Updating the MPA2C3 Panel Using the Web Interface

Step 1: Installing the new App File
1. Navigate to the web server Panel Configuration > Advanced > File Manage-
2. Under Download (To Panel) click Browse to locate the application bin file.
3. Select the file and click Download. Click OK to continue. Once the "Download
4. You will see the Download to primary panel complete; now processing the
Step 2: Installing the new OS File + Application
Note: This procedure is not necessary if the panels are already at the latest OS.
1. Navigate to the web server Panel Configuration > Advanced > File Manage-
2.
3. Select the file and click Download. Click OK to continue. Once the "
4. You will see the "
5. Clear Cache and Cookies: This time, before logging back in, use the browser-
Step 3: Verifying that the Installed Versions are Correct
1. Navigate back to the web server Menu > Panel Configuration > Settings.
2.
3. If you notice any communication issues, and the upgrades are complete,
MPA2C3 User Manual
ment > Upload (To Panel).
to primary panel complete; now processing the image" message pops up, click
OK again.
image message once again. Click OK. This time a reboot will be triggered and
you will see the message: "
click Refresh and log back in
ment > Upload (To Panel).
Download
Under
, click
primary panel complete; now processing the image"
again.
Download to primary panel complete; now processing the image
once again. Click OK to continue. This time a reboot will be triggered. It
message"
will take approximately 10 to 15 minutes for the OS + Application to complete
the install.
dependent steps found in
the MPA2C3 Web Server
away from the current web screen, clear the files, and then navigate back.
In the Firmware Version section, you should see the latest application versions listed as 1.0.3.x.
In the Operating System section, you should see the latest OS version.
typically this means there is more than one panel set up as a primary on the
active loop. You should disconnect each panel from the 485 loop (C-TB9), and
cycle power on all the panels on the loop. Once all panels are powered up,
reconnect the 485 loop to clear the issue.
The Panel is now rebooting. Wait
."
Browse to locate the latest OS + Application file.
Clearing the Cache and Cookies in the Internet Browsers Used by
, to clear your browser cache and cookies. You can navigate
5-7 minutes
, then
Download to
message pops up, click OK