8.8. Function of the sliding jumpers for the light barriers 1 and 2 .............. 27 Overview operating foil RZ3/4 - with motor ................. 29 10. Overview operating foil RZ3/4 - without motor ................30 11. Assembly and installation ......................31 12.
About this guide The hold-open system RZ3 / RZ4 control unit is also referred to as a system or plant in the following. These operating instructions are considered an integral part of the product and must be stored in such a way that rapid access is possible at all times.
Security 4.1. Intended use The hold-open system control RZ3 / RZ4 are exclusively intended for indoor operation of conveyor system closures (in exceptional cases for automatic smoke barriers, fire doors and gates and flexible fire curtains). See also general building authority approvals: abZ: Z-6.510-2627/-2626.
Operating Manual RZ3/4 Operator Operators are all persons who are at least 18 years of age and have been instructed in the operation of the equipment by the manufacturer or an authorized representative. They must have read and understood these instructions completely.
Operating Manual RZ3/4 The system must be subjected to a monthly function check. The operator must document the function check in the log (see test logbook). The following points must be examined: ▪ Proper function (opening / closing) ▪ Optional assemblies (e.g.: Safety contact strip, area light scanners, optical and acoustic signal transmitters).
Operating Manual RZ3/4 Instruction / supervision of the operators The operator must instruct the personnel regularly and always ensure quick access to these operating instructions. The safe work of the operators must be checked by the operator at sufficiently recurring intervals.
Operating Manual RZ3/4 4.9. After the fire After a fire, the equipment must be inspected for damage by qualified personnel if the equipment in the affected fire area was exposed to the influence of fire or smoke. Contact the manufacturer or a maintenance partner authorized by the manufacturer immediately.
▪ Hold-open system control RZ4 (manual / motorized) 5.2. Marking on the product On the cover of the terminal box there are the following designations: ▪ System and type designation: smoke control panel RZ3 (RZ4) ▪ Manufacturer ▪ Input voltage ▪...
▪ Battery fault UBat < 24 V (If jumper J1 on the RZ3-MC-KL is set to ON, a trip occurs). ▪ Deep discharge protection UBat < 21.8 V Charging characteristics as a function of temperature...
Release device (3) ▪ Horn Reset (4) ▪ Motor (5) Figure 1 - Display and operating elements of the hold-open system (control) type RZ3 7.2. Power supply display field Figure 2 - Power supply Page 13 of 32 Protronic Innovative Steuerungselektronik GmbH...
Operating Manual RZ3/4 The "Power supply" display field contains the following optical signals (LED): ▪ Operation (mains) (1) ▪ Fault (collective fault power supply) (2) ▪ Network fault (3) 7.3. Functions Disturbances: In the event of a mains fault, both the LED fault (2) and the LED mains fault (3) light up. In the event of a battery fault, only the LED fault (2) lights up.
Triggering lights up and the contact Fire alarm (X1:6/7/8) does not switch. This function is used to link several RZ3. In this case, the fire alarm is reset at the control panel triggered by the fire alarm loop. The optical signal Operation (1)
Operating Manual RZ3/4 7.5. Display panel smoke control panel for conveyor termination Figure 4 - Smoke control panel The "Smoke control panel for conveyor closure" display panel contains the following visual signals (LED): Opened (1) LED " " indicates that the movable sealing element is open and the associated control element is activated accordingly.
Operating Manual RZ3/4 7.6. Display and control panel Triggering device Figure 5 - Release device The "Triggering device" display and control panel contains the following optical signals (LED) and buttons: " " - Closing - optical signal and control element (1) Button - manual closing initiates controlled closing process without activating emergency power.
Operating Manual RZ3/4 7.7. Reset horn WARNING Fire alarm, electrical fault / danger to life Do not continue working when the horn sounds an acoustic warning signal. Stop work / Use escape routes Fire alarm / malfunction If the internal horn sounds, there may be danger to life. The fire alarm has been triggered or there is a technical malfunction.
