1.0 SAFETY INFORMATION

The provision of the electrical supply and the connection of the unit to the
mains must be carried out by a qualified electrician.
Isolate from power supply before removing any covers. During installation /
Maintenance ensure all covers are fitted before switching on the mains supply.
All-pole disconnection from the mains as shown in the wiring diagram must
be incorporated within the fixed wiring and shall have a minimum contact
separation of 3mm in accordance with latest edition of the wiring regulations.
This unit must be earthed.
Ducting must be securely fixed with screws to the spigot to prevent access to
live parts. Duct runs terminating close to the fan must be adequately protected
by suitable guards.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
Precautions must be taken to avoid the back-flow of gases into the room from
the open flue of gas or other fuel-burning appliances.
This appliance should not be used by children or persons with reduced
physical, sensory or mental capabilities or lack of experience and knowledge,
unless they have been given supervision or instruction concerning the safe
use of the appliance by a person responsible for their safety. Children shall not
play with the appliance. Cleaning and user maintenance shall not be carried
out by children.

2.0 INTRODUCTION

The MEV-X is designed to provide continuous mechanical extract
ventilation to dwellings in accordance with Part F of the building
regulations, the unit is listed on the Product Characteristics
Database (PSDB).
The unit may be used for supply or extract, however, the different
applications will require variations to the completed installation
e.g. filtration, insulation. Contact Nuaire to discuss the full system
design requirements.
nuaire.co.uk
029 2085 8400
MEV-X
Continuous Extract Unit
Installation and Maintenance
IMPORTANT
This appliance should not be used by children or persons
with reduced physical, sensory or mental capabilities or
lack of experience and knowledge, unless they have been
given supervision or instruction concerning the safe use
of the appliance by a person responsible for their safety.
Children shall not play with the appliance. Cleaning and user
maintenance shall not be carried out by children.
26. 02. 24. Document Number 671924
The EMC
Directive
2014/30/EU
The Low Voltage
Directive
2014/35/EU
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MEV-X and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for NuAire MEV-X

  • Page 1 2.0 INTRODUCTION IMPORTANT The MEV-X is designed to provide continuous mechanical extract This appliance should not be used by children or persons ventilation to dwellings in accordance with Part F of the building with reduced physical, sensory or mental capabilities or...
  • Page 2 These should be integrated into the system The provision of the electrical supply and the connection of the design where appropriate and can be purchased from Nuaire unit to the mains must be carried out by a qualified electrician.
  • Page 3 MEV-X Installation Manual Mounting Hole Dimensions 5.0 ELECTRICAL CONNECTION PCB Detail IMPORTANT For good EMC practice, any sensor cable or switched live cables should not be placed within 50mm of, or on, the same metal cable tray as other cables.
  • Page 4 MEV-X Installation Manual Single Speed Wiring Prewired Connections Green / Yellow MAINS Blue 230 V 50 Hz Brown 2 Pole Fuse 2 A ON / OFF Isolator Switch Single Speed Wiring with Mains Activated Back-draught Damper Prewired Connections Green / Yellow...
  • Page 5 International Sales office for further details. A calibrated moving vane anemometer and hood will be required Only genuine Nuaire parts and filters may be used to maintain to carry out commissioning. the unit. Adjustment valves should be locked in place to prevent further 10.0 AFTER SALES...
  • Page 6 MEV-X Installation Manual NOTES nuaire.co.uk 029 2085 8400 26. 02. 24. Document Number 671924...

Table of Contents