Cat M1), see also chapter 4.2. Further specifications of both modems can be found in Appendix 3 of this manual. The inputs are equipped with EX barriers so that UNICOM 300 may be used with equipment that is placed in a zone 0 with a potentially explosive atmosphere.
Two pulse outputs One serial input for UNIGAS 300 UNICOM 300 can count two pulses in the first two counters, readout an encoder in a third counter and log these into an interval logger. UNICOM 300 can transmit the incoming pulses or encoder counter position to two pulse outputs.
It is possible that the sealing will stick, making the housing more difficult to open. Closing of the housing must be done with caution when the UNICOM 300 is hanging upright. Make sure that the lid does not rest on the hinge when closing.
Installation and user manual UNICOM 300 N511 3.3 Connections UNICOM 300 has three cable glands for cables. See table 1 Unused cable glands must be sealed with the supplied sealing caps. Zie table 2 Figure 2: connections UNICOM 300 Output...
Installation and user manual UNICOM 300 N511 3.4 Inside lid UNICOM 300 Figure 3: inside lid UNICOM 300 Switch Switch Function operation optical head detection Optical head placed; Status LEDs and optical head detection are activated. For at least 4 Modem is turned on;...
Installation and user manual UNICOM 300 N511 3.5 Front view inside UNICOM 300 Figure 4: front view inside UNICOM 300 Switch Switch Function operation Manual Encoder Manual initialization of encoder readout (LOGGER function) initialization The status of the initialization is shown through the Encoder status LED.
APN; such as APN name with the corresponding username and password. 4.1 SIM-card placement Open UNICOM 300 (see figure 1, note 2). The mini-SIM holder is located in the lid of the UNICOM 300 (see figure 3).
5 Into service 5.1 Activation and registry When using the UNICOM 300 as data logger, it is necessary to carry out the following action with the central acquisition system: Activate the modem by operating SW1 for 4 seconds until the NETWORK status LED goes on (see figure 1).
6.1 Activation of the modem The modem can be turned on by pressing switch SW1 for at least 4 seconds until the NETWORK status LED starts flashing, SW1 can then be released. The UNICOM 300 modem will remain on for 25 to 30 minutes.
7.1 System status check UNICOM 300 There are eight status LEDs on UNICOM 300 that show different states. The status LEDs are active if an optical head is placed on the communication port (SW2, figure 1), or if SW1 (service window) is operated.
If the encoder counter is reduced, the counter mode will not be adopted by UNICOM 300. A status message is made of this in the status register. If the return is temporary, UNICOM 300 will take over the counting position again as soon as it is larger than the last meter reading.
Check and / or program the correct pulse ratios (parameter 1:0.7.2 and 2:0.7.2) by means of the UNITOOL service software. For UNICOM 300 pulse outputs, a choice can then be made for Vm1-Vm2-Vm3 or Alarm1 via the parameters mentioned in chapter 12.
UNICOM 300 N511 9 Battery packs UNICOM 300 is powered by one or two lithium battery packs (see Figure 4). UNICOM 300 is equipped with two power supply connectors: CON1 and CON2 (see figure 3). A battery pack can be connected to each connector.
Installation and user manual UNICOM 300 N511 The battery packs may be replaced regardless of the state in which UNICOM 300 is located, provided that the battery packs are replaced one by one so that one package always remains connected to UNICOM 300.
UNICOM 300 N511 12 Counters and registers Below are the counters and registers (parameters) that are present in UNICOM 300 MODEM function (Chapter 12.1) or UNICOM 300 LOGGER function (Chapter 12.2). The name is displayed per counter or register, supplemented by the OBIS code, the security level and a short description.
Page 19
• • EXT – BAT • EXT – ACCU • Ah-used C.90.21 Consumed energy from the UNICOM 300 battery in Ah. Networkh C.90.4 GSM / GPRS connected to network time registration Commh C.90.5 GSM / GPRS communication time registration DDN5001GHEN/10-2022/Rev.B3...