Page 19
Operating Manual RZ3/4 - Motor off - optical signal and control element (1) Pushbutton - Motor off interrupts the power supply to the drive. The associated LED remains lit until this state is reset by pressing the button. - Reset motor off - Control element (4) When the button is pressed, the "Actuator off"...
Omnicompact type. The mode of operation differs only slightly from the mode of operation of the standard RZ3 / RZ4. There is one input for external closing. The second input is used for an optional contact strip for monitoring the closing area.
The display and control panels of the hold-open systems (control) contain LEDs to indicate operating states of the FAA. The meaning of the respective display elements is described in chapter 7 "Hold-open system (RZ3 control)". 8.3. Manual opening of the FAA remote closing, fire alarm, on-site fire alarm).
Operating Manual RZ3/4 Figure 8 - Opening the FAA 8.4. Manual closing of the FAA Before closing the terminal, the LEDs 1,2,3 and 5 light up (if there is no fault). Fig. 8 Close gate manually: To close the FAA, press the button (4) on the release device of the control.
Operating Manual RZ3/4 8.6. Relay function Designation Function Condition MC-EV1 circuit board Fault EV No fault EV X1: 3/4/5 3/5 closed from EV fault (mains fault, battery too low, 4/5 closed battery defective. Passive battery test every approx. 5s., active battery test with load every 30 minutes).
Page 24
Operating Manual RZ3/4 Holding magnet no trip RZ, no on-site trip, no scraper +24V at 42 closing, no remote closing X1: 42/43 28/29 closed -on only after additional ES "open" pressed once Release X1:28/29 Immediately off on trip RZ or on-site...
Operating Manual RZ3/4 8.7. Function of the DIL switches Function of the DIL switches - Changeover switch DIL1 (only before software version RSZ016 10.06) "Drive off" delayed (0.05 s) DIL1 "decelerated motor off = 0 (on) => with delay = 1 (off) => without delay As of version RSZ016 10.06:...
Page 26
Operating Manual RZ3/4 -switch DIL3 on => without personal protection off => with personal protection In the case of personal protection, actuation of the safety device causes the closing process to stop. If the actuation takes place before triggering with the door open, a fault message is displayed immediately.
Operating Manual RZ3/4 8.8. Function of the sliding jumpers for the light barriers 1 and 2 The two light barriers are permanently monitored for wire breakage and short circuit to +24V. If no light barrier is connected to the input, the monitoring would report an error.
Page 28
Operating Manual RZ3/4 The sliding jumper on the right side of the board bridges the terminals 50 and 63 when it is in the upper position ON (as shown in the picture). In the lower position OFF, the connection between terminals 50 and 63 is removed, for use with contact strip evaluator.
Operating Manual RZ3/4 Overview operating foil RZ3/4 - with motor Page 29 of 32 Protronic Innovative Steuerungselektronik GmbH Grimmaische Str. 92, D-04828 Bennewitz, district Pausitz...
Operating Manual RZ3/4 Overview operating foil RZ3/4 - without motor Page 30 of 32 Protronic Innovative Steuerungselektronik GmbH Grimmaische Str. 92, D-04828 Bennewitz, district Pausitz...
Operating Manual RZ3/4 Assembly and installation The RZ3 and RZ4 are mounted on the wall of the Bopla housing or in a cabinet. When mounting, make sure that the batteries are inserted with the terminals facing upwards. This ensures the longest possible battery life. Attention: The battery life is directly dependent on the ambient temperature and is drastically reduced at higher ambient temperatures.
Page 32
Operating Manual RZ3/4 Commissioning Measures before or in connection with the handover of a product ready for operation, including the final acceptance test; handover of drawings, instructions for operation, maintenance and repair, if necessary, training of personnel Maintenance Combination of all technical and administrative measures to maintain a unit or product in a usable (safe for use) condition or to return it to such a condition in which it can perform the required function;...