Step 3 — Field Fabricate Ductwork
— Secure all
ducts to building structure. Use flexible duct connectors
between unit and ducts as required. Insulate and weather¬
proof all external ductwork, joints and roof openings
with flashing and mastic in accordance with applicable
codes.
Ducts passing through an unconditioned space must
be insulated and covered with a vapor barrier.
A minimum clearance is not required on 50DPE014
and 50DP016 units. The 50DP020 units with electric
heat require one-in. clearance the first 24 in. of ductwork.
Outlet grilles must not lie directly below unit discharge.
Step 4 — Make Unit Duct Connections
— Unit
is shipped for through-the-bottom duct connections.
Ductwork openings are shown in Fig. 1 and 4. Duct
connections are shown in Fig. 5. Field-fabricated con¬
centric ductwork may be connected as shown in Fig. 6 and
7. Attach all ductwork to roof curb and roof curb base-
pans. Refer to installation instructions shipped with
accessory roof curb.
50DR DPE0I2, 014 50DP0I6
INDOOR FAN MOTOR
NOTE Do not drill in this area, damage to basepan may result
in water leak.
Fig. 5 — Air Distribution — Through-the-Bottom
Step 5 — Trap Condensate Drain
— See Fig. 4
and 8 for drain location. Plug is provided in drain hole
and must be removed when unit is operating. One 3/4-in.
half coupling is provided inside unit evaporator section
for condensate drain connection. An 8-1/2 in. x 3/4-in.
diameter and 2-in. x 3/4-in. diameter pipe nipple coupled
to standard 3/4-in. diameter elbows provide a straight
path down through holes in unit base rails (see Fig. 9).
A trap at least 4 in. deep must be used and must be pro¬
tected against freeze-up.
NOTE: Do not drill in this area, damage to basepan may result
in water leak
Fin 6 — Concentric Duct Air Distribution
Shaded area indicates block-off panels
NOTE. Dimension A, A1 and B, B1 are obtained from field-
supplied ceiling diffuser
Fig. 7 — Concentric Duct Details
Fig. 8 — Condensate Drain Details
6