Bryant 479 Installation Instructions Manual page 13

All weather heating and cooling unit
Hide thumbs Also See for 479:
Table of Contents

Advertisement

Installation Instructions
479
Sizes 180 & 240
Series E
ATTACH TO INSTALLATION INSTRUCTIONS 39479D8
I
39479D12
4/1/72
Use attached 39479D8 Installation Instructions (with changes indicated below) to in¬
stall sizes 180 and 240 of Model 479, Series E, units.
Models 180~ and 240-479 Series E units differ from Series D units as described below.
1,
GAS INPUT to the cooling section of Model 180^479 was. increased from 450,000 Btuh
to 492,000 Ktuh (246,000 Btuh input each chiller).
The generator burner orifices
were changed from #39 drill size to #36 drill size on the natural gas unit.
The
burner orifices on the propane unit were changed from #53 drill size to #52 drill
size.
2,
GAS INPUT to the cooling section of Model 240^479 was increased from 600,000 Btuh
to 640,000 Btuh (320,000 Btuh input each chiller).
The generator burner orifices
were changed from #41 drill size to #39 drill size'on the natural gas unit.
The
burner orifices on the propane unit were changed from #54 drill size to #53 drill
size.
3.
AUTOMATIC PILOT REIGNITI0N is used on both natural and propane units in both the
heating and cooling sections on both Models 180^ and 240^479.
The wiring diagrams
on pages 11 and 12 apply to both natural and propane gas units.
4.
FUSE SIZE was changed on Model 180-479.
The 180-479 now uses one 60 amp and two
3O amp fuses.
NOTE:
Hydraulic Pump Heater Kit P/N 65134D01 (2 required) must be field installed on
each chiller if the cooling section is to be operated at outdoor temperatures below
40°F.
Adding the heater kits permits operation of the cooling section at outdoor temp¬
eratures down to -30°F.
Antifreeze must also be added for protection at the lowest
outdoor temperature.