INSTALLATION GUIDE
TruClimate 700
R-513A
60Hz
General Installation Information ................................................................................................ 2
Dimensional Data ............................................................................................................................ 3
Physical Data .................................................................................................................................... 9
Installation ......................................................................................................................................... 10
Installation of Bypass/Temperature Headers ....................................................................... 14
Removing a Module from the Bank of Units ........................................................................ 17
Lifting and Short Distance Transport ...................................................................................... 18
High Pressure Refrigerant Relief Venting .............................................................................. 19
Water Connections & Water Quality ....................................................................................... 20
Electrical Connections .................................................................................................................. 21
Refrigeration Cycle Analysis ....................................................................................................... 22
Revision Guide ................................................................................................................................. 24
WARNING
WARNING: Before performing service or maintenance
operations on the system, turn off main power switches to
the unit. Electrical shock could cause serious personal injury.
WARNING: All WaterFurnace products are designed,
tested, and manufactured to comply with the latest publicly
released and available edition of UL 60335-2-40 for
electrical safety certification. All field electrical connections
must follow the National Electrical Code (NEC) guide
standards and / or any local codes that may be applicable
for the installation.
WARNING: Only factory authorized personnel are approved
for startup, check test and commissioning of this unit.
INSTALLER: Please take the time to read and understand
these instructions prior to any installation. Installer must
give a copy of this manual to the owner.
OWNER: Keep this manual in a safe place in order to provide
your serviceman with necessary information.
All TruClimate 700 90-140 Ton product is Safety listed under UL60335-2-40 thru ETL
UL-60335-1 / CAN/CSA- C22.2 No. 60335-1
UL-60335-2-40 / CAN/CSA- C22.2 No. 60335-2-40
CAUTION
This appliance is not intended for use by persons (including
children) with reduced physical, sensory, or mental capabili-
ties, or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play
with the appliance.
Maximum altitude for this equipment shall not exceed
2000 m.
For installation only in locations not accessible to the
general public.
Installing and servicing air conditioning and heating equip-
ment can be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
should install, repair or service heating and air conditioning
equipment. When working on heating and air conditioning
equipment, observe precautions in the literature, tags and
labels attached to the unit and other safety precautions that
may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have fire
extinguisher available for all brazing operations.
NOTE: Before installing, check voltage of unit(s) to ensure
proper voltage.
IG1904WW

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TruClimate 700 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for WaterFurnace TruClimate 700

  • Page 1: Table Of Contents

    NOTE: Before installing, check voltage of unit(s) to ensure proper voltage. All TruClimate 700 90-140 Ton product is Safety listed under UL60335-2-40 thru ETL UL-60335-1 / CAN/CSA- C22.2 No. 60335-1 UL-60335-2-40 / CAN/CSA- C22.2 No. 60335-2-40...
  • Page 2: General Installation Information

    TRUCLIMATE 700 INSTALLATION GUIDE General Installation Information Application NOTICE Units are not intended for heating domestic (potable water) by direct coupling. If used for this type of application, a NOTICE: To avoid equipment damage, do not leave the secondary heat exchanger must be used.
  • Page 3: Dimensional Data

