IQ HEAT 135/200 INSTALLATION MANUAL
IQ Heat 135/200
CHOOSE
STEP
1
INSTALLATION
LOCATION
LEARN
STEP
2
INTO
PANEL
Place your panel in
"auto learn" mode
✓
Ceilings
Walls
✓
"Tamper" the device
OVERVIEW
The IQ Heat 135/200 wireless heat detector uses electronic processing to detect
heat conditions plus a wireless transmitter (319.5MHz) in one unit. The micro-
processor trips the transmitter when the temperature at the detector location
reaches a fixed temperature of 135°F (57°C) or 200°F (93°C), depending on
selection, or senses a rate of rise at 12°F to 15ºF (6.7 to 8.3ºC) per minute.
SPECIFICATIONS
Rate of Rise rating: 12° to 15°F (6.7° to 8.3°C) per minute
UL Max Ambient Ceiling Temp: 100°F/150°F (37.8°C/65.6°C)
Operating Temp: 32°F to 150°F (0 to 65.6°C)
Storage Temperature: -30 to 167°F (-34 to 75°C)
Relative Humidity: 0 to 95% noncondensing
Maximum UL Spacing: 50ft (15.2M) x 50ft (15.2M)
Frequency: 319.5MHz (crystal-controlled)
Expected Battery Life: 10 Years
Standby Current: Less than 0.9µA
Supervision Interval: 62 - 68 minutes
Enclosure Dimensions: Diameter: 2.29" (58.25mm). Height: 1.28" (32.4mm)
Regulatory:
-
UL 521 Heat Detectors for Fire Protective Signaling Systems
-
UL985 Household Fire Warning System Units
-
CAN/ULC-S530 Heat Actuated Fire Detectors for Fire Alarm Systems
-
CSFM Category 7270
-
FCC: 15.109 Class B, 15.231
-
Industry Canada: ICES-003, RSS-210
-
Heat detectors should be installed to provide property
protection. Reliance should not be placed on heat sensors for life
safety. Where life safety is involved, smoke sensors must also be
installed.
-
The detectors allow for normal temperature fluctuations;
however, ceiling temperatures should not exceed 100°F (37.8°C)
-
Mount the detector in a central location of the area to be
protected, either on the ceiling or on a wall.
-
If mounting on a ceiling, the detector must be at least 4 in. (10
cm) away from any walls.
-
If mounting on a wall, the top of the detector must be within 4 to
6 in. (10 to 15 cm) of the ceiling.
-
The UL maximum spacing allowance of the detector is 50 x 50
ft. (15 x 15 m). Refer to the NFPA Standard 72 for application
requirements.
-
Do not mount the detector close to devices that change
temperature rapidly, such as ovens, heat vents, furnaces, or
boilers.
ADD
Customize name and settings as
desired and touch "ADD"