Mitsubishi Electric MUZ-AP25VG-E1 Service Manual page 58

Hide thumbs Also See for MUZ-AP25VG-E1:
Table of Contents

Advertisement

NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (12-3.).
Upper lamp
Abnormal point
(Indoor unit)
(Failure mode/protection)
10-time blink
Discharge temperature
2.5 seconds
OFF
11-time blink
Bus-bar voltage (DC)
2.5 seconds
OFF
Each phase current of
compressor
14-time blink
Stop valve (Closed valve)
2.5 seconds
OFF
4-way valve/
Pipe temperature
16-time blink
Outdoor refrigerant system
2.5 seconds
abnormality
OFF
OBH789H
LED indication
(Outdoor P.C. board)
Temperature of discharge temperature
thermistor has been 50°C or less for
20 minutes.
8-time blink
Bus-bar voltage of inverter cannot be
2.5 seconds OFF
detected normally.
9-time blink
Each phase current of compressor
2.5 seconds OFF
cannot be detected normally.
14-time blink
Closed valve is detected by
2.5 seconds OFF
compressor current.
16-time blink
The 4-way valve does not work
2.5 seconds OFF
properly.
The indoor coil thermistor detects an
abnormal temperature.
1-time blink
A closed valve and air trapped in the
2.5 seconds OFF
refrigerant circuit are detected based
on the temperature sensed by the
indoor and outdoor thermistors and the
current of the compressor.
58
Condition
Remedy
• Refer to 12-5. "Check
of LEV".
• Check refrigerant
circuit and refrigerant
amount.
• Refer to 12-5. "How
to check inverter/
compressor".
• Check stop valve.
• Check the 4-way
valve.
• Replace the inverter
P.C. board.
• Check for a gas leak
in a connecting piping
etc.
• Check the stop valve.
• Refer to 12-5.
"Check of outdoor
refrigerant circuit".
Indoor/outdoor
Outdoor unit
unit failure
failure mode
mode recall
recall function
function

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents