Product Specifications - Promation Engineering PX1 Series Installation & Operation Manual

Table of Contents

Advertisement

Product Specifications

100%
75%
Proportional
50%
On/Off/Jog
25%
50°F
75°F
100°F
10°C
24°C
38°C
Ambient Temperature
Introduction
The following procedure is to be followed for set-up, calibration, testing and use of the P Series quarter-turn
electric actuators. Each unit is shipped from the factory with initial calibration of cams and switches completed for
0-90 degree operation. However, these are general settings and serve as a starting point for proper calibration
of the actuator in its real-world application. There are no mechanical stops on this model.
Safety
Safety is a basic factor any time you maintain and operate mechanical equipment. Use of proper handling
methods, tools and clothes can help prevent serious accidents -- accidents which can cause injuries to you
or a fellow worker. This manual was created to enable a trained user to install, adjust and troubleshoot your
ProMation P Series actuator.
Only competent and trained personnel should install, maintain and repair ProMation Actuators. Any work related
to this Actuator must be carried out in accordance with this manual and related codes and regulations. Local
workplace health and safety rules should always be followed.
Duty cycle
Duty cycle is the percent of time that an actuator spends running as a fraction of the total time. Duty Cycle is
directly related to heat; overusing an actuator typically results in motor overheating which can permanently
damage it. Overheating also consumes more electricity. Generally speaking, the hotter a motor becomes, the
longer 'rest' it needs to cool down so it runs effi ciently.
Wire Sizing Chart
MAX distance between Actuator
and Supply (feet)
P1
Actuator/
12VAC/DC
Voltage
Amps
Wire
2.0A
Gage
18
41
16
65
14
105
125°F
150°F
52°C
65°C
P1
24VAC/DC
1.6A
103
162
262
Actuator Specifi cations
Torque "lb/Nm
Supply Voltage
Max Inrush Current
Running Current
Motor
Runtime (90°@60Hz/vdc)
Runtime (90
@50Hz)
O
Duty Cycle
Motor Starts
Weight
Mechanical Connections
Electrical Entry
Electrical Terminations
Environmental Rating
Manual Override
Control
Actuator Case Material
Motor Protection
Ambient Temperature
Operating Range
Page 2 of 11 P1 HV Series
PX1
P1
300"lbs/35Nm
12vac/dc
24vac/dc
2.0A
2.8/1.8A
1.9A
1.6/1.4A
DC Brush Type
15 sec
15 sec
75%
1200 per hour
5lbs/3kg
ISO5211 F03/F05 8pt 14mm
(2) 1/2" NPT
14-18ga
, 7, 9
NEMA 4/4X
8mm Socket Drive
On/Off /Jog
Aluminum Alloy, Powder coated
230°F/110°C Thermal F* Class
*Totally Enclosed Non-Ventilated Motors
-22°F to +158°F
-22°F to +125°F
-30°C to +70°C.