Idem NET-BOX-CS Operating Instructions Manual

Safety io, standard io, and integrated ethernet/ip with cip safety.

Advertisement

Quick Links

IDEM Safety Switches
NET-BOX-CS
Safety IO, Standard IO, and Integrated EtherNet/IP with CIP Safety.
Operating Instructions
Original Instructions - To request this document in other languages please contact
info@idemsafety.com

Advertisement

Table of Contents
loading

Summary of Contents for Idem NET-BOX-CS

  • Page 1 IDEM Safety Switches NET-BOX-CS Safety IO, Standard IO, and Integrated EtherNet/IP with CIP Safety. Operating Instructions Original Instructions - To request this document in other languages please contact info@idemsafety.com...
  • Page 2: Table Of Contents

    Safety Inputs ........................11 Safety Outputs ........................11 Mechanical Data ....................... 12 Environmental Data ......................12 Reliability / Safety Data (EN ISO 13849-1) ................. 12 Reliability / Safety Data (EN 62061 / IEC 61508) ............... 12 102638 2305 NET-BOX-CS Operating Instructions Contents...
  • Page 3: System Overview

    All relevant safety regulations and standards are to be observed. The NET-BOX-CS complies with the requirements of Cat. 4 / PL e and SIL 3 in accordance with ISO 13849-1, IEC 62061 and IEC 61508. The device implements the following safety functions: •...
  • Page 4: Installation & Maintenance

    Repair or modification of the NET-BOX is not allowed unless authorised by IDEM and carried out according to operating guidelines. • Safety critical failures which do not lead to the safe state shall be reported to IDEM immediately. • Replace a malfunctioning NET-BOX immediately.
  • Page 5: Electrical Connection

    • Not all connections are required for all applications, the minimum requirement to operate the device is one data connection and one power connection. All 4 ports are utilised when the NET-BOX is used a ‘daisy chain’ configuration. 102638 2305 NET-BOX-CS Operating Instructions...
  • Page 6: Protocol Setup

    After the detection of a safety critical error, the NET-BOX shall not be kept in fail- safe state for more than 1 hour. INFORMATION • The device EDS file can be found via the NET-BOX product page of the IDEM website www.idemsafety.com/products or alternatively please contact technical@idemsafety.com 102638 2305 NET-BOX-CS Operating Instructions...
  • Page 7: Network Address - Setup/Initial Setting

    Replace the NET-BOX Lid and Lid screws, ensuring a tight seal of the lid. INFORMATION • The example given in the image above shows only switches 2, 16 and 64 set to the ‘ON’ position. The resulting IP address is: 192.168.1.82 102638 2305 NET-BOX-CS Operating Instructions...
  • Page 8: Setting Via Dhcp

    8. Cycle power to the NET-BOX or press and hold the reset button until the LEDs turn red then release to reset the device. The NET-BOX will restart with the configured IP address and with DHCP disabled. 102638 2305 NET-BOX-CS Operating Instructions...
  • Page 9: Studio 5000 Ethernet/Ip Configuration

    Open or create a project with the PLC CPU, Partner and Ethernet/IP modules added. Right click the Ethernet module and select ‘New Module…’ Find and select the NET-BOX (will only appear if EDS file imported correctly), click ‘Create’. 102638 2305 NET-BOX-CS Operating Instructions...
  • Page 10 Operating Instructions IDEM Safety Switches NET-BOX-CS Set the device name (customisable – ‘NET-BOX-CS’ used as example only) and set the previously configured IP address. Change the Safety Network Number (SNN) to match that of the controller/PLC. On the ‘Safety’ tab, uncheck the ‘Configuration Signature’ box, press OK.
  • Page 11: Factory Reset

    Confirm correct operation of each safety input device including the lid mounted E-Stop (if fitted). • Expected operation of all control circuits. Data Map See technical datasheet supplied with product. For assistance please contact: technical@idemsafety.com 102638 2305 NET-BOX-CS Operating Instructions...
  • Page 12: Diagnostic Indication

    Diagnostic LED’s are not reliable indicators and cannot be guaranteed to provide accurate information. They should only be used for general diagnostics during commissioning or troubleshooting. Do not attempt to use LEDs as operational indicators. 102638 2305 NET-BOX-CS Operating Instructions...
  • Page 13: Technical

    Voltage Digital Input Low Current Digital Input High Current Digital Input Low Safety Outputs Parameter Unit Typ. Voltage Digital Output High 19.2 Current Digital Output High Current Digital Output Low Inductive Load Capacitive Load Short Circuit Peak 102638 2305 NET-BOX-CS Operating Instructions...
  • Page 14: Mechanical Data

    Mission Time 20 years SIL CL SIL 3 PFHd 2.3E-9 (Emergency Stop Function) PFHd Safety Inputs 2.4E-9 (voltage free contacts with test pulses) PFHd Safety Inputs 2.4E-9 (OSSD inputs to device) PFHd Safety Outputs 2.4E-9 102638 2305 NET-BOX-CS Operating Instructions...
  • Page 15 Operating Instructions IDEM Safety Switches NET-BOX-CS NOTES: 102638 2305 NET-BOX-CS Operating Instructions...
  • Page 16 EC / EU Declaration of Conformity MANUFACTURER: EU REPRESENTITIVE: ADDRESSES: IDEM SAFETY SWITCHES LIMITED IDEM SAFETY SWITCHES Ro SRL Hindley Industrial Estate Hindley Green Bloc OD6, nr. 35 Wigan Bulevardul Timișoara Lancashire București WN2 4HR 061344 United Kingdom Romania DEVICE(s):...