-Link communication established 0.55 second on 0.55 second off: Find me...
Page 16
N N o. N N ame F F unction I/O power supply terminal Supplies 0 V to input and output devices. block Left 8 terminals: for input devices (0V) (Left eight terminals: 0V, Right 8 terminals: for output devices (M) Right eight terminals: M) Power terminal block Supplies unit power, input power (+24 V, 0V) and output power (L+, M).
8. Specifications General specifications (common) I I tem S S pecifications Power supply voltage 24 VDC +/-15% (*1) Current consumption 50 mA max. (for 24 VDC) Operating temperature 0 to +55°C (no freezing) Operating humidity 5 to 95% RH (no condensation) Storage temperature -25 to +75°C (no freezing) Storage humidity...
IO-Link specifications I I tem S S peci i fications Host communication interface IO-Link (operates as device) Process input data byte UR-DS16D 2 bytes count UR-DS16T 2 bytes UR-DS8D8T 2 bytes Process output data byte UR-DS16D 1 byte count UR-DS16T 4 bytes UR-DS8D8T 3 bytes...
Output Specifications I I tem S S tandard output H H igh current output Output points UR-DS16T UR-DS8D8T High current output function Channel C to F for Source, PNP, output Dielectric withstanding voltage 500 volts AC for one minute between I/O terminal batch and IO-Link batch Insulation resistance 10 MΩ...
Input 3 Input 2 Input 1 Input 0 Output Reserved 1 byte Word assignment Example: When using the IO-Link master of OPTEX FA (default setting: little endian) <Overview> Process Byte Byte No. Details data Higher order byte Lower order byte...
Output 6 Output 5 Output 4 Output 3 Output 2 Output 1 Output 0 Word assignment Example: When using the IO-Link master of OPTEX FA (default setting: little endian) <Overview> Process Byte Byte No. Details data Higher order byte Lower order byte...
Output D Output C Output B Output A Output 9 Output 8 (0: OFF, 1: ON) Word assignment Example: When using the IO-Link master of OPTEX FA (default setting: little endian) <Overview> Process Byte Byte No. Details data Higher order byte...
Page 24
<Details> Process Byte No. Details data Lower order byte Input status Input (0: OFF, 1: ON) 1 word Higher order byte Overcurrent status (0: normal, 1: overcurrent) Lower order byte Output control (0: OFF, 1: ON) Higher order byte Output PNP/NPN setting (0: PNP, 1: NPN) Output...
11. Service Data The service data for this product that can be read and written via IO-Link ISDU handling is as follows. UR-DS16D Name Setting details System 130: Initialization of setting value command 131: Stops IO-Link communication after reverting setting values to default values (Back-to-Box) Device lock 0: Unlocks the storage function.
UR-DS16T N N ame Setting details System 130: Initialization of setting value command 131: Stops IO-Link communication after reverting setting values to default values (Back-to-Box) Device lock 0: Unlocks the storage function. 2: Storage function lock. Tag name Can be used to set a name for this unit, such as the device function or installation location.
UR-DS8D8T N N ame Setting details System 130: Initialization of setting value command 131: Stops IO-Link communication after reverting setting values to default values (Back-to-Box) Device lock 0: Unlocks the storage function. 2: Storage function lock. Tag name Can be used to set a name for this unit, such as the device function or installation location.
Page 28
N N ame Setting details Device 0: Normal status identification 1: Flash the COM LED at 0.55 second intervals request (Find me) *1 R: Read only, W: Write only, R/W: Read/Write *2 The default value is 32 ” ” (asterisk) characters. 12.
Page 29
13. Troubleshooting How to handle this product when it does not work properly or when problems occur. S S ymptom C C heckpoints and countermeasures POWER LED does not light up Check that voltage is applied to the Unit power’s 24 V and 0 V and the I/O power’s L+ and M.
Page 30
S S ymptom C C heckpoints and countermeasures Input status cannot be read by the Check that IO-Link communication is established (COM LED lights up host for 1 second and turns off for 0.1 second). Check that communication is established between the connected IO- Link Master and the field network.
Page 31
S S ymptom C C heckpoints and countermeasures OVERC LED is blinking Overcurrent protection is occurring due to output load. For capacitive loads or inductive loads such as electromagnetic switches, the blinking may be caused by inrush current. In this case, try switching to channels C to F large-capacity output (PNP side only).
Page 32
Specifications and technical information not mentioned here are written in Instruction Manual. Or visit our website for details. All the warnings and cautions to know prior to use are given in Instruction Manual. OPTEX FA CO., LTD. 91 1 Chudoji-Awata-cho o Shimogyo-ku u Kyoto o 600-8815 5 JAPAN TEL.