5-2. Outdoor unit
¢ Discharge temperature thermistor
Temperature (°C)
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
110.0
115.0
120.0
5-2. Outdoor unit
Resistance (kΩ)
1,000.13
720.28
525.51
388.12
289.97
219.01
167.12
128.77
100.14
78.56
62.14
49.54
39.79
32.19
26.22
21.49
17.73
14.71
12.27
10.29
8.68
7.35
6.26
5.35
4.59
3.96
3.43
2.98
2.60
2.28
2.00
- (03-45) -
Voltage (V)
0.06
0.09
0.12
0.16
0.21
0.28
0.36
0.46
0.57
0.71
0.87
1.04
1.23
1.44
1.66
1.88
2.12
2.35
2.57
2.79
3.00
3.19
3.38
3.54
3.69
3.83
3.96
4.07
4.17
4.26
4.33