    TRUCLIMATE 700 INSTALLATION GUIDE Dimensional Data: 34" 866MM LOW VOLT CONTROL BOX 78" 1982MM HIGH VOLT CONTROL BOX 20" 516MM 16" 406MM 16" 406MM 16" 406MM 19" 475MM 74" 1884MM 105" 2665MM...
  • Page 4 TRUCLIMATE 700 INSTALLATION GUIDE Dimensional Data: Service Clearance POWER INLET 29" 737MM SERVICE CLEARANCE 0" Ø SOURCE OUT SOURCE IN LOAD OUT LOAD IN...
  • Page 5 TRUCLIMATE 700 INSTALLATION GUIDE Dimensional Data: Service Clearance (banked units) 24" 610MM RECOMMENDED 76" 1941MM 24" 24" 610MM 610MM RECOMMENDED 80 INCH REQUIRED FOR RECOMMENDED 30" SERVICE CLEARANCE REMOVING THE MODULE SERVICE CLEARANCE 762MM REQUIRED AVOID INSTALLING PIPING ABOVE 24"...
  • Page 6 TRUCLIMATE 700 INSTALLATION GUIDE Dimensional Data: Concrete Pad Requirements 24" 37" 37" 31" 24" 610MM 942MM 942MM 781MM 610MM Note: Embed 2” x 2” x 0.19” angle iron in concrete house keeping pad as shown in red above. DETAIL A...
  • Page 7 TRUCLIMATE 700 INSTALLATION GUIDE Dimensional Data: Center of Gravity CENTER OF GRAVITY 17.45" 43.95" MODEL WCHSM SINGLE CENTER OF GRAVITY 43.26"...
  • Page 8 TRUCLIMATE 700 INSTALLATION GUIDE Dimensional Data: Bypass and Temperature Headers 16.00 25.86 30.17 ORIGINAL ISSUE 15.00 5/9/23 EC-0006348 4.31 (TYP) 4.00 6.50 15.00...
  • Page 9: Physical Data

    TRUCLIMATE 700 INSTALLATION GUIDE Physical Data Variable Speed Screw Model R-513A Refrigerant Number of Circuits Factory Charge, lbs [kg] 109 [49] 140 [64] 170 [77] Compressor Variable Speed Screw Compressor Quantity [tons] 1 [87] 1 [112] 1 [137] Compressor Weight, lbs [kg]...
  • Page 10: Installation

    TRUCLIMATE 700 INSTALLATION GUIDE Chiller Installation Unpack and inspect unit and pipe rack. Note and photograph any damage that is visible. Check for: О panel damage О tight frame bolts О pipe rack damage О secure headers О loose victaulic connections on header racks О...
  • Page 11 TRUCLIMATE 700 INSTALLATION GUIDE Chiller Installation cont. Remove (4) u-bolts (image below) and retain for later installation. Remove (4) U-bolts Remove (4) pipes that are attached to the pipe rack in shipment (image below). Remove (4) sections of pipe...
  • Page 12 TRUCLIMATE 700 INSTALLATION GUIDE Chiller Installation cont. Place removed pipes into the main unit’s heat exchangers, attach victaulic connections that were previously removed. Using a forklift move main unit into position, carefully guiding pipes from heat exchangers into the pipe rack.
  • Page 13 TRUCLIMATE 700 INSTALLATION GUIDE Chiller Installation cont. 10. Install bolts along the junction of pipe rack frame and unit body. Attach the quick connect isolation valves and flow switches. 12. Install bypass and temperature headers based on the specified loops. Bypass installation is required in 6 pipe applications.
  • Page 14: Installation Of Bypass/Temperature Headers

    TRUCLIMATE 700 INSTALLATION GUIDE Installation Information: Bypass and Temperature Headers CUT GROOVE PER VIC 25.01 REV J CUT GROOVE PER VIC 25.01 REV J 1/2" NPT BUNG 1/2" NPT BUNG WATER TEMP WATER PRESSURE SENSOR TYPE II SENSOR WATER TEMP...
  • Page 15 TRUCLIMATE 700 INSTALLATION GUIDE Installation Information: Bypass and Temperature Headers Install both floating flange gaskets on the small pipes. The gasket must be installed as shown. DO NOT LUBRICATE THE FRONT FACE OF THE GASKET. Failing to install the gasket in the correct orientation will cause a leak. Section view of the flange is shown in Figure 3.
  • Page 16 TRUCLIMATE 700 INSTALLATION GUIDE Installation Information: Bypass and Temperature Headers Place the floating flange and hand thread one bolt in the valve body. Place the flange sandwich plate between the valve seal and the flange seal. Add the rest of the bolts and only hand tighten. Center the sandwich plate using a ruler or a tool with marking of the correct distance between the ring and outer diameter of the flange (SEE Figure 4).
  • Page 17: Removing A Module From The Bank Of Units

    TRUCLIMATE 700 INSTALLATION GUIDE Removing Module from Bank of Units Undo the 2.5” groove couplings, disconnect all 3-way valve harnesses and isolation valve harnesses, u-bolts and victaulic connections (detailed in installation section). Remove bolts attaching the pipe rack to the unit frame (see image) Slightly lift (2in maximum) the module and pull away from the bank.
  • Page 18: Lifting And Short Distance Transport

