2.6 Wizard Startup

Context
Wizard startup allows for commissioning of components such as the indoor fan,
spray system, exhaust fan, and cooling system. It also supports component
automatic operation and automatic device checking, and can output an
commissioning report.
After you power on the smart cooling product for the first time, the screen
displays the Wizard Startup screen. If the smart cooling product is not started for
the first time, choose Maint > Wizard Startup to enter the Wizard Startup
screen.
Tapping No or Exit, submission timeout, and system exception all result in
commissioning failures. Choose Maint > Wizard Startup to enter the Wizard
Startup screen for new commissioning.
Procedure
Step 1 On the home screen, choose Maint > Wizard Startup.
Issue 02 (2023-08-03)
Figure 2-13 Requiring a startup password
If the Password required for start or shutdown onsite function is not
enabled, tap OK to start the unit.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Power-On and Commissioning
60