Economizer (Single Or Dual Enthalpy) With Power Exhaust; Economizer With Optional Vav Control; Economizer With Optional Vav Blower With Power Exhaust; Motorized Outdoor Air Dampers - York 20 Series Installation Manual

Gas/electric single package air conditioners
Table of Contents

Advertisement

349215-JIM-B-1008
ECONOMIZER (SINGLE OR DUAL ENTHALPY) WITH
POWER EXHAUST
This system operates as specified above with one
addition. The power exhaust motor is energized 45
seconds after the actuator position exceeds the
exhaust fan setpoint on the economizer control. When
the power exhaust is operating, the second stage of
mechanical cooling will not operate. As always, the "R"
to "G" connection provides minimum position but does
not provide power exhaust operation.

ECONOMIZER WITH OPTIONAL VAV CONTROL

The position of the outside air and return air dampers
are controlled through a 2-10 VDC signal from the VAV
control board. The economizer is enabled only in Occu-
pied or Recovery mode. When the control is not pow-
ered or is in Unoccupied mode, the outside air
dampers will be closed. When the supply fan is pow-
ered and there is no Y1 call, or if free-cooling is
unavailable, the control opens the economizer damp-
ers to the minimum position setting.
Free-cooling is available if the outdoor air temperature
meets one of the three criteria discussed below, based
upon the unit's configuration.
Dry Bulb: The control refers to input from the Out-
side Air Temperature sensor and will allow free-
cooling when the outdoor temperature is less than
both the First-Stage SAT Control setpoint plus 5 °F,
and the Economizer OAT Enable setpoint.
Single Enthalpy (optional): A field-installed, Out-
door Air Humidity sensor is connected to the con-
trol. When the measured outdoor enthalpy is below
the Outside Air Enthalpy setpoint, and the outdoor
temperature is less than the First-Stage SAT Con-
trol setpoint plus 5 °F, free-cooling is available.
Dual Enthalpy (optional): Both the field-installed
Outdoor Air Humidity and the Return Air Humidity
sensors are connected to the control. When the
measured outdoor air enthalpy is less than the
measured return air enthalpy, and the outdoor tem-
perature is less than the First-Stage SAT Control
setpoint plus 5 °F, free-cooling is available.
If free-cooling is available with a Y1 call, then the con-
trol modulates the economizer dampers to maintain the
First-Stage SAT Control setpoint, plus or minus one
degree. If free-cooling is unavailable, then 1st-stage
mechanical cooling is initiated.
Johnson Controls Unitary Products
If at anytime the outdoor air temperature rises above
the First-Stage SAT Control setpoint plus 5 °F, while
free-cooling is available, then a Y1 call will also initiate
1st-stage mechanical cooling.
For a Y2 call, free-cooling is available based upon the
criteria described above, except a Second-Stage SAT
Control setpoint is used in the determination.
Once the call for cooling has been satisfied, it will de-
energize any compressors and condenser fans, after
the minimum compressor run times have been satis-
fied. Otherwise, the unit operates each cooling system
until the minimum run times for the compressors have
been completed.
Upon de-energizing the final compressor, the blower
will continue to run with the economizer damper in its
minimum position if in the Occupied mode; otherwise,
the blower will stop following the elapse of the fan-off
delay for cooling, and the economizer outdoor damper
will close.
ECONOMIZER WITH OPTIONAL VAV BLOWER WITH
POWER EXHAUST
The power exhaust motor is energized via the control-
ler's EXH~ terminal and the ER relay, based on the
position of the economizer damper parameter settings
in the VAV control. Minimum run time is 10 seconds;
minimum off time is 60 seconds. The outlet pressure of
the power exhaust fan forces the barometric relief
dampers open; gravity closes the dampers when the
exhaust fan is off.

MOTORIZED OUTDOOR AIR DAMPERS

This system operation is the same as the units with no
outdoor air options with one exception. When the "R" to
"G" circuit is complete, the motorized damper drives
open to a position set by the thumbwheel on the
damper motor. When the "R" to "G" circuit is opened,
the damper spring returns fully closed.

COOLING OPERATION ERRORS

Each cooling system is monitored for operation outside
of the intended parameters. Errors are handled as
described below. All system errors override minimum
run times for compressors.
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

J15djJ18djJ20djJ25dj

Table of Contents