INSTALLATION
CIRCULATED HOT WATER FLOW AND RETURN SYSTEM
A Rheem 613 series water heater can be installed as part of a circulated hot water flow and return system in
a building.
Temperature Settings
The thermostat setting of the water heater must be set to at least 60°C – AU or 65°C – NZ.
In New Zealand an approved UV sterilisation or chlorine disinfection system may be used instead of setting
the thermostat to 65°C.
If the return water temperature decreases by more than 5°C due to heat loss from the hot water ring main,
the thermostat setting of the water heater must be set to above 60°C – AU or 65°C – NZ.
Circulated Hot Water Flow and Return System – Continuous Electric Water Heater
Refer to the
page 22.
Temperature Limiting Device
A temperature limiting device cannot be installed in circulated hot water flow and return pipe work unless it is
specifically designed to do so, such as the Rheem Guardian warm water system.
The tempered water from a temperature limiting device cannot be circulated. Where a circulated hot water flow
and return system is required in a building, a temperature limiting device can only be installed on a dead leg,
branching off the circulated hot water flow and return pipe.
If circulated tempered water were to be returned back to the water heater, depending on the location of the
return line connection on the water supply line to the water heater, then either:
water will be supplied to the cold water inlet of the temperature limiting device at a temperature exceeding
the maximum recommended water supply temperature, or
when the hot taps are closed no water will be supplied to the cold water inlet of the temperature limiting
device whilst hot water will continue to be supplied to the hot water inlet of the temperature limiting device.
These conditions may result in either water at a temperature exceeding the requirements of AS/NZS 3500.4
being delivered to the hot water outlets in the ablution areas, or the device closing completely and not delivering
water at all, or the device failing. Under either condition, the operation and performance of the device cannot
be guaranteed.