Honeywell NOTIFIER ISO-X Quick Start Manual page 2

Fault isolator module

Advertisement

• Surface-mount box is available as an option.
Specifications
Operating voltage: 15 – 32 VDC (peak).
Current range: 5 mA for LED latched in alarm.
Standby current: 400 μA maximum, plus supervision cur-
rent.
Pulsing current: 30 mA for 15 mS (CMX-1, CMX-2, FCM-1).
Temperature range: 32°F to 120°F (0°C to 49°C).
Relative humidity: 10% to 93%.
Weight: (5 oz.) 150 grams.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
• UL: S635 (UOXX); BP6480 (AMCX, APOU)
• ULC: S635 (OUOXXC, ISO-XA)
• FM Approved
• CSFM: 7165-0028:141; 7165-0028:164; 7165-0028:181;
7165-0028:214;
7165-0028:224;
7170-0028:182;
7165-0028:195;
7170-0028:223; 7165-0028:243; 7170-0028:244
• MEA: 17-96-E; 104-93-E Vol. VI; 290-91-E Vol. V; 317-01-
E; 447-99-E
• Lloyd's Register: 94/60004 (E2); 93/60140 (E2)
Examples of Device Counts
(see notes under Applications )
Page 2 of 2 — dn-2243:A1 • 12/3/09
7170-0028:153;
7170-0028:216;
Example 2
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
• BSA: 578-81-SA
• US Coast Guard: 161.002/23/2(AFP-200); 161.002/27/3
(AFP-1010, AM-2020); 161.002/42/1(NFS-640)
Architectual/Engineering
Specifications
Fault Isolator Modules shall be provided to automatically iso-
late wire-to-wire short circuits on an SLC loop. The Fault Isola-
tor Module shall limit the number of modules or detectors that
may be rendered inoperative by a short circuit fault on the SLC
Loop. If a wire-to-wire short occurs, the Fault Isolator Module
shall automatically open-circuit (disconnect) the SLC loop.
When the short circuit condition is corrected, the Fault Isolator
Module shall automatically reconnect the isolated section of
the SLC loop. The Fault Isolator Module shall not require any
address-setting, and its operations shall be totally automatic. It
shall not be necessary to replace or reset an Fault Isolator
Module after its normal operation. The Fault Isolator Module
shall mount in a standard 4.0" (10.16 cm) deep electrical box,
in a surface-mounted backbox, or in the Fire Alarm Control
Panel. It shall provide a single LED which shall flash to indi-
cate that the Isolator is operational and shall illuminate steadily
to indicate that a short circuit condition has been detected and
isolated.
Product Line Information
ISO-X: Isolator Module.
ISO-XA: Isolator Module. Canadian (ULC) version.
SMB500: Surface Mount Backbox
Example 1
Example 3
NOTIFIER® is a registered trademark of Honeywell International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
www.notifier.com
Made in the U.S. A.