Forced Air Zone Controls
The patented UT3000 Zone Control System has been enhanced to provide
intelligent zone control of the Daikin FIT™ and ComfortNet™ communicating
HVAC systems or 24volt legacy HVAC systems. Create 2 or 3 air zones with a
single panel or "twin" two UT3000's together to create a 4 or 5 zone system. Use
EWC® 24volt motorized dampers and any off-the-shelf 24volt thermostat or
compatible communicating thermostats. Features like Automatic Equipment
Recognition, Modulating and Staged BTU capacity control, Dual Fuel
functions, Energy Saving features and Precise Control of Supply Air Target &
Limit set-points still come standard. Even the LCD display has been enhanced
to include easy to read "System Status" messages. EWC® Controls raises the
bar again and sets another new standard for Residential HVAC Air Zoning.
Zone
Control 2 or 3 air zones with genuine EWC
Capacity
24vac Power Open/Close dampers. Control 4
- 5 zones by twinning 2 UT3000s together.
Control Communicating HVAC systems
Compatible
HVAC
based on the ClimateTalk™ communicating
Systems
open protocol. Or any 24volt legacy 2 Heat /
1 Cool Gas w/AC system or 2 Heat / 1 Cool
conventional or dual fuel Heat Pump.
The UT3000 is compatible with Daikin and
Compatible
Amana communicating (One+ & Touch)
Thermostats
thermostats. The UT3000 is also compatible
with non-communicating 24v single stage
Heat/Cool thermostats and two Heat/1Cool
Heat Pump thermostats.
Automatic
The UT3000 is compatible with "automatic
changeover" thermostat settings, which
Heat / Cool
allows for individual zone comfort from the
Changeover
HVAC system.
The Liquid Crystal Display scrolls to show
Status LCD
each zone thermostat demand input and the
HVAC system demand output. The outside &
System COOL 25%
supply air temperatures are also displayed. In
addition, all UT3000 programming is
performed at the LCD.
4 Button LCD
Four buttons are provided just below the
Programming
LCD screen. The buttons are used to scroll
thru the Menu on the LCD and make your
Select Up
selections. Program the UT3000 and select
Back
the features you like. Non-volatile memory
Forward
maintains your settings even after a
prolonged power failure.
Select Down
In addition to the LCD, a total of 5 colored
System LED's
LED's provide visual indication of the
HVAC system status & mode of operation.
A total of 3 green LED's labeled Zone 1 thru
Damper LED's
Zone 3, are also provided to indicate which
dampers are energized to Open.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
P/N 090375A0260 REV. R Copyright © September 19, 2023
D
C
A
M
PC
P
E
PO
R
C
2
1
R
ZONE
3
C
W/E
O/B
Y
R
G
T'FORMER
R
C
IAQ RELAY
NC
NO
C
SYSTEM
W2/E
W1/B
O
Y
G
RH
S
RC
Y
S
C
T
E
M
C
W
2
Y
1
G
R
R
Figure 1. UT3000 panel
Communicating
WiFi compatible.
Fault Free
Programming
Intuitive
Temperature
