Dear Customer! Thank you for choosing a Rittal Liquid Cooling Package DX (referred to hereafter also as "LCP DX"). This documentation applies to device LCP Inline DX 20 (DX = Direct Expansion). Please take the time to read this documentation carefully and pay particular attention to the safety instructions in the text and to section 2 "Safety instructions".
CE labelling Other applicable documents Rittal GmbH & Co. KG hereby confirms that the cooling The general plant documentation for the room where the units in the LCP DX series are compliant with the EMC...
2 Safety instructions Safety instructions Danger! Risk of poisoning from coolant The devices in the LCP DX series produced by Rittal gases created under the influence of GmbH & Co. KG are developed and produced with due heat. regard for all safety precautions. Nevertheless, the unit...
Note: Caution! Risk of malfunction or damage! Rittal offers leak testing of the device as a In order to prevent EMC-related mal- service. functions during operation, and to allow access for servicing purposes, cross- 2.3.1...
2011/65/EC on the Restriction of Use of Certain Hazard- ous Substances in Electrical and Electronic Equipment (RoHS) of 1 July 2011. Note: Corresponding information about the RoHS Directive may be found on our website at www.rittal.com/RoHS. Rittal Liquid Cooling Package...
(U) of the 482.6 mm (19") level must be sealed with blanking plates, which are available as Rittal accessories (see section 13 "Accessories"). The more devices are installed in the server enclosure, the more important it becomes to follow this specification.
Existing cable entry glands are additionally sealed e.g. using suitable brush strips. Fig. 3: LCP DX front – open front door LCP door Display Rack Electronics box with switches for fans Rittal Liquid Cooling Package...
An external condenser is required in order to operate the inverter, which controls the speed of the compressor device. Only Rittal-supplied condenser units may be and therefore allows the cooling output to be precisely used. The following options are available: adapted to the actual cooling requirement.
Air baffle plate stalled equipment. DC connection cable (control voltage) – Using a different condenser unit not supplied by Rittal. PE conductor connection – Use of impermissible tools. – Improper operation.
Damage and other faults, e.g. incomplete de- lifting gear and load-bearing devices livery, should immediately be reported to the with sufficient load capacity. shipping company and to Rittal GmbH & Co. KG in writing. Place the unit in its intended location.
Please also observe the instructions and data Fig. 8: Relative positioning above the LCP DX relating to the coolant connection as outlined in section 6 "Installation". Offset in a side direction Condenser offset above the LCP DX Rittal Liquid Cooling Package...
For easier servicing of the LCP DX, maintain All the components needed for cold aisle a distance of at least 1 m between the front containment are available from Rittal as ac- and rear of the device and the nearest wall. cessories.
5.2.2 Fit the attenuators strips and air baffle plates, are available as Rittal accessories (see section 13 "Accesso- If applicable, attenuators may be fitted underneath the ries"). unit for vibration insulation. For this purpose, the entire LCP DX must be lifted up.
(see section 13 "Accessories"). On the side of the server enclosure opposite the LCP DX, mount a side panel on the two side panel Rittal Liquid Cooling Package...
Using the assembly screws, mount the assembly Using the corresponding assembly screws, fasten components (2 side panel mountings, 2 side panel three baying connectors each (fig.13, item 2) onto the mounting brackets, 6 side panel holders) onto the side Rittal Liquid Cooling Package...
The following instructions on siting the exter- Console installation nal condenser apply equally to all condenser types available at Rittal. The condenser is weather-resistant and may therefore be installed completely in the open air, with no need for a weather protection canopy etc. If the condenser is in-...
Page 20
Fig. 17: Horizontal or vertical mounting In the case of vertical mounting (with a horizontal air- flow), the hot gas line must be laid above the liquid line. Fig. 18: Laying the hot gas and liquid lines Rittal Liquid Cooling Package...
(two-phase flow, oil transportation in part-load opera- disconnection should be provided. tion), condensation processes, thermal expansion, vi- bration, and good accessibility. Rittal Liquid Cooling Package...
Page 22
5. The gas line must be laid with an incline of 1% in the of the installed moulded parts. The equivalent length direction of flow of the coolant. makes allowance for pressure loss from moulded parts Rittal Liquid Cooling Package...
Page 23
Before starting sol- structure and the connected devices. dering, introduce a generous nitrogen flow, when starting soldering reduce it to a minimum and main- tain this low protective gas flow during the entire sol- dering process. Rittal Liquid Cooling Package...
EN 1779:1999 may be used as a basis for this test. The detector must be calibrated at regular intervals as per the manufacturer's instructions. Any leak detected must be repaired and subjected to a further leak test. Rittal Liquid Cooling Package...
No additional control equipment may be connected upstream of the device at the supply end. Before operating on the electrical panel please wait a few minutes. The LCP DX and the external condenser are supplied with voltage independently of one another. Rittal Liquid Cooling Package...
(L1, L2, and L3) to a length of approxi- mately 35 mm. Leave the length of the PE conductor at approximately 45 mm. Remove approximately 9 mm from the insulation of all conductors with a suitable tool. Rittal Liquid Cooling Package...
