OmniOn Power RP450 Quick Start Manual

Integrated pole mount
Table of Contents

Advertisement

Quick Links

Quick Start Guide
RP450 Integrated Pole Mount
Quick Start Guide
Important safety instructions
Save these instructions
This equipment is not suitable for use in locations where
children are likely to be present
Read and follow all safety statements, warnings, and
precautions in this manual before installing, maintaining or
repairing this equipment.
Document - 8600452418P
Page 1
© 2023 OmniOn Power Inc. All rights reserved.
consignes de sécurité importantes
Conservez ces instructions
Cet équipement n'est pas adapté à une utilisation dans
des
endroits où des enfants sont susceptibles d'être presents
Lisez et suivez toutes les consignes de sécurité, les
avertissements et les précautions de ce manuel avant
d'installer, d'entretenir ou de réparer cet équipement.
RP450_QSG
Rev. 3.1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RP450 and is the answer not in the manual?

Questions and answers

Summary of Contents for OmniOn Power RP450

  • Page 1 Lisez et suivez toutes les consignes de sécurité, les repairing this equipment. avertissements et les précautions de ce manuel avant d'installer, d'entretenir ou de réparer cet équipement. Document - 8600452418P Page 1 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 2: Table Of Contents

    Information - Touch Up Paint ................................. 20 Parts List ........................................ 21 Specifications and Application ............................... 21 Ordering Information ..................................21 Change History ....................................22 Disclaimer ......................................23 Page 2 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 3 Figure 12 AC Input Wiring ................................16 Figure 13 Final Wire Dressing ................................17 Figure 14 Aalrm Connections ................................18 Figure 15 DC output connections ..............................18 Figure 16 AC Input connections..............................19 Page 3 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 4: Important Safety Instructions

    12. WARNING: Equipment is not designed to charge an external battery source. 13. This equipment is not suitable for use in locations where children are likely to be present Page 4 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 5: Consignes De Sécurité Importantes

    12. AVERTISSEMENT : L'équipement n'est pas conçu pour charger une source de batterie externe. 13. Cet équipement ne convient pas à une utilisation dans des endroits où des enfants sont susceptibles d'être présents Page 5 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 6: Precautions

    Effects decrease with distance. • If equipment is mounted 10 ft high or above, use an elevated platform to access equipment. Page 6 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 7: Précautions

    Les effets diminuent avec la distance. • Si l’équipement est monté à 10 pieds de haut ou plus, utilisez une plate-forme surélevée pour accéder à l’équipement. Page 7 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 8: Safety

    équipement. Figure 1 Warning Label Equipment Identification The product ID label on the front door of the RP450 model is shown below. It includes the product serial number and input - output specifications of the cabinet. 1600361512A, RP450-48-PS1-DC6B-SRG...
  • Page 9: Introduction

    Isolated alarm contacts are available for DC Fault and AC Fault. AC FIELD WIRING AC BREAKER SECTION AC SPD DC BREAKERS (OR FUSES) DC SPD DC FIELD WIRING SECTION AC CONDUIT FOR INPUT Page 9 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 10: Information - Tools Required

    3 x TERMINAL BLOCK, 3 POS • • 7 x HOLE PLUG LUG, 6AWG, 2 HOLE, #10 • • 9 x STRAIN RELIEF TERMINAL BLOCK, 2 POS Page 10 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 11: Step 1 - Mount Unit To Pole

    Lift Hook Lifting 2.5mm diameter Harness Samson Amsteel Blue Dyneema 25” 635mm Straps Attach lower Strap before removing Lifting harness Knot Figure 3 Mounting unit to pole Page 11 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 12: Step 2 - Ground The Unit

    Use a slotted screwdriver to loosen the 4 captive screws of the upper dead-front cover, then remove the upper dead-front cover. UPPER DEAD- FRONT SCREWS Figure 6 Upper dead front screws Page 12 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 13: Information - Strain Relief Detail For Output Wiring

    S, SE, SEO, SEOOW, SEOW, SJ, SJEOOW, SJEOW, SJO, SJOO, SJOOW, SJOW, SJTEOOW, SJTEOW, SJTO, SJTOO, SJTOOW, SJTOW, SJTW, SO, SOO, SOOW, SOW, SV, SVE, SVEO, SVO, SVOO. Strain relief Figure 8 Strain relief for output wiring Page 13 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 14: Step 4 - Wire The Dc Output

    One wire carries +. The other carries – terminal block. One wire carries +. The other 48V. carries –48V. GMT fuse 0.6”(16mm)Return 0.6”(16mm)Return 0.35”(9mm)CB 0.5”(13mm)CB Figure 9 DC Output wiring Page 14 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 15: Step 5 - Wire The Alarms

    Caution: Ensure that wires do not come in contact with sharp or rough surfaces that may damage insulation and cause a short circuit. Figure 11 AC Feed Page 15 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 16: Configured As Service Entrance

    10 AWG or smaller, 40 in-lb for 8 AWG using a flat bladed screw driver. bladed screw driver. Pull wire to verify. Pull wire to verify. Bond Jumper Bond Main Ground Washer Figure 12 AC Input Wiring Neutral Page 16 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 17: Step 7 - Final Wire Dressing And Close The Door

    Confirm that DC is present on the outputs by observing a signal from the repeater(s) or radio(s). Test the alarm contacts by cycling the AC to off. Observe that AC and DC alarms are active when no AC is present. Page 17 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 18: Information - Electrical Connections

    Short circuit hiccup is disabled for the first 20 seconds after start up to support the inrush requirements of the load. - 48V Figure 15 DC output connections Page 18 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 19: Ac Input Connections

    AC is present and breaker is Closed/On, and both the DC DC Fail And SPD Fail and SPD Fail are present. Normal Green No Alarms and everything Normal. Page 19 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 20: Information - External Electrical Equipment

    Should any part of the unit coating be damaged, repaint using: LVP Powder and Paints RAL7035 Touch Up Paint - Light Grey - 12 oz Spray Can. Page 20 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 21: Parts List

    Internal rectifier is in an IP 6x enclosure. Ordering Information Ordering Code Model Power (W) Redundancy Backup Load Breakers Load Fuses Surge 1600361512A RP450-48-PS1-DC6B-SRG NONE 1600408704A RP450-48-PS1-DC6F-SRG NONE Page 21 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 22: Change History

    Warning label added in safety section, Updated Product id label Updated figure 16 AC input connections 09/02/2022 Updated as per OmniOn template 12/13/2023 Page 22 © 2023 OmniOn Power Inc. All rights reserved. RP450_QSG Rev. 3.1...
  • Page 23: Disclaimer

    – in whole or in parts – is forbidden without prior document and makes no warranty with respect to written consent of OmniOn Power. This document does and assumes no liability as a result of any use of not convey license to any patent or any intellectual information in this document.

Table of Contents