Page 20
Installation and user manual UNICOM 300 N511 GPRS / LTE cat. (M)1 settings Name Unit OBIS Security level Description TCP APN Name C.92.40 Password 2a APN name on which UNICOM 300 must log in for TCP TCP APN user C.92.41...
Page 21
Installation and user manual UNICOM 300 N511 GPRS / LTE cat. (M)1 settings (continued) Name Unit OBIS Security level Description Pin code for modem. If an Modem CHV1 ME C.92.61 Password 2a incorrect PIN is used for a SIM password...
Installation and user manual UNICOM 300 N511 12.2 UNICOM 300 datalogger Device data Name Unit OBIS Security level Description Device type and version Device type C.1.1 UNICOM 300. Serial number of the Serial number C.1.0 UNICOM 300. Firmware version Firmware version 7-0:0.2.0...
Page 23
Broadcast mode C.93.15 Password 2a Response to a 1107 request. In "Off" UNICOM 300 does not respond if there is no device address in the request (transparent modem) With "On", there will be a response if there is no device address in the...
Page 24
2 status registers 7.1, 7.2 and 7.3 at alarm output 2. Consumption Data Name Unit OBIS Security level Description UBatt LOGGER C.90.6 Voltage of the UNICOM 300 Battery hour C.6.0 Number of hours in operation on counter LOGGER battery DDN5001GHEN/10-2022/Rev.B3...
Page 25
C.91.8 Password 2a Text for display in the file name. If this object is set to 00000000, the serial number of UNICOM 300 is issued in the file name. This object is also displayed in data read out. FTP interval C.92.49...
Page 26
Event writing of OBIS parameter 9, B, D, F 8, 9, A, B, C, D, E, F UNICOM 300 had no power supply 4, 5, 6, 7, Event C, D, E, F 2, 3, 6, 7, Clock has been set with more than +/-...
Page 27
Installation and user manual UNICOM 300 N511 Status registry 1; operational status 1 St : 1 Status Weergave Omschrijving CRC-error 8, 9, A, B, E F CRC error occurred in program memory of the processor LOGGER of the top PCB. The memory is checked once per hour...
Page 28
Installation and user manual UNICOM 300 N511 Status registry 3; other alarm and warnings St : 3 Weergave Weergave Omschrijving Encoder 4, 5, 6, 7, Set if encoder initialization could not be performed. This to enable indicate that encoder is functionally switched on, but not C, D, E, F read out.
• Battery or 230VAC detection Low battery handling Automatic shutdown of modem to prevent • flat battery: log functionality is guaranteed for at least 6 months Battery exchange Can be performed independent of functional • state of UNICOM 300 DDN5001GHEN/10-2022/Rev.B3...
Page 32
Installation and user manual UNICOM 300 N511 Status indicator Front Status indicator LED’s - PWR (battery status (Good; Low; Flat)) • Activated at placing optical head - STATUS (stock-lock active, not active, critical error) - NETWORK (IP service status: Non;...
Page 33
Installation and user manual UNICOM 300 N511 Status indicator 2 Status indicator LED’s Diagnosis • NAMUR Encoder counter initialization Inputs Inputs LF 1 and 2 2 Hz max, reed and electronic switches with • pulse length min 50 ms Cable gland Ø...
Page 34
180 x 50 mm • material Stainless steel • Weight 0,2 kg • Specification universal mounting bracket for mounting UNICOM 300 with UNIGAS 300 General dimensions approx. 40 x 240 mm • material Stainless steel • Weight 0,2 kg •...
Installation and user manual UNICOM 300 N511 Appendix 4: Serial connections UNIGAS converters Connector type Description Cable color black with M12 Cable color blue with M12 Cable color blue with Male connector Male connector optical connector UNIGAS EVC type UNIGAS 61D or UNIGAS...
Page 36
Installation and user manual UNICOM 300 N511 DDN5001GHEN/10-2022/Rev.B3...