Electronic weighing scale
[5] Service tools
Use the below service tools as exclusive tools for R32/R410A refrigerant.
Refer to the spec name plate on outdoor unit for the type of refrigerant being used.
No.
Tool name
1.
Gauge manifold
2.
Charge hose
3.
Electronic weighing scale
4.
Gas leak detector
5.
Adaptor for reverse flow check
6.
Refrigerant charge base
7.
Refrigerant cylinder
8.
Refrigerant recovery equipment
2

PART NAMES AND FUNCTIONS

• Indoor Unit
Air intake (sucks the
air inside the room
into the unit)
Specifications
· Use the existing fitting specifications. (UNF1/2)
· Use high-tension side pressure of 5.3MPa·G or over.
· Use pressure performance of 5.09MPa·G or over.
· Use the detector for R134a, R407, R410A, or R32.
· Attach on vacuum pump.
· R32 or R410A refrigerant
· Cylinder with syphon
Air outlet
In case of rear inlet
Unit
In case of bottom inlet
7