3. SPECIFICATIONS
(6) Faulty station detection (addresses 100 to 103)
(a) Sets 1 to the bit corresponding to the faulty remote I/O station.
1 indicates that normal communication could not be made
after retry processing had been performed the specified
number of times (address 1).
(b) In automatic return mode, the corresponding bit is reset to 0
when the faulty station is restored.
In no automatic return mode, the corresponding bit remains 1.
(c) Any faulty station is detected when Y18 is on. Data is held
when Y18 is off.
(d) Data is made up as indicated below:
1: Error
0: Normal
..
ee
ea
"
""
",
'"
'"
t
Station 16 Station 15 Station 14 Station 13 Station 12
Station 11 Staion
10 Station 9 Slalion8 Station 7 Station 6 Station 5 Station 4 Station 3
Station 2 Station 1
Station 32 Stahlln 31
Station 30
Station 29 Station 28 StatiOll 27 Station 26
Station 25 Slalion 24
Station 23
Station 22 Station 21 Station 20
Station 19 Station 18
Station 17
Station 48 Station 47 Station 46 Station 45 Station 44 Station 43 Station 42 Station 41 Station 40 Station 39 Station 38
Station 37
Station 36 Station 35
Station 34
Statlon 33
Station
64 Station 63 Station 62 StatiOfl 61 Station 60
Station 59 Station
58 Station 57 Station 56 StatiOll 55 Station 54 Station 53 Station 52 Station 51 Station 50
Station 49
100
101
102
103
Address
b15
(7) Communication error code (address 107)
(a) Stores the corresponding error code when X7 is switched on.
(b) Communication error codes are as follows:
I
Code
Definition
Cause
0
No error
1
Initial data error
The number of remote
110
stations or retries is
invalid.
2
Line error
A link cable is broken or a remote I/O station
power is off.
Communication has stopped due to a station
3
Station fault
fault with communication stop mode specified
for fault detection.
(c) The communication error code is reset to 0 when Y18 or Y1Dis
switched on.
(8) Error detection code (address 108)
(a) 1 indicates that X6 has been switched on. 0 indicates normal.
(b) In automatic return mode (mode setting switch
=
0), the error
detection code remains 1 but X6 is switched off when
communication is restored.
(c) Reset to 0 when Y18 or Y1D is switched on.
3-12 - - - - - - - - - - - - - - - - -