Adjustment Possibilities; Electrical Wiring - Riello CG 120/P-F2SD 00 Installation, Use And Maintenance Instructions

Gas trains with proportional valve
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 30
4.6

Adjustment possibilities

P
gas inlet pressure (5 ÷ 36 mbar).
PL
air pressure (0.4 ÷ 30 mbar).
PF
pressure at the combustion head (-2 ÷ + 20 mbar).
PBr
gas pressure to burner (0.4 ÷ 50 mbar).
Effective burner pressure:
pBr = PBr - PF
Effective air pressure:
pL
= PL - PF (min. 0.4 mbar)
To have stable pressures at the output of the val-
ve, the pressures in the combustion chamber
need to be constant.
WARNING
If not, the maximum and minimum outputs of the
burner will vary.
4.7

Electrical wiring

Notes on safety for the electrical wiring
 The electrical wiring must be carried out with the electrical supply disconnected.
 Electrical wiring must be carried out by qualified personnel and in compliance with the regulations currently in
force in the country of destination.
 The manufacturer declines all responsibility for modifications or connections different from those shown in the wir-
ing diagrams.
 Check that the electrical supply of the train corresponds to that shown on the identification label and in this man-
ual.
 The electrical safety of the device is obtained only when it is correctly connected to an efficient earthing system,
DANGER
made according to current standards. It is necessary to check this fundamental safety requirement. In the event of
doubt, have the electrical system checked by qualified personnel. Do not use the gas tubes as an earthing system
for electrical devices.
 Do not touch the device with wet or damp body parts and/or in bare feet.
 Do not pull the electric cables.
The gas train is factory set to be connected according to the wir-
ing scheme shown in Fig. 5.
Installation
p Br
Gas
P
2
Grey
socket
6
GB
+ N
- N
3 1
2
3
P h
N 1 2 3
D7036
S7632
p L
Air
Fig. 4
1
Black
socket
Fig. 5
2903011