9 Heat pump settings

Some of the settings can only be changed at the service level. To log into the service level, press the
knob for 3 seconds and enter code 2000. See section
the settings in the heat pump's user interface.
Before changing a setting, make sure that you understand how the change affects
NOTICE
the operation of the system.

9.1 Basic settings for the heat pump

The basic settings can be found in the Heat pump menu.
Time and date
For the heating programme to work as desired, the year, date and time of the controller clock must be set
correctly under System clock.
The heat pump will not start until the clock is properly set.
Language selection
You can change the interface language under Language selection. By default, the heat pump's language
is Finnish.
The language options are Finnish, English and Swedish.
If
the
user
interface
Lämpöpumppu►Kielenvalinta.
Heat pump operating mode
You can start the heat pump under HP operating mode. When delivered from the factory, the device is
set to Off. When you set the mode to Auto, the heat pump automatically starts heating the domestic and
heating water as needed.

9.2 Domestic water system settings

The heat pump produces domestic hot water by using change-over valve control. When the domestic
water request is activated, the change-over valve turns to domestic water accumulator and charging
starts. The heat pump charges the domestic water by the setpoint and returns to the heating position. If
heating is active, the charging continues to heat the property.
The domestic water accumulator has two temperature sensors: B2 at the top section is the measuring
sensor and sensor B3 below it is the control sensor. The charging of domestic water is started when the
value measured by sensor B3 is lower than the difference between the setpoint and charging hysteresis.
Charging ends when the setpoint is reached.
In the Domestic hot water menu, you can view the following information:
Taurus Inverter Pro and Taurus EVI
Installation, Commissioning and Maintenance Manual
© 2023 Gebwell
is
in
Finnish,
the
User interface menu structure
language
selection
9 Heat pump settings
for the location of
can
be
found
under
Version: 2-1 12/04/2023