Control
Ancillary IAQ
Dry Relay
Provided
EWC Controls Inc. ALL Rights Reserved
Communicating Zone Control System
LEAVE THIS BULLETIN ON THE JOB SITE FOR FUTURE REFERENCE
Ultra Talk
K2
F3
F12
D5
D22
R51
R48
R82
R50
U9
Z3RXD
R47
C18
R49
LED19
D21
F11
F13
R107
R99
C40
F22
R105
R106
R100
CONTRAST
R35
R108
C39
R36
R33
R104
R34
R89
C38
C10
R102
L1
U2
D3
R103
R101
+
C37 R90
C4
U19
D2
D1
FB1
24vac
C2
C1
C3
+
+
+
F1
D27
C12
D8
C21
C22
K5
R9
Y1
D9
R117
U.S. Patent
C14
K6
R8 R7 R6
R10
# 9,253,260
U3
U4
D10
ZONE 3 OPEN
LED10
ZONE 2 OPEN
CONTROL
LED11
R11
K7
ZONE 1 OPEN
LED12
D11
LED13
IAQ RELAY
W2 / EMERGENCY
LED14
R12
HEAT / B
LED15
K8
D12
LED16
COMPRESSOR
FAN
LED17
JMP1
RC/RH
R13
K9
R38
R41
LINK
D18
F7
R40
D28
R37
D17
R79
C8
F6
+ U17
ON
D19
1
BIASING
2
TERMINATION
3
FB2
+
+
C9
C32
R39
LED22
U12
F8
D20
C42
L2
A total of 4 green Pulsing LED's are provided to
indicate a Comm Link has been established with each
LED's
Communicating Thermostat network and the HVAC
Communicating System network. A series of Rapid &
Random Pulses indicate a successful comm-link and
data transmission. Otherwise, each Comm LED will
blink at a slow rate for non-communicating devices.
The UT3000 comes pre-loaded with Default Operating
Parameters (See Page 2, Table 1) for Zoned HVAC
Systems. The Default Programing means less work for
&
the Installer, but also allows Fine Tuning of the System
to Optimize Performance and Personal Preference. The
UT3000 operates in Staged and Modulating mode at all
times. Multi-Stage and Modulating Equipment will be
operated in a manner that maximizes efficiency,
maximizes temperature control & improves system
performance.
The UT3000 includes a SPDT Indoor Air Quality Dry
Relay (IAQ Relay), with a digital & 24v Input
Trigger. It can be used to interlock and control
* Fresh Air Damper * Whole House Humidifier
The UT3000 must detect a Fan, Heat or Cool demand
from one or more communicating zone thermostats or
legacy non-communicating zone thermostats, before
the IAQ relay will energize. See page 8.
E-Mail- info@ewccontrols.com
www.ewccontrols.com
3000
U.S. Patent No. 9,253,260
C
PC
PO
1.82
V
K3
F4
F14
D23
R54
R52
C20
C
U10
2
1
R55
R81
R22
Z2RXD
R
R53
LED20
D24
R56
®
F15
R95
ZONE
F16
R97
F21
C36
R98
R96
E W C
C
C35
R87
R92
W/E
R93
O/B
R94
Y
C34
R88
R86
R
C33
R91
G
R85
+
C5
C
PC
PO
U18
J1
F5
C23
F17
R27
D25
C19
R57
C
C13
U6
U11
2
R28
R60
1
R80
Z1RXD
R61
LED21
R
R58
D26
R65
U7
R72
F18
C27
ZONE
F19
R73
R62
1
C24
F20
R63
®
R64
C
SYSTEM
R66
W/E
R67
O/B
C25
R112
R68
Y
R69
R113
C26
R43
R115
R
R70
U14
R71
R118
G
C41
C28
R110
R74
R114
R75
Relay
U15
R45
C29
R119
R76
ONE
R111
C43
R77
ZONE
R116
U16
C31
R83
R109
R84
R46
R23
D13
OAS
C30
R24
D14
C15
R25
D15
ClimateTalk
®
D16
SAS
R26
C16
SYSTEM RECEIVE DATA
Ancillary IAQ functions:
* Energy Recovery Ventilator
TB-260
D
A
M
P
E
R
2
D
A
M
P
E
R

