INTERCONNECTING ADDITIONAL UNITS
To connect several smoke detectors, press and hold the Test/Hush button on the primary
unit until the Red indicator flashes 3 times then immediately release it.
The Red indicator will flash rapidly for 2 minutes while waiting for other devices to pair. If
you need to end the pairing in advance, press the Test/Hush button again.
Press and hold the Test/Hush button on the secondary unit(s) until the Green indicator
flashes 2 times then immediately release it. The unit will emit a long beep and the Red
indicator will flash slowly. If the pairing is successful, the indicator will flash 3 times.
If the products have been previously paired with other groups, it will exit directly after the
Green indicator flashes 4 times. For a successful match, you should clear paired data on all
units first.
Note: The equipment has been matched before delivery.
Clearing paired data: Press and hold the Test/Hush button and wait for the Green
indicator to flash 4 times, immediately release the button. If the paired data is cleared
successfully, it will flash 3 times slowly and exit. Otherwise, repeat the above steps to clear.
FUNCTIONS
Low voltage alarm:
When the built-in battery voltage of the smoke detector is below 2.7V, the Red indicator
flashes once every 50 seconds, accompanied by a beep sound. The app will also show a
warning in the status bar.
Smoke alarm fault:
The LED of the smoke alarm flashes once every 8 seconds and is accompanied by a buzzer.
The app status will display an alarm fault.
If the device operates normal the Red LED indicator flashes once every 55 seconds.