Table 5.A
Scan Count Sequencing
[1]
At Count:
Program Executes Command To:
1
PUT Control word into output word
2
PUT Preset word #1 into output word Sends output word
3
PUT Preset word #2 into output word Sends output word
[1]
This count is the scan counter Accumulated value for PLC 2, PLC 2/15, PLC 2/20, and
Mini PLC 2 Controllers. For the PLC Controller, these values would be doubled: 2, 4,
and 6 respectively.
The scan counter must indicate that both an I/O scan and a program
scan have occurred. For PLC-2, PLC-2/15, PLC-2/20 and PLC-2/30
Processors and the Mini-Processor Module, the I/O scan and
program scan, because they are sequential, are synchronous: one
program scan occurs for each I/O scan. This means the scan counter
can simply be incremented each program scan. Section titled Scan
Counter - PLC-2 Family Processors describes a suitable scan
counter for these processors.
With the PLC processor, however, the I/O scan and program scan are
asynchronous; this means that the scan counter must be programmed
to increment based on the longer of the two scans. Section titled
Scan Counter - PLC Processor describes a suitable scan counter
for these processors.
With the sample program following, note that the scan counter is
programmed to run continuously; it resets itself when the
accumulated value equals the preset value, and begins to count again.
This arrangement is normally preferred because it allows subsequent
programmed changes in bits of the output control word to be sent to
the module as soon as possible after the change is made.

Scan Counter PLC 2 Family Processors

Figure 5.6 shows an example scan counter that can be used for any
PLC-2 family processor. This type of scan counter increments with
each program scan. Because the I/O and program scans of these
processors are synchronous, each increment of this scan counter
indicates that both an I/O scan and a program scan have occurred.
Single Transfer Programming
Sends output word
Publication 1771 UM006B-EN-P - June 2002
5–9