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ULTRA-TALK 3000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for EWC Controls ULTRA-TALK 3000

  • Page 1 Open. the IAQ relay will energize. See page 8. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com P/N 090375A0260 REV. R Copyright © September 19, 2023 EWC Controls Inc.
  • Page 2: Installation Instructions

    INSTALLATION INSTRUCTIONS Installation must be performed by qualified/licensed personnel only! MOUNTING: Choose a suitable location to mount the UT3000 housing. Suitable Typical Up-flow locations are on the Return Duct, a Nearby Wall or Convenient Studs where Installation with plywood can be installed to support the housing. Do Not mount the UT3000 on the DX Cooling Supply duct.
  • Page 3 UTC) screen, depending on the mode of operation. Conflicting Zone Demands due to mis-wiring or incorrect programming will not be recognized! System TOO HOT System TOO COLD Supply OTC* 152° Supply UTC* 38° EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 4 49°F, 50°F or 51°F, and the Cool Target has been External Load, SAS Response Delay Setting, Supply Air Target set-point, set to 50°F. Continued on the next column. Thermostat type and the Thermostat demand value. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 5 10 seconds and the LCD screen will resume scrolling. equal 100%, but going above 100% is not permitted. The programming is complete and the UT3000 will store all settings into permanent memory. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 6 The purge cycle is fixed at 210 Zone 1 = 24v HP seconds. Zone 2 = 24v HP Refer to Page 11 for Sample Thermostat Diagrams Zone 3 = 24v HP EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 7: System Fan

    Note: On HP applications, if the UT3000 cannot detect thermostats are occurring. any outside air temperature at all, it will default to emergency heat or W2 heat for all heating demands. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 8 210 seconds. Timer Most basic “Flow Thru” humidifiers require a separate 10va or 12va transformer to operate the water solenoid valve or the media motor. EWC Controls highly recommends that you utilize it! Short Cycle When all Zones are satisfied, the...
  • Page 9 UT3000 Features Zone 4 Button Scrolling Zone Damper Programming at a Glance LCD Screen Damper Communicating Z1 h030c000f025 Communicating T-stat T-stat Communicating Zone #2 Communicating Z2RXD Z3RXD LED19 LED20 Zone #3 ZONE ® ZONE R107 Indicator R105 Indicator R106 E W C R100 Regular CONTRAST...
  • Page 10 See the Addendum sheet #090376A0180 rev V, for wiring and guidance on “twinning” (4 and 5 zone) systems. wire are not required at the communicating outdoor unit EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 11: Wiring Instructions

    NOTE: High fire (W2) on a 2 stage communicating furnace occurs at 51% system demand, similar to Y2 HP Heating or Cooling. The W2 Threshold setting has no affect on a 2 stage or modulating furnace. The W2 Threshold setting only affects Auxiliary/Backup on heat pump systems. EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-635-8646 E-Mail- info@ewccontrols.com...
  • Page 13 Plug & Play electrical interference. Using two wires for each data circuit rather than one, will stabilize the system network. Figure 3c EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-635-8646 E-Mail- info@ewccontrols.com...
  • Page 14 Note: You must specify the tonnage of the non-communicating outdoor unit, inside the Furnace equipment User Menu, in order to achieve the correct airflow! Figure 3e EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-635-8646 E-Mail- info@ewccontrols.com...
  • Page 15 35second travel time, and have LED position indicators. No other residential zone damper is stronger, more efficient or as reliable. Figure 5c Figure 5a EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 16 H/C: W1 (Heat) / Y1 (Cool) 100% HC: Y2 & W2 HP: W2 Threshold Threshold HP= HEAT PUMP SYSTEM HC= HEAT/COOL SYSTEM Adjustable (Fixed) 65% - 99% EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 17 H/C: W1 (Heat) / Y1 (Cool) 100% HC: Y2 & W2 HP: W2 Threshold Threshold HP= HEAT PUMP SYSTEM HC= HEAT/COOL SYSTEM Adjustable (Fixed) 65% - 99% EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 18: Troubleshooting

    ® www.ewccontrols.com When calling for Technical Support from the job-site, please have a good quality multi-meter, pocket screwdriver, and wire cutters/strippers on hand. Copyright © 03/14/2023 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 19 3000 Communicating Zone Control System U.S. Patent No. 9,253,260 JOB NOTES: Register your warranty today at https://ewccontrols.com/warranty/ EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...
  • Page 20 (Tech Bulletin - French) https://ewccontrols.com/acrobat/090376a0194.pdf (Quick Start - English) https://ewccontrols.com/acrobat/090376a0196.pdf (Quick Start - Spanish) https://ewccontrols.com/acrobat/090376a0199.pdf (Quick Start - French) https://ewccontrols.com/acrobat/090376a0180.pdf (Addendum - English) https://ewccontrols.com/acrobat/090376a0188.pdf (Addendum - Spanish) EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com...