    TRUCLIMATE 700 INSTALLATION GUIDE Lifting and Short Distance Transport When lifting the chiller all lifting brackets must be used. 2. Always use spreader bars. The sound enclosure of the chiller may be damaged if spreader bars are not used. The front pockets of the chiller must not be used to lift the chiller when connected to the header rack.
  • Page 19: High Pressure Refrigerant Relief Venting

    High Pressure Refrigerant Relief Venting All TruClimate 700 Series units utilize a refrigerant-pressure relief valve which must be vented to the outdoor atmosphere. The valves are located on the discharge piping and have a 1” FPT connection. See figure below for guidance on connecting to the pressure relief valve inside the chiller enclosure. In cases of multiple chillers installed as a bank, each unit may be piped...
  • Page 20 TRUCLIMATE 700 INSTALLATION GUIDE Water Connections Water Piping Temperature Headers Water Piping must be installed in accordance with applica- Temperature headers will need to be installed between the tion codes and per necessary standards. Supply and return building and chiller connections. DP transducers must be connections should be connected per units’...
  • Page 21: Electrical Connections

    TRUCLIMATE 700 INSTALLATION GUIDE Electrical Connections Field proven communicating Aurora Compressor management control (ABC and AXB boards) HydroLink2 Niagara AX based system controller Fused disconnect for high SCCR rating Line reactor 10” chiller interface...
  • Page 22: Refrigeration Cycle Analysis

    TRUCLIMATE 700 INSTALLATION GUIDE Refrigeration Cycle Analysis...
  • Page 24: Revision Guide

    Date: Document Creation 21 July 2023 Manufactured at 9000 Conservation Way Fort Wayne, IN 46809 *IG1904WW* Product: TruClimate 700 Type: Water-Cooled Chiller - 60 Hz Size: 90-140 Tons Document: Installation Manual IG1904WW 07/23 ©2023 9000 Conservation Way, Fort Wayne, IN 46809-9794. Manufacturer has a policy of continual product research and development and reserves the right to change design...
  • Page 25 Utilisez un chiffon mouillé pour toute opération de brasage. Ayez un extincteur à disposition pour toute opération de brasage. Tout appareil TruClimate 700 90-140 Ton répond aux REMARQUE : Avant de procéder à l’installation, vérifiez que la normes de sécurité UL60335-2-40 thru ETL tension de l’appareil est correcte.
  • Page 26: Informations Générales Sur L'installation

    MANUEL D’INSTALLATION TRUCLIMATE 700 Informations générales sur l’installation Utilisation AVIS Les appareils ne sont pas conçus pour le chauffage de l’eau domestique (potable) par couplage direct. Pour ce type AVIS : Pour éviter d’endommager l’équipement, ne laissez d’utilisation, un échangeur de chaleur complémentaire doit pas le système rempli dans un bâtiment sans chauffage être utilisé.
  • Page 27: Données Dimensionnelles

