Configuring The Module And Setting Outputs With Block Transfer Write Instructions - AB Quality ALLEN-BRADLEY 1791 User Manual

Analog block i/o input/output modules
Table of Contents

Advertisement

Configuring the Module and
Setting Outputs with Block
Transfer Write Instructions
Decimal
15
14
13
Octal
17
16
15
0
Module Mode
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
You must configure your block module by performing a block transfer
write (BTW) instruction from the programmable controller to the module.
Each input can be independently configured in one BTW.
Maximum length of the BTW is 27 words (0 thru 26). When configuring
the module, first send the complete BTW. You can shorten the BTW to 3
words for subsequent write operations if parameters for each channel
remain the same.
Block transfer write data is shown in Figure 4.2.
Figure 4.2
Block Transfer Write for Analog Block I/O
12
11
10
09
08
14
13
12
11
10
Scaling
Range
Output Channel 0 Data
Output Channel 1 Data
Output Channel 0 Minimum Scaling
Output Channel 0 Maximum Scaling
Output Channel 1 Minimum Scaling
Output Channel 1 Maximum Scaling
Input Channel 0 Minimum Scaling
Input Channel 0 Maximum Scaling
Input Channel 1 Minimum Scaling
Input Channel 1 Maximum Scaling
Input Channel 2 Minimum Scaling
Input Channel 2 Maximum Scaling
Input Channel 3 Minimum Scaling
Input Channel 3 Maximum Scaling
Input Channel 0 Low Alarm Level
Input Channel 0 High Alarm Level
Input Channel 0 Alarm Deadband
Input Channel 1 Low Alarm Level
Input Channel 1 High Alarm Level
Input Channel 1 Alarm Deadband
Input Channel 2 Low Alarm Level
Input Channel 2 High Alarm Level
Input Channel 2 Alarm Deadband
Input Channel 3 Low Alarm Level
Input Channel 3 High Alarm Level
Input Channel 3 Alarm Deadband
Chapter 4
Analog Block Applications Using
Block Transfers
07
06
05
04
07
06
05
04
Alarm Enable
03
02
01
00
03
02
01
00
Filter
4-3