5. Inspect the report on the cooling system leak test. 6. Visually inspect the cooling system. 7. Check the labels. This inspection must be documented; see EN 378-2, section 6.4.3. No cooling system may be operated with- out the correct documentation. Rittal Liquid Cooling Package...
Change the status of the device in the "On/Off Unit" menu from "On" to "Off" (see section 7.6 "Menu level A "On/Off Unit""). Switch off the LCP DX and the condenser at their re- spective master switches. Rittal Liquid Cooling Package...
Press the "Down" button to select the "ON" entry. Press the "Return" button to edit the selected param- Delay Alarm Time delay by which the alarm is output. eter value. Tab. 7: Settings in menu B02 Rittal Liquid Cooling Package...
Menu D01 – D06 The pLAN device addresses of the display and the The current values of the analog inputs are displayed in motherboard are displayed in menu F01. This may be menus D01 to D06. Rittal Liquid Cooling Package...
20 seconds whilst the card is – Microsoft Internet Explorer booting up, until the status LED flashes three times – Mozilla Firefox slowly. Rittal Liquid Cooling Package...
Enter the fixed IP address via which you wish to ac- Enter admin as the user and fadmin as the pass- cess the network interface under Eth0 in the IP Ad- word. dress main field. Rittal Liquid Cooling Package...
The procedure for configuration is described in the original user instructions for the pCO Web card from Carel. These instructions can be found at the following ad- dress: http://www.carel.com/carelcom/web/eng/catalogo/ prodotto_dett.jsp?id_gamma=39&id_prodot- to=350&id_mercato=4 Rittal Liquid Cooling Package...
Only for Service/ cation or internal debug) Manufacturer Main Setpoint LCP °C -99.9 99.9 Customer 49…207 Reserved – (not used or other special appli- – – – – Only for Service/ cation or internal debug) Manufacturer Rittal Liquid Cooling Package...
Page 35
Customer Fans Speed (percent) Customer Fans Speed (rpm) 3700 Customer EVD Valve opening percent Customer 31…207 Reserved – (not used or other special appli- – – – – Only for Service/ cation or internal debug) Manufacturer Rittal Liquid Cooling Package...
Page 36
Reserved – (not used or other special appli- – Only for Service/ cation or internal debug) Manufacturer Memory alarm probe broken (analogic input – Customer B2): LCP Server IN Memory alarm probe broken (analogic input – Customer B3): LCP Server IN Rittal Liquid Cooling Package...
Page 37
Reserved – (not used or other special appli- – Only for Service/ cation or internal debug) Manufacturer System reboot – Customer 101…207 Reserved – (not used or other special appli- – Only for Service/ cation or internal debug) Manufacturer Rittal Liquid Cooling Package...
Note: For technical queries, or if servicing is re- General quired, please contact Rittal using the ad- If there is a malfunction or alarm on the device, a corre- dresses shown in section 18 "Customer sponding error message will be displayed. The corre- service addresses".
High pressure ing of fan. ALB02 Alarms ALB02 High ambient temperature, incor- Check device limits, check coolant High pressure compressor 1 by rect coolant filling, defective fan. volume and check correct function- transducer ing of fan. Rittal Liquid Cooling Package...
Page 40
High ambient temperature, incor- Check device limits, check coolant High condensing temperature rect coolant filling, defective fan volume, check fan on condenser. (HiTcond) on condenser. ALD09 Alarms ALD09 Cf. inverter manual. Cf. inverter manual. Driver offline Rittal Liquid Cooling Package...
Page 41
After the reset, the alarm is stored in the alarm data log as ALL01. ALW04 ALW04 A previous alarm has stopped the Reset the previous alarm. Max temperature (warning) unit; heat load too high compared to the cooling capacity of the unit. Rittal Liquid Cooling Package...
Rotate the fan module in the rack in a clockwise direc- tion by 90° (fig. 39). Grasp the fan module with both hands on the left and right, and pull it out of the rack. Rittal Liquid Cooling Package...
Page 43
9 Inspection and maintenance Fig. 39: Rotated fan module in fan tray Note: The LCP DX may only be operated with all four fans running. Rittal Liquid Cooling Package...
The LCP DX must not be subjected to temperatures above +50 °C during stor- age. During storage, the LCP DX must stand upright. Disposal can be performed at the Rittal plant. Please contact us for advice. Caution! Risk of environmental contami- nation!
See tab. 23 "Refrigerant pipes" (1mm wall thickness) Other information Storage temperatures [°C] -20…+55 Ambient temperature [°C] -20…+45 Noise level [dB(A)] (Open air above reflective flooring, distance 10 m) Tab. 18: Technical specifications for the high temperature condenser unit Rittal Liquid Cooling Package...
See tab. 23 "Refrigerant pipes" (1mm wall thickness) Other information Storage temperatures [°C] -20…+55 Ambient temperature [°C] -20…+53 Noise level [dB(A)] (Open air above reflective flooring, distance 10 m) Tab. 21: Technical specifications for the high temperature condenser unit Rittal Liquid Cooling Package...
