Page 1
TRA-102D TRANSMITTER Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 mA outputs Instruction Manual...
Page 2
Instruction manual for use of TRA-102D transmitter Transmitter is designed for measurement of ambient air temperature at °C or °F and relative humidity of air without aggressive ingredients with computing one of the following values: dew point temperature, absolute humidity, specific humidity, mixing ratio and specific enthalpy.
Page 3
Electrical system (wiring) may do only worker with required qualification by rules in operation. Dimensions Typical application wiring Calculation of minimum power voltage Uss for proper operation: Uss min> Uo min + Imax * Rz, where: Uo min= 9 V Imax...
Page 4
Range and type of value for output 1 (current loop I1 = symbol „1“on display). Type of value, assigned to output 1, is indicated by displayed unit (here %RH = relative humidity). Upper line displays current value corresponding to measured value (lower line). Here 4 mA corresponds to 0 %RH Press button again to get value for upper point (same output, same value) similarly as at previous point.
Page 5
Technical parameters: Accuracy data shown are for value displayed on LCD display. For value on analog output is valid too, if selected output range is set inside measuring range. Analog outputs: Two galvanic isolated current loops with range from 4 to 20 mA Current output in case of error: <3.8 mA or >24 mA Power: 9 to 30 V dc, maximum ripple 0.5 % Measuring parameters:...
Page 6
Communication with computer: via USB port by means of USB communication cable ATS- AC17 Protection: electronics IP65, sensors are located in cover with IP40 protection Air filter: filtering ability 0.025 mm Operating conditions: Operating temperature range: -30 to +80 °C, over +70°C switch LCD display OFF Operating humidity range: 0 to 100 %RH Outer characteristics in accordance with EN 33-2000-3: normal environment with the specifications: AE1, AN1, BE1...
Page 7
Error States of the device Device continuously checks its state during operation. In case error is found LCD displays corresponding error code: Error 0 First line displays „Err0“. Check sum error of stored setting inside device’s memory. Output value is < 3.8 mA. This error appears if incorrect writing procedure to device’s memory occurred or if damage of calibration data appeared.