Commissioning

Programming the physical address and application program
Switch on the bus voltage.
Press the programming button (2).
The programming LED (3) lights up.
Program the physical address with the ETS.
The programming LED goes out.
Program the application program with the ETS.
6.1

Safe-state mode and master reset

Safe-state mode
The safe-state mode stops the execution of the loaded application program.
Only the system software of the device is still functional. ETS diagnosis func-
tions and programming of the device are possible.
Activating safe-state mode
Switch off the bus voltage or remove the KNX device connection terminal.
Wait approx. 10 seconds.
Press and hold down the programming button.
Switch on the bus voltage or attach the KNX device connection terminal.
Wait until the programming LED flashes slowly.
Release the programming button.
The safe-state mode is activated.
By briefly pressing the programming button again, the programming mode can
also be switched on and off in the safe-state mode as usual. If the program-
ming mode is active, the programming LED stops flashing.
Deactivating safe-state mode
Switch off bus voltage (wait approx. 10 seconds) or carry out ETS program-
ming.
Master reset
The master reset restores the basic device settings (physical address 15.15.255,
firmware remains in place). The device must then be recommissioned with the ETS.
In secure operation: A master reset deactivates device security. The device can then
be recommissioned with the device certificate.