20 m to 45 m 16/16 Up to 20 m 12/16 Low temperature 22/22 20 m to 45 m 16/16 Up to 20 m 12/16 High temperature 28/28 20 m to 45 m 16/16 Tab. 23: Refrigerant pipes Rittal Liquid Cooling Package...
Air baffle plate for TS, for enclosure width 600 mm 7151.206 Air baffle plate for TS, for enclosure width 800 mm 7151.208 Add-on cover 3301.221 Server enclosure compensating panel for LCP 7067.200 Inline Tab. 25: Accessories list – LCP DX Rittal Liquid Cooling Package...
Fig. 41: Logging on to the 2nd menu level (Main Setup) Example of a static IP address: Once again, enter rittal as the user and 1234 as the http://172.16.0.1 password. A dialogue will appear for logging onto the LCP DX.
40 W To activate the humidification function, proceed as fol- lows: Water supply temperature 1…40 °C Assign the "YES" value to the "Enable B5 humidity" range entry in the "Hc39" menu. Tab. 27: Humidifier technical specifications Rittal Liquid Cooling Package...
Alternatively, connect the optional condensate pump condensate pump to malfunction. (see section 15.5 "Condensate pump"). – Rittal recommends that the device is oper- ated with demineralised water as the ser- 15.3 Electrical heaters vice life of the humidifier may otherwise be adversely affected, depending on the qual- 15.3.1...
"Electrical heaters" option must also be installed (see section 15.3 "Electrical heaters"). 15.4.2 Activating the dehumidification To activate the heaters, proceed as follows: Assign the "YES" value to the "Enable" entry in the "Ha30" menu. Rittal Liquid Cooling Package...
15.5.3 Installation 15.4.3 Installation prerequisites Connect the pump pipe connection (diameter ⅛"M") Any condensate that occurs is then fed to the conden- with an external pipe to discharge the water of the tray. sation tray. Rittal Liquid Cooling Package...
(to maximum +53 °C), the optional high temperature condenser that replaces the 3311.363 standard unit must be deployed. For the above-mentioned maximum temperature, the maximum cooling capacity with the optional condenser is 7.55 kW. Rittal Liquid Cooling Package...
LCP DXs using a twin-core cable. perature is to the set-point + band. Note that the maximum cable length from the first LCP DX to the last LCP DX must not exceed 100 m. Rittal Liquid Cooling Package...
15 Options Fig. 57: "Debug" menu 15.9.4 Installation prerequisites No additional software is required for redundancy oper- ation. For previously installed devices, it must be guar- anteed that the correct version of the software is pres- ent. Rittal Liquid Cooling Package...
Ambient tempera- credited cooling system specialists. ture [°C] Server air outlet To avoid damage to the device, Rittal prescribes the use temperature [°C] of coolant R410A. R410A is virtually azeotropic and is comprised of equal Server air inlet tem- parts of R32 and R125.
16 Further technical information 16.3 Overview drawing Fig. 58: Overview drawing of the LCP DX (depth 1200 mm) Rittal Liquid Cooling Package...
Page 62
16 Further technical information Vertical installation "V" version 417.7 2282 282.5 Ø10 Ø10 2100 Horizontal installation "H" version 2282 Ø10 Ø10 2100 Fig. 59: Installation diagram of the standard condenser Rittal Liquid Cooling Package...
Page 63
16 Further technical information Vertical installation "V" version 2206 2000 Horizontal installation "H" version 2225 Ø13 2000 Fig. 60: Installation diagram of the high temperature condenser Rittal Liquid Cooling Package...
Page 64
16 Further technical information Vertical installation "V" version 417.7 2282 282.5 Ø10 Ø10 2100 Horizontal installation "H" version 2282 Ø10 Ø10 2100 Fig. 61: Installation diagram of the low temperature condenser Rittal Liquid Cooling Package...
Page 65
16 Further technical information Fig. 62: Refrigerant scheme low temperature unit Rittal Liquid Cooling Package...
Page 66
16 Further technical information Fig. 63: Installation scheme winter kit module (low temperature unit) Rittal Liquid Cooling Package...
16 Further technical information 16.5 Piping and instrumentation diagram to DIN EN 1861:1998 Fig. 65: Piping and instrumentation diagram to DIN EN 1861:1998 Rittal Liquid Cooling Package...
Page 69
16 Further technical information Fig. 66: Parts list, piping and instrumentation diagram Rittal Liquid Cooling Package...
For a hysteresis of x%, the warning or alarm for undershooting an upper limit value or overshooting a lower limit value clears only for a difference of x/100*limit value to the limit val- Rittal Liquid Cooling Package...
Customer service addresses For technical questions, please contact: Tel.: +49(0)2772 505-9052 E-mail: info@rittal.de Homepage: www.rittal.com For complaints or service requests, please contact: Tel.: +49(0)2772 505-1855 E-mail: service@rittal.de Rittal GmbH & Co. KG Auf dem Stützelberg 35745 Herborn Germany Rittal Liquid Cooling Package...