1. DESCRIPTION
The Viking Quick Response Extra-Large Orifice Upright Sprinkler VK531 is a ther-
mosensitive glass bulb spray sprinkler available in several different finishes and
temperature ratings to meet design requirements. The special Polyester, Electroless
Nickel PTFE (ENT), and PTFE coatings can be used in decorative applications where
colors are desired. In addition, these coatings have been investigated for installa-
tion in corrosive environments and are listed/approved as indicated in the Approval
Charts.
The extra-large orifice provides greater flows at lower pressures than standard
orifice or large orifice sprinklers. This feature allows reduced pipe sizing for hy-
draulically calculated sprinkler systems, which require high densities of water.
Viking Standard Response Extra-Large Orifice Sprinklers may eliminate the
need for a fire pump or reduce the size of the pump if it is required. On existing
systems, replacing large orifice sprinklers with extra-large orifice sprinklers may
provide the higher densities required to allow an increase in the hazard classifica-
tion of an occupancy.
Viking Quick Response Extra-Large Orifice Upright Sprinkler VK531 may be
ordered and/or used as an open sprinkler (glass bulb and pip cap assembly re-
moved) on deluge systems. Refer to
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class 2020
VdS Approved: Certificate G413059, G413060
LPCB Approved: Certificate 096e/14
Refer to Approval Chart 1 and Design Criteria on page 3 for cULus Listing requirements, and refer to Approval Chart 2 and Design
Criteria on page 4 for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2000.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: See Approval Charts
Nominal K-Factor: 11.2 U.S. (161.3 metric
* Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown
by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-5/16" (58.7 mm)
Material Standards:
Sprinkler Frame: Brass UNS-C84400
Deflector: Brass UNS-C26000
Bulb: Glass, nominal 3 mm diameter
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
Compression Screw: Brass UNS-C36000
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT Coated Sprinkler: Belleville Spring-Exposed, Screw and Pipcap-ENT plated.
Ordering Information: (Also refer to the current Viking price list.)
Order Quick Response Extra-Large Orifice Upright Sprinkler VK531 by first adding the appropriate suffix for the sprinkler finish
and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Form No. F_120699
18.10.11
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Ordering Instructions
)
*
Rev 18.2.P65
NOTE: As of May 2018 all logos have been removed from the
wrench boss.
below.
QUICK RESPONSE
EXTRA-LARGE ORIFICE
UPRIGHT SPRINKLER
VK531 (STORAGE-DENSITY/AREA)
Replaces Form No. F_120699 Rev 18.2
(Added P65 Warning.)
Page 1 of 5

Advertisement

loading
Need help?

Need help?

Do you have a question about the VK531 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Viking VK531

  • Page 1 Ordering Information: (Also refer to the current Viking price list.) Order Quick Response Extra-Large Orifice Upright Sprinkler VK531 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
  • Page 2: Technical Data

    Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °F) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G, OPEN = Z (PTFE only). For example, sprinkler VK531 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 10633AB Available Finishes And Temperature Ratings: Refer to Table 1.
  • Page 3 VK531 (STORAGE-DENSITY/AREA) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com 1-3/4” (45 mm) Protective clip 2-5/16”...
  • Page 4 (Also refer to Approval Chart 1 above.) cULus Listing Requirements: Quick Response Extra-Large Orifice Upright Sprinkler VK531 is cULus Listed for installation in accordance with the latest edition of NFPA 13 for standard upright spray sprinklers: Designed for use in hazard occupancies up to and including Ordinary Hazard Group II with a minimum operating pressure of 7 PSI (0.5 bar).
  • Page 5 FM Approval Requirements: Quick Response Extra-Large Orifice Upright Sprinkler VK531 is FM Approved as a quick response upright Non-Storage sprinkler and as a quick response upright Storage sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including 2-0 and 8-9).
  • Page 6 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 7 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 8 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 9 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 10: Listings And Approvals

    1. DESCRIPTION Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An open sprinkler does not use an operating element and is open at all times.
  • Page 11 TECHNICAL DATA SPRINKLER OVERVIEW The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow arrow in the direction of discharge.
  • Page 12 Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
  • Page 13: Warranty Terms And Conditions

    For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking’s current list price schedule at www.vikinggroupinc.com or contact Viking directly. New Bulletin Form No. F_111218 18.11.15...