    MANUEL D’INSTALLATION TRUCLIMATE 700 Données dimensionnelles : 34" 866MM BOÎTIER DE COMMANDE LOW VOLT CONTROL BOX BASSE TENSION 78" 1982MM BOÎTIER DE COMMANDE HIGH VOLT HAUTE TENSION CONTROL BOX 20" 516MM 16" 406MM 16" 406MM 16" 406MM 19" 475MM 74" 1884MM 105" 2665MM...
  • Page 28 MANUEL D’INSTALLATION TRUCLIMATE 700 Données dimensionnelles : Espace libre pour l’opération d’entretien PRISE D’ALIMENTATION POWER INLET 29" 737MM SERVICE ESPACE CLEARANCE LIBRE POUR 0" L’OPÉRATION Ø D’ENTRETIEN SOURCE DE SORTIE SOURCE OUT SOURCE D’ENTRÉE SOURCE IN CHARGE D’ENTRÉE LOAD OUT CHARGE DE SORTIE LOAD IN...
  • Page 29 MANUEL D’INSTALLATION TRUCLIMATE 700 Données dimensionnelles : Espace libre pour l’opération d’entretien (appareil en série) 24" 610MM RECOMMENDED RECOMMANDÉ 76" 1941MM 24" 24" 610MM 610MM ESPACE RECOMMANDÉ RECOMMENDED 203 CM REQUIS POUR ESPACE RECOMMANDÉ 80 INCH REQUIRED FOR RECOMMENDED 30" SERVICE CLEARANCE POUR L’OPÉRATION REMOVING THE MODULE RETIRER LE MODULE...
  • Page 30 MANUEL D’INSTALLATION TRUCLIMATE 700 Données dimensionnelles : Exigences relatives à la dalle en béton 24" 37" 37" 31" 24" 610MM 942MM 942MM 781MM 610MM Remarque : Implantez une cornière de 5 x 5 x 0,5 cm dans la dalle en béton comme indiqué en rouge ci-dessus. DÉTAIL A DETAIL A...
  • Page 31 MANUEL D’INSTALLATION TRUCLIMATE 700 Données dimensionnelles : Centre de gravité CENTER OF GRAVITY CENTRE DE GRAVITÉ 17.45" 43.95" MODEL WCHSM SINGLE CENTER OF GRAVITY CENTRE DE GRAVITÉ 43.26"...
  • Page 32 MANUEL D’INSTALLATION TRUCLIMATE 700 Données dimensionnelles : Collecteurs de dérivation et de température 16,00 16.00 25,86 25.86 30.17 30,17 ORIGINAL ISSUE 15,00 15.00 5/9/23 EC-0006348 4,31 4.31 (TYP) 4,00 4.00 6,50 6.50 15,00 15.00...
  • Page 33: Données Physiques

    MANUEL D’INSTALLATION TRUCLIMATE 700 Données physiques Vis à vitesse variable Modèle R-513A Réfrigérant Nombre de circuits Charge d’usine, livres [kg] 109 [49] 140 [64] 170 [77] Compresseur Vis à vitesse variable Volume du compresseur [tonnes] 1 [87] 1 [112] 1 [137] Poids du compresseur, livres [kg] 1621 [735] 1632 [740]...
  • Page 34: Installation

    MANUEL D’INSTALLATION TRUCLIMATE 700 Installation du refroidisseur Déballez et inspectez l’appareil et le support à tuyaux. Notez et photographiez tout dommage visible. Vérifiez les points suivants : О dommage au niveau du panneau О boulons du châssis serrés О dommage au niveau du support à tuyaux О...
  • Page 35 MANUEL D’INSTALLATION TRUCLIMATE 700 Installation du refroidisseur (suite). Retirez les (4) boulons en U (voir image ci-dessous) et gardez-les pour une installation ultérieure. Retirez les (4) boulons en U Retirez les (4) tuyaux fixés au support à tuyaux lors de l’expédition (voir image ci-dessous). Retirez les (4) sections de tuyaux...
  • Page 36 MANUEL D’INSTALLATION TRUCLIMATE 700 Installation du refroidisseur (suite). Placez les tuyaux retirés dans les échangeurs de chaleur de l’appareil principal, fixez les raccords de type victaulic retirés plus tôt. À l’aide du chariot à fourches, mettez l’appareil principal en position, tout en orientant avec précaution les échangeurs de chaleur dans le support à...
  • Page 37 MANUEL D’INSTALLATION TRUCLIMATE 700 Installation du refroidisseur (suite). 10. Fixez les boulons le long de la jonction du cadre du support à tuyau et du corps de l’appareil. Fixez les valves d’isolement à connexion rapide et les régulateurs de circulation d’eau. 12.
  • Page 38 MANUEL D’INSTALLATION TRUCLIMATE 700 Information sur l’installation : Collecteurs de dérivation et de température RAINURE TAILLÉE EN FONCTION CUT GROOVE PER VIC 25.01 REV J DE VIC 25.01 REV J RAINURE TAILLÉE EN FONCTION CUT GROOVE PER VIC 25.01 REV J DE VIC 25.01 REV J BOUCHON NTP 1,27 CM 1/2"...
  • Page 39 MANUEL D’INSTALLATION TRUCLIMATE 700 Information sur l’installation : Collecteurs de dérivation et de température Installez les deux joints d’étanchéité de la bride flottante sur les petits tuyaux. Le joint d’étanchéité doit être installé comme illustré. NE PAS LUBRIFIER LA FACE AVANT DU JOINT D’ÉTANCHÉITÉ. Un joint qui n’est pas installé suivant le bon sens provoquera des fuites.
  • Page 40 MANUEL D’INSTALLATION TRUCLIMATE 700 Information sur l’installation : Collecteurs de dérivation et de température joint de valve et le joint de bride. Ajoutez le reste des boulons et serrez uniquement à la main. Centrez la plaque sandwich à l’aide d’une règle et d’un outil indiquant la distance exacte entre la bague et le diamètre extérieur de la bride (VOIR figure 4). Si la bague n’est pas correctement centrée, cela risque de provoquer des fuites.
  • Page 41: Extraction Du Module De La Banque D'appareils

    MANUEL D’INSTALLATION TRUCLIMATE 700 Extraction du module de la banque d’appareils Démontez les raccords à rainure de 6 cm, déconnectez les faisceaux de vannes 3 voies et les faisceaux de vannes d’isolement, les boulons en U et les raccords de type victaulic (détaillés dans la section d’installation). Retirez les boulons qui fixent le support à...
  • Page 42: Levage Et Transport Sur Courte Distance

    MANUEL D’INSTALLATION TRUCLIMATE 700 Levage et transport sur courte distance Lors du levage du refroidisseur tous les supports de levage doivent être utilisés. Toujours utiliser les palonniers. L’enceinte d’insonorisation peut être endommagée si le palonnier n’est pas utilisé. Les poches avant du refroidisseur doivent être utilisées pour lever le refroidisseur lorsqu’il est raccordé au support collecteur.
  • Page 43: Évent De Décharge Du Réfrigérant À Haute Pression

    MANUEL D’INSTALLATION TRUCLIMATE 700 Évent de décharge du réfrigérant à haute pression Tous les appareils TruClimate de la série 700 utilisent une vanne de décharge à haute pression qui doit être ventilée en atmosphère extérieure. Les valves sont situées sur la tuyauterie de refoulement et ont un raccord de 2,5 cm. Voir la figure ci-dessous pour l’orientation sur le raccordement de la soupape de décharge à...
  • Page 44 MANUEL D’INSTALLATION TRUCLIMATE 700 Raccords d’eau Tuyauterie d’eau Collecteurs de température La tuyauterie d’eau doit être installée conformément aux Des colleteurs de température devront être installés codes d’application et aux normes en vigueur. Les raccords entre le bâtiment et les connexions du refroidisseur. Des d’alimentation et de retour doivent être effectués suivant transducteurs DP doivent être installés au niveau de la les instructions de l’appareil.
  • Page 45: Raccords Électriques

    MANUEL D’INSTALLATION TRUCLIMATE 700 Raccords électriques Contrôle du compresseur Aurora communicant ayant fait ses preuves sur le terrain (cartes ABC et AXB) Contrôleur de système HydroLink2 Niagara AX Déconnexion par fusible pour un SCCR nominal élevé Réacteur de ligne Interface refroidisseur de 25 cm...
  • Page 46: Analyse Du Cycle De Réfrigération

    MANUEL D’INSTALLATION TRUCLIMATE 700 Analyse du cycle de réfrigération...
  • Page 48: Guide De Révision

    Guide de révision Pages : Description : Date : Par : Toutes Création de document 21 juillet 2023 Fabriqué à 9000 Conservation Way Fort Wayne, IN 46809 *IG1904WW* Produit : TruClimate 700 Type : Refroidisseur à eau - 60 Hz Taille : 90-140 tonnes Document : Manuel d’installation IG1904WW 07/23 ©2023 9000 Conservation Way, Fort Wayne, IN 46809-9794. La politique du fabricant en matière de recherche et de développement de produits est continue; il se réserve le droit de modifi...