7.3.2 Cleaning output

When selecting "Cleaning Output" in "Main Menu" -> "Alarm Set" -> "Relay X" ->
"Function Set" menu , the relay is in the cleaning output state, the relay can be closed
periodically to do cleaning control.

7.3.3 Cleaning state

Select the state of the measured value during cleaning.
After selecting "Keep", when cleaning, the measured value displayed maintains the value
before the relay action.After selecting "Continuous", the measured value is the real-time
value of continuous measurement.

7.3.4 ETEMP

alarm
When "Ambient Temperature Alarm" is selected in the "Main Menu" -> "Alarm Settings" ->
"Relay X" -> "Function Settings" menu, the relay is in the alarm control output state. The
relay status is controlled by the working environment temperature of the instrument. When
the environment temperature exceeds 50°C, the relay is closed.
7.4 Current set
The meter provides two current signal outputs with independent parameters that can be set,
corresponding to the "Current 1" and "Current 2" menus respectively. The user can set the
corresponding channels and upper and lower limits of the two currents respectively.
Lower value<upper value
20mA
4-20mA type
4mA
Lower value<upper value
20mA
0-20mA type
0mA
Lower value
Upper value
Lower value
Upper value
20mA
4mA
Value
Upper value
20mA
Value
0mA
Upper value
- 12 -
Lower value>upper value
4-20mA type
Value
Lower value
Lower value>upper value
0-20mA type
Value
Lower value