VD4/R - VD4/L - VD4/R-SEC - VD4/L-SEC - INSTALLATION AND OPERATING INSTRUCTIONS
20
5. Product description
5.6 Characteristics of the electrical accessories
Shunt opening release (-M01); Additional shunt
opening release (-M02); Shunt closing release (-MC)
Un
Un
Operating limits
Power on inrush (Ps)
Inrush time
Holding power (Pc)
Opening time
Closing time
Insulation voltage
Undervoltage release (-MU)
Un
Un
Operating limits:
– circuit breaker opening
– circuit breaker closing
Power on inrush (Ps)
Inrush time
Holding power (Pc)
Opening time
Insulation voltage
Electronic time delay device for undervoltage
release (installed outside the circuit breaker)
Un
Un
Adjustable opening time
(release + time-lag device)
Summary of the total quantity of auxiliary contacts available(*)
Total quantity
VD4/R p230
VD4/R p300
VD4/L p230
VD4/L p300
VD4/R-SEC
VD4/L-SEC
(*) Each opening release required uses an auxiliary contact to shut off its power supply after having opened the circuit breaker. Thus the number of auxiliary
contacts really available diminishes in the same way as the number of opening releases installed.
LV: 24...30 Vdc; 48...60 Vdc/ac 50-60 Hz
HV: 110...132 - 220...250 Vdc/ac 50-60 Hz
65...120% Un
70 W
150 ms
1.5 W
40...60 ms
30...60 ms
2000 V 50 Hz (for 1 min)
LV: 24...30 Vdc; 48...60 Vdc/ac 50-60 Hz
HV: 110...132 - 220...250 Vdc/ac 50-60 Hz
35-70% Un
85-110% Un
150 W
150 ms
3 W
60...80 ms
2000 V 50 Hz (for 1 min)
24...30 - 48 - 60 - 110...127 - 220...250 V–
48 - 60 - 110...127 - 220...240 V~ 50/60 Hz
0.5 - 1 - 1.5 - 2 - 3 s
5 auxiliary contacts
10 auxiliary contacts
(-BB1)
(-BB1, -BB2)
Standard equipment
Alternative available on
request. This is the obligatory
minimum quantity if -MO2
(the additional opening
release) is also required
Standard equipment
Alternative available on
request but with 8 auxiliary
contacts
Auxiliary contacts of the circuit breaker
Un
24 ... 250 V ac/dc
Rated current
Ith2 = 10 A
Insulation voltage
2000 V 50 Hz (for 1 min)
Electrical resistance
3 mOhm
Rated current and breaking capacity in class
AC11 and DC11
Un
Cosϕ
T
220 V~
0.7
24 V–
15 ms
60 V–
15 ms
110 V–
15 ms
220 V–
15 ms
Motor operator (-MS)
Specifications
Un
24...30 - 48...60 - 110...130 - 220...250 V–
Un
100...130 - 220...250 V ~ 50/60 Hz
Operating limits
85...110 % Un
Power on inrush (Ps)
DC=600 W; AC=600 VA
Rated power (Pn)
DC=200 W; AC=200 VA
Inrush time
0.2 s
Loading time
6-7 s
Insulation voltage
2000 V 50 Hz (for 1 min)
10 auxiliary contacts
(-BB1, -BB2)
Alternative not available
Alternative not available
In
Icu
2.5 A
25 A
10 A
12 A
6 A
8 A
4 A
5 A
1 A
2 A
10 auxiliary contacts
(-BB1, -BB2)
Alternative available
on request
As above