ABB VD4 Installation And Operating Instructions Manual page 13

Table of Contents

Advertisement

M E D I U M V O LTA G E P R O D U C T S
5.3.4
General specifications of fixed circuit breakers with lh lateral operating mechanisms for ABB UniSec switchgear (12-17.5-24 kV)
Circuit breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated thermal current (40 °C)
Rated duty breaking capacity
(symmetrical rated short-circuit current)
Short-time withstand current (3 s)
Making capacity
Sequence of operations
Opening time
Arcing time
Total break-time
Closing time
Overall dimensions
(maximum)
H
D
W
Weight (
4
)
Application of REF 601 protection device (
Standardized dimensions table
Wiring diagram
Operating temperature
Tropicalization
Electromagnetic compatibility
(
) for 12.08.20 and 17.08.20, versions with withstand voltage up to 42 kV are available
1
(
2
) rated duty breaking capacity 21 kA at 17.5 kV. Rated short-time withstand current 21 kA x 3 s
(
) rated short-time withstand current 25 kA x 2 s
3
(
) increase the indicated weight by 20 kg for circuit breakers with REF 601 devices and 3 current sensors
4
(
5
) "IEC" or "CEI 0-16" version. If the "CEI 0-16" is required, the circuit breaker is always supplied with 3 phase current sensors (Rogowsky coils) installed on the actual circuit breaker and with a
loose toroidal TA. In the "CEI 0-16" version, the REF 601 device opens the circuit breaker by means of the undervoltage release -MU
(
) the rated current of the REF 601 device must be set in the relay in accordance with the circuit breaker's rated current
6
(
7
) for 12.08.20 and 17.08.20, versions with operating temperature up to -25 °C and storage temperature up to -40 °C are available
IEC 62271-100
CEI EN 62271-100
Ud (1 min) [kV]
Up [kV]
Isc [kA]
[ O - 0.3s - CO - 15s - CO ]
H [mm]
W [mm]
D [mm]
Pole center-distance P [mm]
)
5
without / with REF 601
IEC: 60068-2-30, 60721-2-1
IEC 62271-1
VD4/L-SEC 12
Ur [kV]
12
Us [kV]
12
281 (
)
1
75
fr [Hz]
50-60
Ir [A]
630
800
1250
12.5
12.5
12.5
16
16
16
20
20
20
25
25
25
Ik [kA]
12.5
12.5
12.5
16
16
16
20
20
20
25 (
)
25 (
)
25
3
3
Ip [kA]
31.5
31.5
31.5
40
40
40
50
50
50
63
63
63
[ms]
40...60
[ms]
10...15
[ms]
50... 75
[ms]
30...60
740
315
1005
230
[kg]
65
• (
)
6
1VCD000132
1VCD400118
[°C]
-5 ... +40 (
)
7
VD4/L-SEC 17
17.5
17.5
38 (
)
1
95
50-60
630
800
1250
630
12.5
12.5
12.5
12.5
16
16
16
16
20 (
2
)
20 (
2
)
20
20
25
25
12.5
12.5
12.5
12.5
16
16
16
16
20 (
2
)
20 (
2
)
20
20
25 (
)
25 (
)
3
3
31.5
31.5
31.5
31.5
40
40
40
40
50
50
50
50
63
63
40...60
10...15
50... 75
30...60
740
315
1005
230
65
• (
)
6
1VCD000132
1VCD400118
-5 ... +40 (
)
7
13
VD4/L-SEC 24
24
24
50
125
50-60
800
1250
40...60
10...15
50... 75
30...60
740
315
1005
230
65
• (
)
6
1VCD000132
1VCD400118
-5 ... +40 (
)
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

R-vd4L-vd4R-sec-vd4L-sec

Table of Contents