eSure™
Inverter Module
User Manual
Specification Number: 1I1201000
Model Number: I120-1000

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the eSure I120-1000 and is the answer not in the manual?

Questions and answers

Summary of Contents for Vertiv eSure I120-1000

  • Page 1 eSure™ Inverter Module User Manual Specification Number: 1I1201000 Model Number: I120-1000...
  • Page 2 The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
  • Page 3: Table Of Contents

    Vertiv™ eSure™ Inverter Module User Manual TABLE OF CONTENTS Admonishments Used in this Document ..........................iv Important Safety Instructions ..............................v Static Warning .................................... vii 1 Introduction ....................................1 1.1 Overview ......................................................... 1 1.2 Specifications ..................................................... 1 1.2.1 AC Output Ratings ..............................................1 1.2.2 DC Input Ratings ..............................................
  • Page 4: Admonishments Used In This Document

    Vertiv™ eSure™ Inverter Module User Manual Admonishments Used in this Document will likely DANGER! Warns of a hazard the reader be exposed to that will result in death or serious injury if not avoided. (ANSI, OSHA) could WARNING! Warns of a potential hazard the reader...
  • Page 5: Important Safety Instructions

    Vertiv™ eSure™ Inverter Module User Manual Important Safety Instructions Safety Admonishments Definitions Definitions of the safety admonishments used in this document are listed under “Admonishments Used in this Document” on page iv. General Safety DANGER! YOU MUST FOLLOW APPROVED SAFETY PROCEDURES.
  • Page 6 Vertiv™ eSure™ Inverter Module User Manual Personal Protective Equipment (PPE) DANGER! ARC FLASH AND SHOCK HAZARD. Appropriate PPE and tools required when working on this equipment. An appropriate flash protection boundary analysis should be done to determine the “hazard/risk” category, and to select proper PPE.
  • Page 7: Static Warning

    Vertiv™ eSure™ Inverter Module User Manual Static Warning This equipment contains static sensitive components. The warnings listed below must be observed to prevent damage to these components. Disregarding any of these warnings may result in personal injury or damage to the equipment.
  • Page 8 Vertiv™ eSure™ Inverter Module User Manual This page intentionally left blank. viii...
  • Page 9: Introduction

    1 Introduction 1.1 Overview The Vertiv™ eSure™ 1I120-1000 is a compact inverter module which offers efficient power conversion. It operates from a nominal 120 VAC or 48 VDC source (as a default power input) to provide nominal 120 VAC load power.
  • Page 10 Vertiv™ eSure™ Inverter Module User Manual WARNING! The inverter is rated for continuous operation at full output power up to +45 °C (+113 °F). Operation between +45 °C (+113 °F) and +80 °C (+176 °F) will result in output power decrease. When ambient temperature increases above +80 °C (+176 °F), the inverter shuts down.
  • Page 11: Dc Input Ratings

    Vertiv™ eSure™ Inverter Module User Manual Figure 1.3: DC-AC Efficiency Curve (53.5VDC) DC-AC Efficiency VS Load 93.00% 92.00% 91.00% 90.00% 53.5V 89.00% 88.00% 87.00% 86.00% 90% 100% Load 1.2.2 DC Input Ratings • Voltage: Nominal 48 VDC. 40 VDC to 58.5 VDC, off at 40 VDC and 58.5 VDC, fails safe with reverse polarity on battery.
  • Page 12: Compliance Information

    Vertiv™ eSure™ Inverter Module User Manual • Surge Protection: Compliance with IEC60664-1. Satisfy category IV installation place, I capable of withstanding 1.2/50uS+8/20us wave, higher than 6kV/3kA. • Ventilation Requirements: The inverters are fan cooled and utilize front to back forced ventilation. An inverter must be mounted so ventilating openings are not blocked and temperature of the air entering the inverter does not exceed the “Operating Ambient Temperature Range”...
  • Page 13: Mechanical Specifications

    Vertiv™ eSure™ Inverter Module User Manual AC - Low/High Input Voltage Protection: When the AC input voltage is less than 96 VAC, the inverter will shut down or transfer to DC input. When the AC input voltage is higher than 140 VAC, the inverter will shut down or transfer to DC input. The maximum AC input voltage must not exceed 140 VAC.
  • Page 14 Vertiv™ eSure™ Inverter Module User Manual Table 1.1: Exchange of Information between Inverter and Controller Commands / Signals that can be Received by the Inverter Information Gathered by the Controller from the Inverter Module Module from the Controller • Remote On/Off •...
  • Page 15: Operation

    Vertiv™ eSure™ Inverter Module User Manual 2 Operation 2.1 Local Indicators Location and Identification: Refer to Figure 2.1. Description: There are three (3) indicators located on the inverter’s front panel. The functions of these indicators are as shown in Table 2.1.
  • Page 16: Installing Inverter Modules

    Vertiv™ eSure™ Inverter Module User Manual 2.2 Installing Inverter Modules Inverters can be inserted or removed with power applied (hot swappable). NOTE! Each inverter locks into a module mounting shelf by means of a latch located on the bottom of the module. The latch and inverter handle are interactive.
  • Page 17: Troubleshooting And Repair

    Vertiv™ eSure™ Inverter Module User Manual 3 Troubleshooting and Repair 3.1 Troubleshooting 3.1.1 Inverter Module Parallel Current Sharing Abnormal When multiple inverters are operating in parallel and the load is greater than 20%, if the current sharing abnormal among them is greater than 0.5 A, check if the inverter is properly seated in the shelf.
  • Page 18: Replacement Procedures

    Vertiv™ eSure™ Inverter Module User Manual 3.2 Replacement Procedures 3.2.1 Inverter Module Replacement Inverters can be inserted or removed with power applied (hot swappable). NOTE! Each inverter locks into a module mounting shelf by means of a latch located on the bottom of the module. The latch and inverter handle are interactive.
  • Page 19: Inverter Fan Replacement

    Vertiv™ eSure™ Inverter Module User Manual 3.2.2 Inverter Fan Replacement Each inverter uses a fan (P/N 32010474) for cooling. If fan replacement should become necessary, perform the following procedure. Refer to Figure 3.1 as this procedure is performed. Procedure Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these alarms cannot be easily disabled, notify the appropriate personnel to disregard any alarms associated with this system while this procedure is performed.
  • Page 20 Vertiv™ eSure™ Inverter Module User Manual This page intentionally left blank.
  • Page 21 Vertiv™ eSure™ Inverter Module User Manual Connect with Vertiv on Social Media https://www.facebook.com/vertivI https://www.instagram.com/vertiv/ https://www.linkedin.com/company/vertiv/ https://www.twitter.com/vertiv/...
  • Page 22 Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2021 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp.

This manual is also suitable for:

1i1201000Esure

Table of Contents