10          MSI OTM Installation and Operation Manual
Control Theory
The Oil Tank Monitor measures and displays the number of inches of oil in a tank, and can activate an alarm if the oil level falls below 
a user‐configured number of inches. The unit is designed to transmit the tank level (via the MSI Hub) to the Platinum Control, which 
then sends the information to the Internet Control Management System (ICMS). This allows remote users to monitor the level of the 
tank and send out alarms if the tank level is outside the desired range.
The Oil Tank Monitor has a pump for automatic pressure compensation. An internal timer energizes the pump at regular intervals to 
ensure correct operation. The pump can also be programmed to activate immediately for testing or after maintenance.
The Oil Tank Monitor's internal programming mode allows adjustment of the Alarm value (in inches) and provides an offset for tube 
placement in the oil tank. Once programmed, these values will not be lost if power is interrupted or lost. The program values are 
displayed, allowing precise adjustment for each setting.
Programming the OTM
Figure 2: Oil Tank Monitor User Interface
1. Press the MENU/SET button once to enter programming mode.
2. Use the up/down arrow buttons to navigate through the menu options. When the desired menu option is found, press the 
MENU/SET button to select the option. Press the BACK button to return to the previous screen.
3. Continue setting programming options using the up/down arrow, MENU/SET, and BACK buttons until all options have been 
configured.
4. After all options have been configured, press the Back button until the OTM main display is reached, showing the current oil 
level in the tank (in inches).
059411-00 Rev. A