Inspect Your Shipment; Installation; Electrical Wiring - Pearl BEST-BOOST Installation And Operating Instructions Manual

Device for control and protection of the electric pump
Table of Contents

Advertisement

Available languages

Available languages

INSPECT YOUR SHIPMENT

All pump controller devices are carefully tested, inspected,
and packaged to ensure they arrive in perfect condition. When
the device is received, examine it closely to make certain no
damage occurred during shipping. If damage is evident, report
it to your shipping carrier and product dealer immediately. The
shipping carrier assumes full responsibility for the shipment's
safe arrival. Any claim for damage to the shipment, either visible
or concealed, must be made through the shipping carrier.
Package Includes:
• Pump controller device
• Installation manual

INSTALLATION

Location of the Pump Controller Device
Decide on a suitable location for the device installation, based
on the enclosure rating of the device.
WARNING: Liquid-tight cables or conduit and fittings
must be used to maintain Type 4 rating.
WARNING: This equipment must not be used by
children or persons with reduced physical, sensory, or mental
abilities, or people lacking in experience and expertise, unless
supervised or instructed. Children may not use the equipment,
nor may they play with the unit or in the immediate vicinity of
the unit. Choose a clean, well-ventilated location that provides
protection from freezing, flooding, and excessive heat. In
addition, the location should provide access for servicing and
allow convenient draining of the pump, tank, and service pipes.
The device must be mounted in a vertical position (See Figure
1).
Notice: Read and Follow all Instructions.
WARNING: Hazardous voltage can shock, burn, or cause
death.
CAUTION: Improper wiring can result in permanent
damage to the system. Pump connections must comply with
National Electric Code (NEC) or Canadian Electric Code (CEC),
and all applicable local codes.
CAUTION: If you are not sure of the proper electrical
connections, employ a competent electrician for the installation.
This ensures the installation complies with all noted electrical
codes.
Disconnect power at the electrical panel before making any
electrical connections. Supply voltage must be +/- 10% of
device nameplate voltage.
Low or high voltage can damage the device and will void the
warranty. Connect the device to a dedicated branch circuit with
no other appliances on it.
Do not operate the device unless it is grounded.
A fused disconnect switch or circuit breaker should be placed
at, or near, the pump, as required by local electrical codes.
NOTICE: Before installing the device, carefully check the
technical features and make sure they comply with those of the
pump and the system.

ELECTRICAL WIRING

WARNING: Serious or fatal electric shock may result from
failure to connect the pump and control to the service entrance
ground. Also, ground metal plumbing and all other metal near
the device. When grounding these components, use a wire no
smaller than the power supply wires from the circuit breaker
to the device. To reduce the risk of electric shock, disconnect
power before working on or around the water system.
INSTALLATION PROCEDURE WIRING
1. Disconnect electrical power at the main breaker.
2. Verify that the dedicated branch circuit for the device is
equipped with a proper Listed fuse/Listed circuit breaker.
3. Remove the cover of the device by removing the four screws,
as shown in Figure 5.
WARNING: The electrical wiring must be carried out
by qualified personnel in compliance with local regulations.
Observe all safety standards and make sure the device is
properly grounded.
Follow all the indications on the electrical diagrams (See Figures
8, 9, and 10).
COVER
SCREWS

Advertisement

Table of Contents
loading

Table of Contents