11.3 Start-Up Wizard

The start-up wizard should run the first time the
unit is powered on. The wizard must be completed
before the boiler can be used.
1. Set the language.
English
French
2. Set the time.
YYYY:MM:DD:HH:MM:SS
3.
Set the units to display.
Celsius (°C), L/M, Meter
Fahrenheit (°F), GPM, Feet
4. Check the gas type.
Natural Gas
Propane Gas
5. Installation Elevation Check.
Displays the altitude setting using the main DIP
switch.
6. Set the zone system.
Zone Pump System
Zone Valve System
6-1. Pump 1 Settings (When Zone System is Zone
Pump System)
Zone 1 Pump
DHW Pump
7. Set the outdoor reset ON/OFF.
Enable
Disable
7-1. Set the outdoor reset curve (Enable select).
Finned Tube Baseboard
FAN Coil
Cast Iron Baseboard
Low mass Radiant
High mass Radiant
Radiator
Custom
7-2. Set the outdoor high temp.
7-3. Set the outdoor low temp.
7-4. Set the WWSD temp.
8. Set the DHW Call Signal.
DHW Thermostat
DHW Tank Sensor
9. Setup Summary
Once the start-up Wizard is finished, a summary
of the settings will be displayed. Press the OK
button (OK) at each summary screen until the
air purge mode is displayed. Settings made in
the start-up Wizard can be adjusted from the
Main Menu and Installer Menu as described in
Section 11.5 and 11.6.
Operating the Boiler